TxIsoBlock-HRT
NOVUS AUTOMATION
4/4
VOLTAGE (0-50 mV)
Fig. 9
– Transmitter electrical connections (0-50 mV)
NTC
Fig. 10
– Transmitter electrical connections (NTC)
OUTPUT (4-20 mA)
Fig. 11
– Transmitter electrical connections ( 4-20 mA)
OPERATION
The transmitter is factory calibrated with standardized sensors, not
requiring any adjustment by the user.
Small corrections can be accomplished through the
TxConfig II
software (in units of temperature).
The user may choose the sensor and the range that best fits its
application. The range chosen must not exceed the maximum
measuring range defined for the sensor and must not be less than
the minimum range for the sensor.
It is important to note that the accuracy of the transmitter refers to the
maximum range of the sensor used, regardless of the actual range.
Example:
•
The sensor Pt100 has a max. range of -200 to 650 °C and total
accuracy de 0.08 %.
•
Thus, we can have an absolute error up to 0.68 °C (0.08% of
850 °C).
•
This error is possible in a wide range as the maximum (-200 to
650 ° C) or in a narrower range, set by the user as (example) 0
to 100 ° C.
SAFETY INFORMATION
Control system projects must take into account that any part of the
system has the potential to fail. This product is not a safety or
protection device and its internal alarms do not provide protection in
case of failure. External safety devices should be provided whenever
there is a risk to persons or property.
The performance and specifications of this product may be affected
by your operating environment and installation. It is the responsibility
of the user to ensure adequate grounding, shielding, cable routing
and noise filtering, following local regulations and good installation
practices and electromagnetic compatibility.
SUPPORT AND MAINTENANCE
This product does not contain any serviceable parts. Contact our
local distributor for an authorized service.
WARRANTY
Warranty conditions are available on our website
www.novusautomation.com/warranty
.