CONFIGURATION 

If the default configuration or the ordered configuration satisfies the application, then no further configuration is necessary, and the transmitter is 

ready to be used. If a new setting is desired, this can be accomplished by the 

TxConfig

 and sent to the transmitter through the 

TxConfig USB

 

interface. 
The 

TxConfig

 interface and software compose the 

Transmitter Configuration Kit

, with can be purchased separately from the manufacturer or 

one of its distributors. The software can be updated for free on 

NOVUS

 website. To install it, run the 

Tx_setup.exe

 and follow the instructions. 

The 

TxConfig

 interface connects the transmitter to the PC, as shown in figure below: 

 

Figure 8 -

 

TxConfig

 Interface USB connections 

Once the connection is accomplished,  you  must run the 

TxConfig

  software and, if necessary, use the 

Help

  topic to arrange the transmitter 

configuration. Figure below shows the 

TxConfig

 software main screen: 

 

Figure 9 -

 

TxConfig

 software main window 

The fields in the screen mean: 
1.

 

Measuring Range

: Define the transmitter humidity and temperature measurement ranges, indicating a 

Lower Limit

 value and an 

Upper Limit

 

value. 
The defined range cannot exceed the 

Sensor Measuring

 shown in this same field, and cannot establish a range with a span less than the 

Minimum Range

 indicated below in this same field. 

When the 

Lower Limit

 is set to a value higher than the 

Upper Limit

, the output current has a decreasing behavior (20 ~ 4 mA). 

2.

 

Sensor Failure

: Establish the transmitter output behavior in the presence of a sensor fail. When 

Minimum

 is selected, the output assumes its 

minimum value (4 mA) (down-scale). When 

Maximum 

is selected, it assumes its maximum value (20 mA) (up-scale). 

3.

 

Zero Correction

: Correct, in the output value, small measurement errors presented by the transmitter. 

4.

 

Device Information

: This field contains data that identifies the transmitter and is important in any queries to the manufacturer. 

5.

 

Read Device

: When selected, allows you to read the configuration present on the connected transmitter. 

6.

 

Apply

: When pressed, allows you to send the configuration to the connected transmitter. 

Note

: The factory default configuration is (unless otherwise specified or ordered): 

 

Measuring ranges: 0 to 100 °C and 0 to 100 % RH. 

 

Correction zero: 0 °C. 

 

Upscale when sensor fails.

 

It is important to notice that the transmitter accuracy is always based on the total span of the used sensor, even if a narrower range is configured. 

Example: 

Содержание RHT-WM

Страница 1: ...NOVUS AUTOMATION 1 8 RHT WM and RHT DM Transmitter INSTRUCTIONS MANUAL V2 0x A ...

Страница 2: ...Duct Mount model must be attached with a flange The flange is attached to the duct wall After this the transmitter probe must be inserted into the flange center hole and then fixed Figure 1 shows the dimensions and drilling of the polyamide 6 6 flange Figure 1 Mounting flange for RHT DM The probe is made of stainless steel with lengths of 150 mm 250 mm or 400 mm Figure 2 Model RHT DM dimensions Th...

Страница 3: ...l indicator controller register etc The connection wires go inside the transmitter trough to the cable gland mounted in the transmitter housing INSTALLATION RECOMMENDATIONS Electronic and analog signal conductors should run through the plant separately from the output and supply conductors If possible in grounded conduits The power supply for electronic instruments must come from a network suitabl...

Страница 4: ...2 Remove the tip by turning it counterclockwise Step 3 Without the tip the sensor will be exposed Remove it by pulling it forward to disconnect it Step 4 Connect the new sensor to the probe tip connector using clean antistatic gloves or other measures to avoid static discharges Avoid unnecessary handling Hold the sensor by the connector or its surroundings Avoid handling the sensor by the thinner ...

Страница 5: ...it value and an Upper Limit value The defined range cannot exceed the Sensor Measuring shown in this same field and cannot establish a range with a span less than the Minimum Range indicated below in this same field When the Lower Limit is set to a value higher than the Upper Limit the output current has a decreasing behavior 20 4 mA 2 Sensor Failure Establish the transmitter output behavior in th...

Страница 6: ...u must follow the following steps Connect the device to the TxConfig interface and run the software The software will recognize the RHT model read its configuration and make it available to the user In the Options menu enter Humidity Reading Type only available when an RHT model is detected and select the Dew Point option At this point the values of the scales will be converted to the dew point un...

Страница 7: ...T2 output resolution 0 022 mA 4 20 mA Isolation between loops 4 20 mA outputs are isolated from each other Provides protection against power supply polarity inversion Yes Protection Electronic circuit case IP65 Sensor capsule IP40 Cable entrance Cord grip PG7 Operating limits Sensor and Probe RHT DM See Figure 11 Electronic circuit Electronic circuit WM DM Operating temperature 10 to 65 C 14 to 14...

Страница 8: ...his is a Class A product In a domestic environment this product may cause radio interference in which case the user may be required to take adequate measures 5 WARRANTY Warranty conditions are available on our web site www novusautomation com warranty ...

Отзывы: