NOVUS AUTOMATION
18/28
NP785-20 Model: Information Registers Table
Address
Name
Description
R/W
Type
Standard
Min.
Max.
Decimal Places
300
HR_NUM_SERIEH
Serial number High
RO
uint_32
-
0x0000
0xFFFF
N.A.
301
HR_NUM_SERIEL
Serial number Low
-
0x0000
0xFFFF
N.A.
302
HR_VERSAO_SW
Firmware version
RO
uint16
-
0x0000
0xFFFF
2
303
HR_RELEASE
Release version
RO
uint16
-
0x0000
0xFFFF
0
304
HR_ID
ID
RO
uint16
0xB3
0x0000
0xFFFF
N.A.
305
HR_MODEL
Informs the product
model
RO
uint16
0
0x0000
0xFFFF
N.A.
341
HR_DIAGNOSE01
Diagnostic**
RO
uint16
0
0x0000
0xFFFF
N.A.
342
HR_DIAGNOSE02
RO
uint16
0
0x0000
0xFFFF
N.A.
343
HR_DIAGNOSE03
RO
uint16
0
0x0000
0xFFFF
N.A.
359
HR_PRESS_HIGH_LIMIT
Maximum limits
RO
uint32
20 mbar
290,08 mpsi
8,029 inH2O
203,94 mmH2O
2000,0 Pa
-20 mbar
-290,08 mpsi
-8,029 inH2O
-203,94 mmH2O
-2000,0 Pa
20 mbar
290,08 mpsi
8,029 inH2O
203,94 mmH2O
2000,0 Pa
mbar:
3 decimal
places
mpsi:
2 decimal places
inH2O:
3 decimal
places
mmH2O:
2 decimal
places
Pa:
1 decimal place
360
HR_PRESS_HIGH_LIMIT_H
361
HR_PRESS_LOW_LIMIT
Minimum limits
RO
uint32
-20 mbar
-290,08 mpsi
-8,029 inH2O
-203,94 mmH2O
-2000,0 Pa
-20 mbar
-290,08 mpsi
-8,029 inH2O
-203,94 mmH2O
-2000,0 Pa
20 mbar
290,08 mpsi
8,029 inH2O
203,94 mmH2O
2000,0 Pa
mbar:
3 decimal
places
mpsi:
2 decimal places
inH2O:
3 decimal
places
mmH2O:
2 decimal
places
Pa:
1 decimal place
362
HR_PRESS_LOW_LIMIT_H
** Check the
Table 11
for more information about the device configuration registers.
Table 09
– NP785-20 Model: Information Registers
Table 10
lists the device configuration registers and the captions for their respective values:
Register
Name
Value
Description
101
HR_OUT1_TYPE
0
Output 4-20 mA;
Output 0-10 V.
1
107
HR_OUT1_ERR
0
Low alarm in case of failure;
High alarm in case of failure;
Low/high alarm in case of failure.
1
2
115
HR_UNIT_SYSTEM
0
Unity: mbar;
Unity: mpsi;
Unity: inH2O;
Unity: mmH2O;
Unity: Pa.
1
2
3
4
122
HR_A1FU
0
Alarm: Off;
Alarm: Sensor Error;
Alarm: Lower Setpoint;
Alarm: Higher Setpoint;
Alarm: Intra-range;
Alarm: Extra-range.
1
2
3
4
5
137
HR_BAUD
0
Baud Rate:
1200 bps;
Baud Rate:
2400 bps;
Baud Rate:
4800 bps;
Baud Rate:
9600 bps;
Baud Rate:
19200 bps;
Baud Rate:
38400 bps;
Baud Rate:
57600 bps;
Baud Rate:
115200 bps.
1
2
3
4
5
6
7
138
HR_PRTY
0
1
2
Parity: No parity;
Parity: Odd parity;
Parity: Even parity.
Table 10
– Subtitle
www.
GlobalTestSupply
.com
Find Quality Products Online at: