Novus N480D Скачать руководство пользователя страница 6

N480D Controller  

NOVUS AUTOMATION 

                                                                                                                                                

 

   6/6

 

FINDING THE CONTROLLER’S VERSION AND SERIAL NUMBER 

When the controller is turned on, it shows on its displays for three 

seconds its 

version

  (review). To see the 

serial number

  turn the 

controller on holding the 

 key. 

This information is necessary for eventual contact with the controller’s 

manufacturer. 

SPECIFICATIONS 

DIMENSIONS

: ........................................ 48 x 48 x 110 mm (1/16 DIN) 

 ............................................................ Approximate Weight: 150 g 

CUTOUT IN THE PANEL

: ................... 45.5 x 45.5 mm (+0.5 -0.0 mm) 

POWER SUPPLY

: ..................... 100 to 240 Vac/dc (±10 %), 50/60 Hz 

 

Optional 24 V: .....................  12 to 24 Vdc / 24 Vac (-10 % / 20 %) 

 

Maximum consumption: .........................................................  6 VA 

ENVIRONMENTAL CONDITIONS

Operation Temperature: ...............................................  5 to 50 

°

Relative Humidity: .......................................... 80 % max. up 30 °C 
For temperatures above 30 °C, reduce 3 % for each °C 
Internal Use; Category of installation II, Degree of  pollution 2; 

altitude < 2000 m. 

INPUT

 .......................... Thermocouples, Pt100 (according to 

Table 1

Internal Resolution

: ................................... 32767 levels (15 bits) 

Resolution of Display

: ...... 12000 levels (from -1999 up to 9999) 

Rate of input reading

: .................................. up to 55 per second 

Precision

:.. Thermocouples 

J

K

T

,

 E

: 0.25 % of the 

span

 

±

1 °C 

 .................. Thermocouples 

N

R

S

B

: 0.25 % of the 

span

 

±

3 °C 

 ................................................................ Pt100: 0.2 % of the 

span

 

Input Impedance

: ................. Pt100 and thermocouples: >10 M

 

Measurement of Pt100

: .............. Three wires type, (

α

=0.00385) 

with compensation for cable length, excitation current of 0.170 mA. 
All input and output types are factory-calibrated. Thermocouples 

according to standard NBR 12771 / 99, RTD’s NBR 13773 / 97; 

OUTPUTS 

OUTa / OUTC ........................... Relay SPST-NA: 1.5 A / 240 Vac, 

 

 ....................................... General use, resistive load; 100 k cycles 
OUTB .........................  Voltage pulse for SSR, 12 V max. / 20 mA

 

OUTD (RPR / RRR) ....... Relay SPDT: 3 A / 250 Vac, general use

 

OUTD (RAR).................................................. 0-20 mA or 4-20 mA

 

 ................................................ 550 

 max. 31000 levels, Isolated

 

ELECTROMAGNETIC COMPATIBILITY

 ........................................ EN 61326-1:1997 and EN 61326-1/A1:1998 

SAFETY

: .......................... EN61010-1:1993 and EN61010-1/A2:1995 

USB INTERFACE

:  2.0, CDC class  (virtual communications port), 

MODBUS RTU protocol.

 

FRONT PANEL

: IP65, polycarbonate UL94 V-2.

 

STARTS UP OPERATION

:  After  3 seconds connected to the power 

supply. 

CERTIFICATIONS

: .................................................... CE / UL (FILE: E300526) 

 
 
 
 
 
 
 

MODEL IDENTIFICATION 

The sticker on the controller presents the identification of the model, as 

described below. 

N480 D - A - B 
Where A =   
 

RP

:  OUTA: Relay; OUTB: Pulse 

 

RPR

:  OUTA: Relay; OUTB: Pulse; OUTD: Relay

 

 

 

RAR

:  OUTA: Relay; OUTB: Pulse; OUTC: Relay; OUTD: mA 

 

 

RRR

:  OUTA: Relay;  OUTB:  Pulse;  OUTC:  Relay; OUTD: Relay 

Where B =

 ........................... 

24V

 for power supply 12 to 24 Vdc / 24 Vac  

 

 ..................................... 

blank

: power supply 100~240 Vac/dc 

WARRANTY 

Warranty conditions are available on our website 

www.novusautomation.com/warranty

 

Содержание N480D

Страница 1: ...C 454 to 2372 F R Tc R Range 50 to 1760 C 58 to 3200 F S Tc S Range 50 to 1760 C 58 to 3200 F B Tc B Range 400 to 1800 C 752 to 3272 F E Tc e Range 90 to 730 C 130 to 1346 F Pt100 Pt Range 199 9 to 850 C 328 to 1562 F Table 1 Types of sensors accepted by the controller CONTROL OUTPUTS AND ALARM OUTA OUTB OUTC AND OUTD The controller can have 2 3 or 4 outputs which can be configured as control outp...

Страница 2: ...fter this time the controller displays the first parameter of the next cycle Tuning Cycle Holding the key down for three seconds the next cycle Input Cycle is also accessed Release the key in the desired cycle Press the key again to access all other parameters of this cycle The key allows to return parameters within the cycle The upper display shows the parameter and the lower display shows the va...

Страница 3: ...t to ON OFF action Pb 0 Adjustable between 0 5 and 99 99 KySt HYSterisis CONTROL HYSTERESIS Hysteresis for ON OFF control set in temperature units This parameter is only used when the controller is in ON OFF mode Pb 0 A1SP A2SP Alarm SP SETPOINT FOR ALARM 1 AND 2 Tripping point for alarm 1 and 2 PROGRAM CYCLE Ptol Program Tolerance Maximum admitted deviation of PV with respect to SP If exceeded th...

Страница 4: ...se between Ramp to Cycle rate and a complete Ramp and Cycle program Pr User can also choose to not execute any type of program none PROGRAMS OF RAMP AND SOAK Available when the Rate option in the Pr Ty parameter is selected The controller allows the process temperature to vary gradually from an initial value until a specified final value determining a Ramp like behavior The initial value of the Ra...

Страница 5: ...Band Slow answer Decrease Great oscillation Increase Rate of Integration Slow answer Increase Great oscillation Decrease Derivative Time Slow answer or instability Decrease Great oscillation Increase Table 3 Guidance for manual adjustment of the PID parameters ALARMS FUNCTIONS The minimum and maximum alarms are used to signalize extreme temperature values These extreme values are defined on the A1...

Страница 6: ...mpedance Pt100 and thermocouples 10 MΩ Measurement of Pt100 Three wires type α 0 00385 with compensation for cable length excitation current of 0 170 mA All input and output types are factory calibrated Thermocouples according to standard NBR 12771 99 RTD s NBR 13773 97 OUTPUTS OUTa OUTC Relay SPST NA 1 5 A 240 Vac General use resistive load 100 k cycles OUTB Voltage pulse for SSR 12 V max 20 mA O...