Novus N322S Скачать руководство пользователя страница 2

b1y 

Booster

 

Booster output 1 activating temperature hysteresis (

SP1

). 

Adjustable between 0.1 and 50.0 ºC 

dly 

Delay

 

Control start delay. After having the controller turned on, the control output 

will be activated after the time programmed in this parameter has lapsed. 
Value in seconds, from 0 to 250 seconds. 

0f1 

Offset Sensor 1

 

Offset correction value for the temperature measured by the sensor 1. This 

parameter allows for small adjustments in the sensor 1 temperature reading. 

Measurement differences may happen, for instance, when  a  temperature 

sensor is replaced. 
Adjustable from -10.0 to 10.0 °C. 

0f2 

Offset Sensor 2

 

Offset correction value for the temperature measured by the sensor 2.  This 

parameter allows  small adjustments to  the  sensor 2  temperature  reading. 

Measurement differences may occur, for instance, when a temperature sensor 

is replaced. 
Adjustable from -10.0 to 10.0 °C. 

spl 

SP Low Limit

 

Lower

 limit of the setpoint value: defines the 

minimum

 value for setpoint 

adjustment. In degrees. 
Adjustable between -50 and 120 °C. 

spk 

SP High Limit

 

Upper

  limit of the setpoint: defines the 

maximum

  value for setpoint 

adjustment. Must be defined with a value necessarily 

higher

 than 

spl

. In 

degrees. 
Adjustable between -50 and 120 °C. 

Add 

Address

 

Modbus Address: used to define a unique network address in instruments 

that are featured with the optional RS485 Modbus RTU communication.  
Address range is from 1 to 247. 

Level 3 – Calibration level 

The N322S inputs are factory calibrated and recalibration should only be done by qualified 

personnel. If you are not familiar with these procedures do not attempt to calibrate this. 
Press the 

  key  for 

10  seconds

  to access this level. This level contains  also  the 

parameters for configuration the protection. 

If you have entered this level accidentally, go through all the parameters without making 

any changes until the controller returns to the measurement level. 

pas 

Password

  –  Enter the correct password to unlock write operations in the 

following parameters.

 

[l1 

Calibration

 

Low Input 1

 – Input 1 offset.  

[k1 

Calibration High Input 1

 – Gain adjustment (full scale value).  

[l2 

Calibration Low Input 2

 - Input 2 offset. 

[k2 

Calibration High Input 2

 – Input 2 gain adjustment (full scale value).  

FA( 

Factory Calibration

 – Restores factory calibration parameters. Change from 

0

 to

1

 to restore the calibration parameters with factory values. 

Prt 

Protection

 – Defines the levels of parameters that will be password protected. 

See "

Configuration Protection

" for details. 

Pa( 

Password Change

 – Allows changing the current password to a new one. 

Values from 1 to 999 are allowed. 

Sn2 

Serial number 2

 – First part of the controller electronic serial number. 

sn1 

Serial number 1

 – Second part of the controller electronic serial number. 

sn0 

Serial number 0

 –

 Third part of the controller electronic serial number.

 

WORKING WITH THE CONTROLLER 

While the solar collector is receiving energy, the temperature in the sensor S1 increases. 

When T1 –  T2 is higher than the value specified in 

d0n

, the pump will be turned on, 

circulating the heated water down and storing it in the tank. 
As the pump is operating, the hot water will circulate downwards and the cold water goes 

upwards. Consequently, the temperature difference between S1 and S2 tends to diminish. 

When this difference goes under the value configured in 

d0f

, the pump will be turned off 

and the water circulation will stop. 
The signaler 

P1

 at the front panel of the controller will light up when the control output is 

activated. The signaler 

P2

 light up when the booster output is activated. 

 

Fig. 2

 – Front Panel 

Indicator 

Function 

T1 

Sensor 1 temperature 

T2 

Sensor 2 temperature 

T1   T2 

S1 – S2 (Differential Temperature) 

CONFIGURATION PROTECTION 

A protection system to avoid unwanted changes to the controller parameters is implemented. 

The level of protection can be selected from partial to full. The following parameters are part 

of the protection system: 

Pas

:   When this parameter is presented, the correct 

password

  should be entered to 

allow changes of parameters in the following levels.

 

Prt

:   Defines the level of parameters that will be password protected: 

1

 -   Only 

calibration

 level is protected (factory configuration); 

2

 -  

Calibration

 and 

configuration

 levels are protected; 

3

 -  All levels are protected – 

calibration

configuration

 and 

setpoints

PA(

:

 

Parameter for definition of a new password. Since it is located in the calibration 

level, can only be changed by a user that knows the current password. Valid 

passwords are in the change 1 to 999. 

CONFIGURATION PROTECTION USAGE 

PAS

  parameter is displayed before entering a protected level. If the correct password is 

entered, parameters in all following levels can be changed. If wrong or no password is 

entered, parameters in the following levels will be read only. 

Important notes

1 - After 

five

 consecutive attempts to enter a wrong password, new tentative will be blocked 

for the next 10 minutes. If the current valid password is unknown, the 

master password

 

can be used 

only

 to define a new password for the controller. 

2 - The password for a brand new device is 111. 

 

 

 

MASTER PASSWORD 

The master password allows user to define a new password for the controller, even if the 

current password is unknown. The master password is based in the serial number of the 

controller, and calculated as following: 

[ 1 ] + [ higher digit of SN2 ] + [ higher digit of SN1 ] + [ higher digit of SN0 ] 

For example the master password for the device with serial number 987123465 is: 

1936

 

As follows:  

sn2

= 987;  

sn1

= 123;  

sn0

= 465  =   1 + 9 + 3 + 6 

How to use the master password: 

1- Enter the master password value at 

PaS

 prompt. 

2- Go to 

PA(

 parameter and enter the new password, which must not be zero (

0

). 

3- Now you can use this new password to access all controller parameters with modify rights. 

ERROR MESSAGES 

Sensor measurement errors force the controller outputs to be turned off.  The cause for these 

errors may have origin in a bad connection, sensor defect (cable or element) or system 

temperature outside the sensor working range. The display signs related to measurement errors 

are shown below: 

 

 

Measured temperature exceeded 

maximum

  allowed range for 

the sensor. Short circuited 

NTC

 sensor. 

IND

 = 

0

 or 

1

 

 

 

Measured temperature is below 

minimum

 measurement range 

of the sensor. Broken 

NTC

IND

 = 

0

 or 

1

 

 

 

If the temperature in S1 or S2 exceeds the measurement limit 

IND

 = 

2

, the differential value displayed is 

0

WARRANTY 

Warranty conditions are available on our website 

www.novusautomation.com/warranty

.

 