Novus N322RHT Скачать руководство пользователя страница 2

Unt 

Unit

 

Temperature

 

Unit

 - Selects display indication for degrees Celsius or Fahrenheit. 

0

 - Temperature Celsius 

1

 - Temperature in degrees Fahrenheit 

0fk 

Offset 

Humidity

 

RH Offset

 - Offset value to be added to the displayed relative humidity to compensate 

for sensor mismatches (when replacing a sensor, for instance). Adjustment range: 

between –10.0 and 10.0 % of RH. Default value: 0.0  

0ft 

Offset 

temperature 

Temperature Offset

  -  Offset value to be added to the measured temperature to 

compensate for sensor mismatches. Adjustment range: between –10.0 and 10.0 % of 

RH.   Default value: 0.0 

Sl1 

SP Low Limit 1 

Lower limit value for 

SP1

 (minimum value with which 

SP1 

can be configured)

.

 Sl1 

must be programmed with a lower value than 

sK1

Sk1 

SP High Limit 1 

Upper limit for 

Sp1

 (maximum allowed value for 

Sp1

). 

sK1

 must be programmed with 

a value lower than the one configured in 

sl1

Sl2 

SP Low Limit 2 

Lower limit value for 

SP2

 (minimum value with which 

SP2 

can be configured)

.

 Sl2 

must be programmed with a lower value than 

sK2

Sk2 

SP High Limit 2 

Upper limit for 

Sp2

 (maximum allowed value for 

Sp1

). 

sK2 

must be programmed 

with a value lower than the one in 

sl1

ky1 

Histeresis 1

 

OUTPUT 1 Hysteresis

: defines the differential range between the input variable value at 

which the OUTPUT 1 is turned on and the value at which it is turned off. In degrees. 

ky2 

Histeresis 2

 

OUTPUT 2 Hysteresis

: defines the differential range between the input variable value at 

which the OUTPUT 2 is turned on and the value at which it is turned off. In degrees. 

Ac1 

Action 1 

Control action for OUTPUT 1 : 

0

     

Reverse: For heating or humidification. Outputs turn on when variable is 

lower than SP (See 

(nt

 parameter below). 

1

 

  Direct: For cooling or dehumidification. Output turns on when variable is 

above SP. 

2

 

  Low (minimum value) alarm. 

3

 

  High (maximum value) alarm. 

4

 

Low alarm with initial blocking. 

5

 

High alarm with initial blocking 

Ac2 

Action 2 

Action 2 - Control OUTPUT 2 action or Alarm functions: 

0

  Reverse control action (heating or humidification). (See 

(nt

 parameter below). 

1

 

Direct control action (cooling or dehumidification). 

2

 

Low (minimum value) alarm. 

3

 

 High (maximum value) alarm. 

4

 

Alarm inside the range 

5

 

Alarm outside the range. 

6

 

Low alarm with initial blocking. 

7

 

High alarm with initial blocking. 

8

 

Inside the range alarm with initial blocking. 

9

 

Outside the range alarm with initial blocking. 

The section 

Working with the RHT Controller 

describes how these functions work. 

(nt 

Control

 

Assigns the relay for each variable:  

0

  OUTPUT 1 = RH;    

  OUTPUT 2 = RH; 

1

 

OUTPUT 1 = RH;   

  OUTPUT 2 = Temperature; 

2

 

OUTPUT 1 = Temperature;  OUTPUT 2 = RH; 

3

 

OUTPUT 1 = Temperature;  OUTPUT 2 = Temperature; 

of1 

Off time 1 

Off time 1

 - Defines the minimum 

off

 time for control OUTPUT 1. Once OUTPUT 1 is 

turned off, it remains so for at least the time programmed in 

of1

. For thermocouple 

inputs this parameter is not available. This parameter is intended for refrigeration 

systems where longer compressor life is desired. For heating systems, program

 of1

 

to zero. Value in seconds, 0 to 999 s. 

on1 

on time 1 

On time 1

 - Defines the minimum 

on

 time for control OUTPUT 1. Once turned on, 

OUTPUT 1 remains so for at least the time programmed in 

on1

. For thermocouple 

inputs this parameter is not available. This parameter is intended for refrigeration 

systems where increased compressor life is desired. For heating systems, program

 

on1

 to zero. Value in seconds, 0 to 999 s. 

dl1 

Delay 1 

Delay 1

 - Delay time to start control. Upon power-on, control OUTPUT 1 is kept 

off

 until 

the time programmed in 

dl1

  is elapsed.  Its usage is intended to prevent multiple 

compressors to start simultaneously after the turn-on of a system with several 

instruments.  Value in seconds, 0 to 250 s. 

of2 

Off time 2 

Off time 2

 - Defines the minimum 

off

 time for control OUTPUT 2. Once OUTPUT 2 is 

turned off, it remains so for at least the time programmed in 

of2

. For thermocouple 

inputs this parameter is not available. This parameter is intended for refrigeration 

systems where increased compressor life is an issue. For heating systems, program

 

on2

 to zero. Value in seconds, 0 to 999 s. 

on2 

on time 2 

On time 2

 - Defines the minimum 

on

 time for control OUTPUT 2. Once turned on, 

OUTPUT 2 remains so for at least the time programmed in 

on2

. For thermocouple 

inputs this parameter is not available. This parameter is intended for refrigeration 

systems where increased compressor life is desired. Value in seconds, 0 to 999 s. For 

heating systems, program

 of2

 to zero. 

dl2 

Delay 2 

Delay 2

 - Delay time for OUTPUT 2 to turn on relative to OUTPUT 1. This parameter 

defines a particular working mode, typically used in multiple stage systems, where 

OUTPUT 2 is allowed to go 

on

  only if OUTPUT 1 is already on for at least 

dL2

 

seconds.  Also, OUTPUT 2 is driven 

off 

whenever OUTPUT 1 goes off. 

dL2

=

  0 

disables this function. Value in seconds, 0 to 250 s. 

Add 

Address

 

Address

  –  The parameter

  Add

  is presented in instruments loaded with the optional 

RS485 Modbus RTU communication interface.  
Set a unique Modbus address for each equipment connected to the network. Address 

range is from 1 to 247. 

Level 3 – Calibration level 

The N322RHT is factory adjusted and calibrated using traceable standards. The following parameters 
should be accessed only by experienced personnel. To enter this cycle, the 

  key must be kept 

pressed for 4 seconds. 

Don’t press the 

 

and

 

 

keys if you are not sure of the calibration procedures. Just press the 

 key a few times until the measurement level is reached again.

 

pas 

Password - Enter the correct password to unlock write operations for the parameters in the 

following levels.

 

(rk

 

RH Calibration low

. Offset calibration for RH. 

(tp

 

T Calibration low

. Offset calibration for Temperature. 

Prt 

Protection  - Defines the levels of parameters that will be password protected. See 

"Configuration Protection" for details. 

Pa( 

Password Change - Allows changing the current password to a new one. Values from 1 to 

999 are allowed. 

Sn2

 

Serial number - First part of the electronic serial number of the instrument.  

This is a read only parameter. 

sn1

 

Serial number - Second part of the electronic serial number of the instrument. This is a 

read only parameter. 

sn0

 

Serial number - Third part of the electronic serial number of the instrument. This is a read 

only parameter. 

 

ERROR MESSAGES 

Sensor measurement errors force the controller outputs to be turned off.  The cause for these errors may 

have origin in a bad connection, sensor defect (cable or element) or system temperature outside the 

sensor working range. The display signs related to measurement errors are shown below 

 

Overflow 

 

Underflow 

 

 

Sensor error 

CONFIGURATION PROTECTION 

A protection system to avoid unwanted changes to the controller parameters is implemented. The level of 

protection can be selected from partial to full. The following parameters are part of the protection system: 

Pas

:   When this parameter is presented, the correct password should be entered to allow changes of 

parameters in the following levels.

 

Prt

:   Defines the level of parameters that will be password protected: 

1 -  Only calibration level is protected (factory configuration); 
2 -  Calibration and Configuration levels are protected; 

             3 -     All levels are protected - calibration, Configuration and setpoints. 

PA(

 

Parameter for definition of a new password. Since it is located in the calibration level, can only be 

changed by a user that knows the current password. Valid passwords are in the range 1 to 999.

 

Configuration protection usage 

The 

PAS

 parameter is displayed before entering a protected level. If the correct password is entered, 

parameters in all following levels can be changed. If wrong or no password is entered, parameters in the 

following levels will be read only. 

Important notes:

 

1- After five consecutive attempts to enter a wrong password, new tentative will be blocked for the next 10 

minutes. If the current valid password is unknown, the master password can be used only to define a 

new password for the controller. 

2 - The factory default password is 

111

MASTER PASSWORD 

The master password allows user to define a new password for the controller, even if the current password is 

unknown. The master password is based in the serial number of the controller, and calculated as following: 

 [ 1 ] + [ higher digit of SN2 ] + [ higher digit of SN1 ] + [ higher digit of SN0 ] 

for example the master password for the device with serial number 987123465 is: 

1 9 3 6

 

as follows: 

1 +

 

sn2

= 987;   

sn1

= 123;   

sn0

= 465 =  1 + 9 + 3 + 6 

How to use the master password:

 

1-  Enter the master password value at   

PaS 

prompt.

 

2-   Go to 

PA(

 parameter and enter the new password, which must not be zero (

0

).

 

3-   Now you can use this new password to access all controller parameters with modify rights. 

WARRANTY 

Warranty conditions are available on our website 

www.novusautomation.com/warranty

Отзывы: