Novus N3000 Скачать руководство пользователя страница 7

Controller N3000  

NOVUS AUTOMATION

 

7/9

 

RAMP AND SOAK PROFILE PROGRAM 

Seven  ramp  and  soak  profiles  with  up  to 

7  segments

  each can be 

programmed. Longer profiles of up to 49 segments can be created by 
linking 2 or more profiles. 

 

SP  

tim e 

T1 

T 2 

T 3 

T4 

T5 

SP0 

S P1 

S P2 

S P3 

SP 4 

S P5 

SP 6 

S P7 

T 6 

T7 

 

 

SV 

time 

T1 

T2 

T3 

SP0 

SP1 

SP2 

SP3 

T4=0 

 

Figure 11

 - Example of a complete ramp 

and soak profile 

Figure 12

 - Example of a profile 

with fewer segments. (T4 is set 0) 

To execute a profile with fewer segments just program 0 (zero) for the 
time intervals that follow the last segment to be executed. 

The  program  tolerance  “

Ptol

Ptol

Ptol

Ptol

”  defines  the  maximum  deviation 

between PV and SV for the execution of the profile. If this deviation is 
exceeded,  the  program  will  be interrupted until the deviation falls to 
within the tolerance band. 

Programming  0  (zero)  at this prompt disables the tolerance and the 
profile execution will not to be halted even if PV does not follow SV 
(time priority as opposed to SV priority). 

The ramp and soak event function is used to activate alarms at any 
segment of program 1. This applies only to program 1. 

LINK OF PROGRAMS 

It  is  possible  to  create  a  more  complex  program,  with  up  to  49 
segments,  joining  the  seven  programs.  This  way,  at  the  end  of  a 
program execution the controller immediately starts to run another one. 

When  a  program  is  created,  it  must  be  defined  in  the  “

LP

LP

LP

LP

"  screen 

whether there will be or not another program. 

To  make  the  controller  run  a  given  program  or  many  programs 
continuously, it is only necessary to link a program to itself or the last 
program to the first.

 

 

SV 

time 

T1 

T2 

T3 

T4 

T5 

T1 

T2 

T3 

T4 

SP0 

SP1 

SP2 

SP3 

SP4 

SP5 / SP0 

SP1  SP2 

SP3 

SP4 

Program 1 

Program 2 

 

Figure 13

 - Example of two linked programs

 

EVENT ALARM 

To  enable  this  event  function  the  alarms  to  be  activated  must  be 
selected for 

rS

rS

rS

rS

 function and are programmed at the 

PE 0

PE 0

PE 0

PE 0

 to 

PE 5

PE 5

PE 5

PE 5

 

prompts.  The  number  to  be  programmed  at  the  prompt  defines  the 
alarms to be activated (

Table 5

). 

CODE 

ALARM 1 

ALARM 2 

ALARM 3 

ALARM 4 

0

0

0

 

 

 

 

 

 

 

1

1

1

 

 

 

 

 

 

2

2

2

 

 

 

 

 

 

3

3

3

 

 

 

 

 

4

4

4

 

 

 

 

 

 

5

5

5

 

 

 

 

 

6

6

6

 

 

 

 

 

7

7

7

 

 

 

 

8

8

8

 

 

 

 

 

 

9

9

9

 

 

 

 

 

10

10

10

10 

 

 

 

 

 

11

11

11

11 

 

 

 

 

12

12

12

12 

 

 

 

 

 

13

13

13

13 

 

 

 

 

14

14

14

14 

 

 

 

 

15

15

15

15 

 

 

 

Table 5

 - Event codes for ramp and soak 

To configure and execute a ramp and soak program: 

 

Program the tolerance value, SV, time and event. 

 

If  any  event  alarm  is  required  program  the  ramp  and  soak  event 
function. 

 

Set the control mode to automatic. 

 

Select ramp and soak program to be executed at prompt 

Prn

Prn

Prn

Prn

 

(0 to 7)  

 

Start control at the 

rvn

rvn

rvn

rvn

 prompt by selecting YES. 

Before executing the program the controller waits for PV to reach the 
first set point SP0 if 

PtoL

PtoL

PtoL

PtoL

 is different than zero.  

Should  any  power  failure  occur  the  controller  resumes  at  the 
beginning of the segment it currently is. 

AUTO TUNE 

During  auto  tune  the  process  is  controlled  in  ON/OFF  mode  at  the 
programmed  SetPoint  (SV).  Depending  on  the  process 
characteristics large oscillations above and below SV may occur and 
auto tuning may take several minutes to be concluded. 

The recommended procedure is as follows: 

 

Disable the control output at the 

rvn

rvn

rvn

rvn

 prompt by selecting NO. 

 

Select auto mode operation at the 

Avto

Avto

Avto

Avto

 prompt by selecting YES. 

 

Disable the ramp and soak function (select NO) and program a new 
SV value other than the present PV (close to the desired set point). 

 

Enable auto tuning at the 

Atvn

Atvn

Atvn

Atvn

 prompt by selecting YES. 

 

Enable the control output at the 

rvn

rvn

rvn

rvn

 prompt by selecting YES. 

During the auto tune procedure the soft-start function will not operate 
and large oscillations will be induced around the setpoint. Make sure 
the  process  can  accept  these  oscillations  and  fast  control  output 
changes. 

If auto tuning results are not satisfactory refer to Table 6 for manual 
fine tuning procedure. 

PARAMETER 

RESPONSE 

SOLUTION 

Slow Response 

Decrease 

Proportional Band 

Large Oscillation 

Increase 

Slow Response 

Incre ase 

Integral Rate 

Large Oscillation 

Decrease 

Slow Response or Instability 

Decrease 

Derivative Time 

Large Oscillation 

Increase 

Table 6

 - Suggestions for manual tuning of PID parameters 

CALIBRATION 

INPUT CALIBRATION 

All inputs are factory calibrated and recalibration should only be done 
by  qualified personnel. If you are not familiar with these procedures 
do not attempt to calibrate this instrument. The calibration steps are: 

a)

  Select the input type to be calibrated. 

b)

  Set the desired upper and lower display limits. 

c)

  At the input terminals inject an electrical signal corresponding to 

a  known  indication  value  a  little  higher  than  the  lower  display 
limit. 

d)

  Select the 

inL(

inL(

inL(

inL(

 prompt. Through the 

 and 

 keys adjust 

PV so that it matches the injected signal. 

e)

  Inject a signal that corresponds to a value a little lower than the 

upper limit of the display. 

f)

  Select the 

ink(

ink(

ink(

ink(

 prompt. Through the 

 and 

 keys adjust 

PV so that it matches the injected signal. 

g)

  Repeat steps 

c)

 to 

f)

 to improve calibration. 

Note

:  When  verifications  are  proceeded,  note  if  the  Pt100 

excitation/activation current the calibrator requires is compliant to the 
Pt100 excitation current used in this instrument: 0.750 mA. 

 

Содержание N3000

Страница 1: ... S 5 5 5 5 range 0 to 1760 C 32 to 3200 ºF Pt100 6 6 6 6 range 199 9 to 530 0 C 328 0 to 986 0 ºF Pt100 7 7 7 7 range 200 to 530 C 328 to 986 ºF 4 20 mA 8 8 8 8 J linearization Programmable range 110 to 760 C 4 20 mA 9 9 9 9 K linearization Programmable range 150 to 1370 C 4 20 mA 10 10 10 10 T linearization Programmable range 160 to 400 C 4 20 mA 11 11 11 11 N Linearization Programmable range 90 ...

Страница 2: ...fic segments of the program See item 7 2 in this manual Event alarm Detects a heater broken condition by monitoring the load current when the control output is activated This alarm function requires an optional device option 3 Details of the resistance fail option can be found in a specific documentation that is sent with the product when the option is purchased TYPE PROMPT ACTION Disabled off off...

Страница 3: ... 5 to 1 5 mm2 16 to 22 AWG The terminals should be tightened to a torque of 0 4 Nm 3 5 lb in To minimize the pick up of electrical noise the low voltage DC connections and the sensor input wiring should be routed away from high current power conductors If this is impractical use shielded cables In general keep cable lengths to a minimum RECOMMENDATIONS FOR INSTALLATION Input signal wires should be...

Страница 4: ...ous displayed parameter INCREASE and DECREASE keys Used to change parameter values Programmable FUNCTION Key Can be assigned to the special functions described for the f fvnc f fvnc f fvnc f fvnc parameter When the controller is turned on its firmware version is displayed for 3 seconds after which the controller starts normal operation The values of PV and SV are displayed and the outputs are enab...

Страница 5: ...d soak Valid for all profile programs 0 0 0 0 PT1 to PT7 values are in seconds 1 1 1 1 PT1 to PT7 values are in minutes Pr n Pr n Pr n Pr n PROGRAM TO BE VIEWED Selects the ramp and soak profile program to be edited viewed in the following cycle prompts 7 programs available ptol ptol ptol ptol RAMP AND SOAK TOLERANCE maximum deviation between PV and SV Whenever this deviation is exceeded the time ...

Страница 6: ...ut Options 0 6 7 8 9 and 10 are possible for this input Refer to Table 2 for functions f fvnc f fvnc f fvnc f fvnc F KEY FUNCTION Selects the I O function assigned to the front panel key Available functions are 0 0 0 0 Key not used 7 7 7 7 Start Stop the controller RUN function 8 8 8 8 Select remote setpoint 9 9 9 9 Execute Hold ramp and soak profile 10 10 10 10 Enable Disable ramp and soak profil...

Страница 7: ...t ramp and soak program to be executed at prompt Prn Prn Prn Prn 0 to 7 Start control at the rvn rvn rvn rvn prompt by selecting YES Before executing the program the controller waits for PV to reach the first set point SP0 if PtoL PtoL PtoL PtoL is different than zero Should any power failure occur the controller resumes at the beginning of the segment it currently is AUTO TUNE During auto tune th...

Страница 8: ... the host to up to 31 slaves in a multidrop network topology Up to 247 units can be addressed by the MODBUS RTU protocol Maximum network distance 4 000 feet Time of indicator disconnection Maximum of 2 ms after the last byte Te communication signals are electrically isolated from the rest of the instrument and can be 1200 2400 4800 9600 19200 38400 and 57600 bps Number of data bits 8 without parit...

Страница 9: ...se Please retain the dated sales receipt as evidence of the date of purchase You will need it for any warranty service Within this period warranty against defects in material and workmanship under normal use is free of charge For repair send the product and the sales receipt to our address Expenses and transportation risks are under the purchaser s responsibility This warranty does not cover any d...

Отзывы: