Novus N1540-485 Скачать руководство пользователя страница 3

N1540 

NOVUS AUTOMATION

 

3

 

 

 

The USB interface IS NOT SEPARATE from the 

signal input (PV) or the digital inputs and outputs. 

It is intended for temporary use during 

CONFIGURATION and MONITORING periods.  
For the safety of people and equipment, it must 

only be used when the equipment is completely 

disconnected from the input/output signals. 

Using the USB in any other type of connection is 

possible but requires a careful analysis by the 

person responsible for installing it.  
When MONITORING for extended periods of time 

and with connected inputs and outputs, we 

recommend using the RS485 interface, which is 

available or optional in most of our products. 

PV RETRANSMISSION 

The digital panel meter may include an analog output which performs 

the retransmission of the measured process variable (PV) values. 

The analog retransmission can be scaled, i.e., there are minimum 

and maximum limits to establish the retransmission range, defined in 

the 

rtLL

 

and

 

rtkL

 

parameters. 

The digital panel meter allows a ratio between indication range and 

output current with inversely proportional behavior (

rtll

 > 

rtKL

).  

The analog output is available on terminals 18 (+) and 19 (-) for 

N1540-RT

 and 

N1540-RT-24V 

models. 

The user sets the relay signal between 0 to 20 mA and 4 to 20 mA. 
To  obtain retransmission at an electrical voltage of 0 to 10 V, the 

user shall install a shunt  resistor (500

 Ω

  max.) across the analog 

output terminals and select the 0 to 20 mA signal as the electrical 

relay signal. 
The analog retransmission output is electrically isolated the other 

circuits. 

 

Figure 2 –

 

PV retransmission terminals (RT mA OUT) 

Note: 

RS485 Communication and PV Retransmission features are 

mutually exclusive.

 

 

INSTALLATION / CONNECTIONS 

The digital panel meter is meant for panel mounting. The sequence of 

steps is:  

 

Prepare a cut-out of 93.0 by 45.5 mm on the panel. 

 

Remove the mounting clamp from the digital panel meter. 

 

Insert the digital panel meter into the cut-out from the front side of 

the panel. 

 

Place the clamp on the digital panel meter again, pressing until 

firm grip to the panel. 

ELECTRICAL CONNECTIONS  

The terminals configurations are shown in 

Figure 3

 

 

 

Figure 3 –

 

Inputs connections and power supply 

It is necessary to observe the existence of polarity in the connection 

of power supply line in 24 V models: Terminal 18 = (+) and terminal 

19 = (-). 

 

 

 

Figure 4 –

 

Thermocouple, Pt100, and 50 mV signal connection 

 

 

 

 

Figure 5 –

 

Current (mA) and Voltage (V) signal connection 

This digital panel meter offers an auxiliary 24 Vdc power supply which 

is typically applied to power up 2-wire 4-20 mA field transmitters. The 

Figure 6

 presents the wiring for this application: 

 

 

  

Figure 6 –

 

24 Vdc source with a 2-wire transmitter (passive, Sink 

type) 

INSTALLATION RECOMMENDATIONS 

 

To minimize the pick-up of electrical noise, the low voltage DC 

connections and the sensor input wiring should be routed away 

from high-current power conductors. If this is impractical, use 

shielded cables. In general, keep cable lengths to a minimum. 

 

The input signals conductors shall be positioned throughout the 

factory separate from the output and the power supply 

conductors, in grounded conduits if possible. 

 

The power supply of the electronic instruments shall come from a 

proper source for the instrumentation network. 

 

It is recommended to use RC FILTERS (0,1 uF in series with 100 

ohms) to suppress the noise generated by contactors coils, 

solenoids, etc. 

 
 
 

Содержание N1540-485

Страница 1: ...f equipment that require the same configuration FEATURES SIGNAL INPUT TYPE The input type to be used by the N1540 is defined in the equipment configuration Table 1 presents the input options available...

Страница 2: ...t value Inp xx a respective output indication ovP xx is defined The input signal must present an always crescent Applied to 0 20 mA 4 20 mA 0 50 mV 0 5 V and 0 10 V input types 24 VDC AUXILIARY VOLTAG...

Страница 3: ...mA OUT Note RS485 Communication and PV Retransmission features are mutually exclusive INSTALLATION CONNECTIONS The digital panel meter is meant for panel mounting The sequence of steps is Prepare a cu...

Страница 4: ...PV PV Display Indication The value of the measured variable PV is shown on the upper display red Sp a1 Sp a2 Setpoint Alarm Alarm SP Value that defines the alarm activation point For the alarms set up...

Страница 5: ...signal applied to the input ink Input High Calibration Indication of the full scale calibration signal applied to the input rstr Restore It restores the factory calibrations of the input disregarding...

Страница 6: ...4 V 12 to 24 Vdc 24 Vac 10 20 Maximum consumption 6 VA ENVIRONMENTAL CONDITIONS Operation temperature 0 to 50 C Relative humidity 80 30 C For temperatures above 30 C reduce 3 per C Indoor use Installa...

Страница 7: ...N1540 NOVUS AUTOMATION 7 Other error messages may indicate hardware problems requiring maintenance service WARRANTY Warranty conditions are available on our website www novusautomation com warranty...

Отзывы: