Novus DigiRail-4C Скачать руководство пользователя страница 4

DigiRail-4C 

NOVUS AUTOMATION 

4/5

 

Address 

Description 

SuperView Mnemonic 

Minimum 

Maximum 

R/W 

69 

Counted pulses in the last interval for input 4 -  most 
significant word 

PulseRate4H 

65535 

70 

Counted pulses in the last interval for input 4 -  least 
significant word 

PulseRate4L 

65535 

71 

Maximum of pulses counted on time interval for input 
1 - most significant word 

PeakPulse1H 

65535 

72 

Maximum of pulses counted on time interval for input 
1 - least significant word 

PeakPulse1L 

65535 

73 

Maximum of pulses counted on time interval for input 
2 - most significant word 

PeakPulse2H 

65535 

74 

Maximum of pulses counted on time interval for input 
2 - least significant word 

PeakPulse2L 

65535 

75 

Maximum of pulses counted on time interval for input 
3 - most significant word 

PeakPulse3H 

65535 

76 

Maximum of pulses counted on time interval for input 
3 - least significant word 

PeakPulse3L 

65535 

77 

Maximum of pulses counted on time interval for input 
4 - most significant word 

PeakPulse4H 

65535 

78 

Maximum of pulses counted on time interval for input 
4 - least significant word 

PeakPulse4L 

65535 

79-84 

Reserved 

DETAILS OF SOME REGISTERS 

REGISTER 2 – BAUD RATE 

Code of speed used in Modbus communication. 

Code

 

Baud rate

 

1.200 

2.400 

4.800 

9.600 

19.200 

38.400 

57.600 

115.200 

REGISTER 3 – MODBUS ADDRESS 

Address of the device in the Modbus network. Valid values: from 1 to 247. We recommend using the lower addresses for 
the equipment. 

REGISTER 4 – PARITY 

Code of the parity used in Modbus communication. 

Code

 

Parity

 

No parity 

Odd 

Even 

REGISTER 5 – FIRMWARE VERSION 

Indicates the firmware version of the equipment, according to the examples below: 

If the version is "1.00", the value "100" will be read. If the version is "2.04", the value "204" will be read. 

REGISTER 6 – DIAGNOSTIC STATE TIMER 

Internally used by the DigiConfig software. 

REGISTER 7 – STATE OF THE DIGITAL INPUTS 

Bit at 0: Input deactivated 

Bit at 1: Input activated 

Bit 

15  14  13  12  11  10  9  8  7  6  5  4  3  2  1  0 

Entry 

-  -  -  -  -  -  4  3  2  1 