Novus DigiRail-2A Скачать руководство пользователя страница 2

DigiRail-2A 

NOVUS AUTOMATION 

2/5

 

Address 

Description 

PV of Channel 2 in engineering unit. 
Range: defined by the limits of the temperature sensor, or by the indication limits as 
defined by the parameters 44 and 45 of the 

Holding Registers

7-9 

Reserved 

The specified 

addresses

 correspond to the low level physical addresses, where zero (0) corresponds to the address of 

PLC 30001. 

READ HOLDING REGISTERS – 03H 

This command can be used for reading one or several holding registers, according to the table in the chapter apart. 

WRITE SINGLE REGISTER – 06H 

This command can be used for writing in a holding register, according to the table in the chapter apart. 

TABLE OF HOLDING REGISTERS 

The specified 

addresses

 correspond to the low level physical addresses, where zero (0) corresponds to the address of 

PLC 40001. The columns 

minimum

 and 

maximum

 contain the range of values valid for each parameter. The column 

R/W

 

indicates if the parameter is for writing and reading (R/W) or for reading (R) only.

 

Address 

Description 

SuperView Mnemonic 

Minimum 

Maximum 

R/W 

Series number (word high) 

65535 

Series number (word low) 

65535 

Baud-rate 

R/W 

Modbus Address 

247 

R/W 

Parity 

R/W 

Firmware version 

999 

Analog input filter 

20 

R/W 

Status flags of the input channels 

InSts 

65535 

Reserved 

PV of channel 1 in percentage 

PVPer1 

62000 

10 

PV of channel 2 in percentage 

PVPer2 

62000 

11-13 

Reserved 

14 

PV of channel 1 in engineering unit 

PVEng1 

-31000 

31000 

15 

PV of channel 2 in engineering unit 

PVEng2 

-31000 

31000 

16-20 

Reserved 

21 

Input type of channel 1

 

In1Type 

-1 

21 

R/W 

22 

Input type of channel 2

 

In2Type 

-1 

21 

R/W 

23-25 

Reserved 

26 

Measuring unit of channel 1 

R/W 

27 

Measuring unit of channel 2 

R/W 

28-30 

Reserved 

31 

User offset of channel 1 

Ofs1 

-16000 

16000 

R/W 

32 

User offset of channel 2 

Ofs2 

-16000 

16000 

R/W 

33-35 

Reserved 

36 

Square root fitness for channel 1 

R/W 

37 

Square root fitness for channel 2 

R/W 

38-40 

Reserved 

41 

Lower indication limit of channel 1 when input type is linear 

In1LL 

-31000 

31000 

R/W 

42 

Upper indication limit of channel 1 when input type is linear 

In1HL 

-31000 

31000 

R/W 

43 

Lower indication limit of channel 2 when input type is linear 

In2LL 

-31000 

31000 

R/W 

44 

Upper indication limit of channel 2 when input type is linear 

In2HL 

-31000 

31000 

R/W 

45-50 

Reserved 

51 

Lower indication limit of channel 1 

-31000 

31000 

52 

Upper indication limit of channel 1 

-31000 

31000 

53 

Lower indication limit of channel 2 

-31000 

31000 

54 

Upper indication limit of channel 2 

-31000 

31000 

Отзывы: