background image

CAUTION: The 01-190-BAS Sensor is designed specifically for use in corridors where walking is the predominant motion to be detected.

Sensor performance is optimized when used in walled corridors. The 01-190-BAS should NOT be used in open-area walkways, offices or

other rooms. Refer to Novitas Tech Sheets for Sensors to use in these areas.

SENSOR

For full coverage in corridors, the Sensor should be mounted 8’-10’ high and located in the

center of the corridor. The Sensor must have a clear line of “sight” through air along the corri-

dor. For full coverage of longer corridors, additional Sensors may be wired together as shown

in the Wiring Diagram. When using multiple 01-190 Sensors, the first Sensor should be

placed 40’ form the end of the hall with additional Sensors on 90’ centers.
Do not mount where forced air will blow directly at or by any Sensor.

MULTIPLE FREQUENCIES

False activation of lighting in adjoining corridors can be prevented by using alternate frequen-

cy Sensors. Three frequencies are available: 25 kHz, 27 kHz and 32 kHz (Standard)
Coverage is slightly reduced at higher frequencies. See Coverage Diagrams.

SWITCHPACK

The Switchpack is generally mounted above the ceiling on the outside of the junction box that

contains a hot line, neutral and the existing switch leg from which the lighting is controlled. If

additional Switchpacks are required, they are mounted on the

outside of the boxes containing the appropriate switch legs. In

installations where there are no existing switch legs, the

Switchpack may be mounted outside any conventional stan-

dard junction box, with or without an extension ring.

NOTE:

Certain high inrush electronic ballasts may damage the

13-031 Switchpack if used with this product. Use Model 13-

051 Heavy Duty Switchpack when controlling high inrush bal-

lasts. Contact Novitas Customer Service for the latest informa-

tion regarding ballast compatability.

Installation Instructions

MODEL 01-190-BAS TWO-WAY CORRIDOR SENSOR

Read all instructions on both sides of this sheet first.

Plan all component locations carefully.

Install in accordance with all local codes.

For use with 10-30 VDC only.

Not for use where temperatures fall below 32

o

F or

exceed 110

o

F.

For indoor use only.

GENERAL INFORMATION

DESCRIPTION OF OPERATION

COMPONENT LOCATION

INSTALLATION

SENSOR:

Pass wires through the threaded mounting post and interlock to the

backplate. The Sensor mounts to a normal ceiling tile through a single 3/4” hole.

When mounted, the Sensor’s slotted grills must point along the path where

motion is to be detected.
An Adapter Plate (04-011) is available to allow mounting to a standard fixture ring

and junction box. The threaded mounting post may be cut down if it is too long to

fit into the junction box.

CAUTION: Finger-tighten the nut to avoid stripping

the mounting post.

SWITCHPACK:

Designed to be mounted externally to any junction box. When

mounted, the line connections are inside the box and the Class 2 wiring exits via

the rear of the Switchpack housing. In areas where Class 2 wiring is not permit-

ted, the Switchpack can be mounted internally to any standard electrical box.

CAUTION: Before installing or performing any service on a Novitas

system, the power MUST be turned off at the branch circuit breaker.

According to NEC 240-83(d), if the branch circuit breaker is used as

the main switch for a fluorescent lighting circuit, the circuit breaker

should be marked “SWD.”

NOTE REGARDING COMPACT FLUORESCENT LAMPS: The life of

some compact fluorescent lamps (CFLs) is shortened by frequent

automatic or manual switching. Check with CFL and ballast manu-

facturer to determine the effects of cycling.

When Sensors are used in conjunction with computer lighting sweep systems, you MUST remove the shunt marked “JP2” located on the printed circuit board. Removing the

shunt prevents an unnecessary “lights on” following the computer power-on sweep. For instructions on how to remove the shunt, see the Sensor Cover Removal section.

LIGHTING SWEEP APPLICATIONS

The 01-190-BAS is an ultrasonic motion Sensor with built-in timing and load control relay

driving circuitry. The Sensor produces a low intensity, inaudible sound. It detects

changes in the acoustic waves caused by motion, such as walking into a room, reaching

for a telephone, turning in a swivel chair, etc. The Sensor does not respond to audible

sound.

When the Sensor detects motion, it signals a BAS system or the relay in the con-

nected Switchpack is closed and lights are turned on. If no motion occurs within a

pre-set period of time, lights are turned off. To ensure continuous light when people

are present, time delay can be set from 15 seconds (for installer testing) to 30 min-

utes. The recommended time delay is usually 6-8 minutes. People who remain very

still for long periods may need a longer time delay.

The 01-190-BAS offers the most versatile connections available. A built-in isolated

Form C relay may be configured for either a Building Automation System (BAS) or

HVAC system. When connecting the 01-190-BAS to a BAS, any of the following may

be used: (1) Form C relay output, (2) open collector output, and (3) direct BAS/HVAC

connection. See Power Requirements and Wiring Diagram.

MOUNTING

POST

SENSOR UNIT

NUT

WASHER

ADAPTER

PLATE

NO. 04-011

SCREW

Mounted in Corridor with 10’ Ceiling

Mounted in Corridor with 10’ Ceiling

COVERAGE DIAGRAMS

32 KHZ FREQUENCY COVERAGE

27 KHZ FREQUENCY COVERAGE

Mounted in Corridor with 10’ Ceiling

25 KHZ FREQUENCY COVERAGE

72’

13’

96’

13.5’

100’

14’

Отзывы: