Flexible connections can be placed as close as ½D before the fan inlet.
Figure 7.
Installation spaces in ducts – optimal (left) and reduced
D
>
D
>
½D
r >
½D
>
D
>
Built into duct
Free inlet
D = Fan diameter
3 x D
>
3 x D
>
½D
r
>
D
>
D
>
D = Fan diameter
Built into duct
Free inlet
Figure 8.
Installation in duct
Figure 9.
Installation in duct
Fan size,
ØD, [mm]
RPM
1
2
1. Fan speeds depend on the installation space.
2. Fans with Ø160 hubs can run at maximum RPMs
irrespective of the installation conditions.
Maximum Optimal Reduced
Hu
b
di
am
et
er
s
16
0
250
4919
—
—
280
4747
—
—
315
4570
—
—
355
4408
—
—
400
4269
—
—
450
4145
—
—
500
4086
—
—
Hu
b
di
am
et
er
s
35
0
500
3660
3660
3483
560
3460
3460
3286
630
3238
3238
3059
710
3000
3000
2804
800
2751
2751
2523
900
2498
2498
2217
1000
2270
2270
1918
1120
2029
1900
1568
1250
1809
1500
1201
Hu
b
di
am
et
er
s
56
0
1000
2034
2034
1904
1120
1893
1893
1727
1250
1751
1751
1552
1400
1599
1599
1371
1600
1419
1419
1166
1800
1262
1262
1002
2000
1130
1130
878
Table 3.
Max. allowable speed at 20 °C
AZN-AZW fans are for circular duct
connections with flanges on both inlet and
outlet sides. The AZL has a flange on the outlet
side only.
Flanges on AZL-AZN fans are as standard
according to Eurovent 1/2. Fan type AZW has
flanges of type DIN 24154 row 4 as standard.
Systems with high vibration levels or more
exacting performance requirements must be
provided with expansion joints between fan
and duct.