3. Storage

Novax smoke exhaust fans type ACN-
smoke can stand outdoor storage for 1 
month provided the packing is intact. 
Fans with no packing must be stored in 
a sheltered place.
If the fans are stored indoors under well-
ventilated conditions with no risk of con-
densation the storage period may be ex-
tended to 6 months. The storage place 
must not be exposed to vibrations likely 
to damage the motor bearings.
If the storage period exceeds 3 months, it 
is recommended to turn the impeller re-
gularly by hand.

4. Installation

4.1 Prior to attachment

Prior to attachment make sure that the 
impeller rotates freely in the fan casing, 
wherever possible with equal distance 
between blade tip and fan casing throug-
hout the circumference.

4.2  Attachment

Fans must always be installed so that the 
rotating parts cannot be touched. The fan 
must be provided with a wire guard on 
the inlet and outlet sides. If ducts are con-
nected, they should be provided with 
wire guards on the inlet side.
The fan is provided with an arrow-plate 
denoting the direction of air flow 
through the fan casing. See during instal-
lation that the fan is oriented so as to pro-
vide the desired direction of air flow in 
the system.
The best way of installing the fan is using 
mounting feet (available as optional ex-
tras), but it may also be suspended in the 
fan casing flanges or in special carriers.
The carriers must not hamper the free in-
let and outlet of air. 
When the fan has been finally secured 
make sure that the impeller rotates freely 
in the casing.
If the motor is provided with drain holes 
for condensed water the fan must be ori-
ented so that the holes turn downwards 
(lowest point).
Generally, it is of the utmost importance 
for the performance and sound level of 
an axial flow fan that the air flow is un-
impeded and free from eddies.

4.3 Mounting feet

Mounting feet for type ACN-smoke con-
sist of two mounting plates (see fig. 
1item 01).
Mount two stiffeners (item 02) between 
these by means of joining elements (item 
03). Stiffeners are only available from fan 
size 630 mm inclusive.

To prevent vibrations spreading from the 
fan to the surroundings, anti-vibration 
mountings may be inserted between fan 
and support and flexible connections fit-
ted in the ducts before and after the fan
(available as optional extras).

Secure anti-vibration mountings (fig. 2 
item 06) in the mounting feet by means of 
bolts (item 05).
Mount base plates (item 07) for attach-
ment in the foundation/floor at the bot-
tom of the rubber element.
The natural frequency of the support 
must differ at least 20% from the fan 
speed.
The anti-vibration mountings serve to 
ensure that the natural frequency of the 
system does not exceed 10 Hz and that 
the damping is at least 80% at 1500 r.p.m.

Figure 1. Mounting foot for type ACN

Figure 2. ACN with mounting foot and antivibration mountings

 

 

Содержание FALKINN ACN

Страница 1: ...supplied with approval number class category are also men tioned as well as test standard applied EN 12101 3 Fan pressure air quantity output and maximum speed per minute The fan is also provided with a motor nameplate with relevant motor data in cluding insulation class of the motor 2 2 Weight The total weights shown in table 1 apply to axial flow fan type ACN smoke The totalweightisdeterminedont...

Страница 2: ...uspended in the fan casing flanges or in special carriers The carriers must not hamper the free in let and outlet of air When the fan has been finally secured makesurethattheimpellerrotatesfreely in the casing If the motor is provided with drain holes for condensed water the fan must be ori ented so that the holes turn downwards lowest point Generally it is of the utmost importance for the perform...

Страница 3: ...med by the person responsible for the operation of the system and the documentation must be kept and produced whenever asked for Prior to start of operation check that the fan and duct connections are clean and free from tools and foreign substances Also check that the electric connections meet the prescribed requirements that any wire guard fitted on the fan inlet or outlet side is correctly moun...

Страница 4: ...r bearings or other fan compo nents 6 6 Mounting of motor for types ACN smoke see fig 5 After servicing remount the motor take care that the motor flange item 10 is cor rectly located and that the motor shaft is concentrically placed in the fan casing before tightening the bolts item 06 Mount the impeller item 04 on the mo tor shaft by means of a tool fastened in the threaded hole of the motor sha...

Страница 5: ...ectricity supply Cleaning inside with pressure air outside with water Itisrecommendedtoenterallvaluesand observations in a log 8 Sound The sound generation of the fans de pends on installation and operating con ditions which means that no general da ta of the sound generation can be given Reference is made to our catalogues or computer programs for calculation of the specific sound generation 9 At...

Отзывы: