Installation and Maintenance 

Novax Smoke Exhaust Fan Type ACN Smoke

1. Application

2. Handling

2.1 Marking
2.2 Weight
2.3 Transport

3. Storage

4. Installation

4.1 Prior to attachment
4.2 Attachment
4.3 Mounting brackets
4.4 Duct connection
4.5 Electric connection

5. Start of operation

5.1 Prior to start of operation
5.2 Motors with Y/

Δ

 starting

5.3 Starting procedure

6. Maintenance

6.1 Protection prior to inspection and

maintenance

6.2 Fan casing
6.3 Impeller
6.4 Motor
6.5 Dismounting of motor
6.6 Mounting of motor
6.7 Blade pitch adjustment
6.8 Fault localization

7. Test of operability and

operating condition

7.1 Periodic inspection

8. Sound

9. Attestation of conformity

1. Application

Novax smoke exhaust fans type ACN-
smoke are sturdy axial flow fans de-
signed for both the daily ventilation re-
quirements under normal conditions
and smoke/heat exhaustion in the event 
of a fire in all kinds of commercial and in-
dustrial buildings.
Novax smoke exhaust fans type ACN-
smoke are tested and approved to meet
the requirements of fans for smoke ex-
haustion class F300 (300°C for 60 min-

utes) and F400 (400°C for 120 minutes) 
according to standard: EN 12101-3.

2. Handling

2.1 Marking

The ACN smoke exhaust fan is provided 
with a standard nameplate with Noven-
co's name and address.
It also mentions type/size e. g. ACN 
1000/380, number of blades, year of pro-
duction, weight, serial number/order 
number (production number). Further-
more, it mentions maximum tempera-
ture and working period in minutes and 
if the fan is supplied with approval 
number, class/category are also men-
tioned as well as test standard applied 
(EN 12101-3). Fan pressure, air quantity, 
output and maximum speed per minute.
The fan is also provided with a motor 
nameplate with relevant motor data in-
cluding insulation class of the motor.

2.2  Weight

The total weights shown in table 1 apply 
to axial flow fan type ACN-smoke. The 
total weight is determined on the basis of 
type/size of fan and maximum motor 
size employed and is in terms of kg.

2.3  Transport

When transporting the fans take care 
that no water (e. g. rainwater) gets into 
the motor or other sensitive components.
Novax smoke exhaust fans type ACN-
smoke are delivered on pallets or bearers 
to allow fork-lift transport.
The forks of the fork-lift truck must lift 
underneath the frame. Set down the fan 
as slowly as possible and on a soft foun-
dation. Vibrations, shocks, and fall may 
result in imbalance and deformation and 
may damage the motor bearings.

MU 14347 0610

918149-0

GB

Table 1. Example of total weights (Fan incl. motor, LOHER 4-pole) [kg]

Type ACN-smoke

Fan size

Motor size

-90

-100

-112

-132

-160

-180

-200

-225

-250

-280

Hu

b d

ia

m

et

er

s

160,

 230,

 280,

 330 and 380

400

47

57

500

62

72

80

95

560

75

85

93

108

185

630

80

90

98

113

190

222

710

93

103

111

126

203

235

800

102

112

120

135

212

244

900

118

128

136

151

228

260

1000

154

164

172

187

264

296

Hub diameters

40

3

900

170

247

1000

207

284

316

1120

205

220

297

329

1250

222

237

314

346

1400

255

332

364

H

u

b di

a

m

eters

578

900

206

283

315

1000

245

322

354

442

1120

257

272

349

381

469

554

1250

307

322

399

431

519

604

689

1400

459

491

579

664

749

899

1600

616

701

786

936

Motor type

-90

-100

-112

-132

-160

-180

-200

-225

-250

-280

Motor Weight (kg)

20

30

38

53

130

162

250

335

420

570

Содержание FALKINN ACN

Страница 1: ...supplied with approval number class category are also men tioned as well as test standard applied EN 12101 3 Fan pressure air quantity output and maximum speed per minute The fan is also provided with a motor nameplate with relevant motor data in cluding insulation class of the motor 2 2 Weight The total weights shown in table 1 apply to axial flow fan type ACN smoke The totalweightisdeterminedont...

Страница 2: ...uspended in the fan casing flanges or in special carriers The carriers must not hamper the free in let and outlet of air When the fan has been finally secured makesurethattheimpellerrotatesfreely in the casing If the motor is provided with drain holes for condensed water the fan must be ori ented so that the holes turn downwards lowest point Generally it is of the utmost importance for the perform...

Страница 3: ...med by the person responsible for the operation of the system and the documentation must be kept and produced whenever asked for Prior to start of operation check that the fan and duct connections are clean and free from tools and foreign substances Also check that the electric connections meet the prescribed requirements that any wire guard fitted on the fan inlet or outlet side is correctly moun...

Страница 4: ...r bearings or other fan compo nents 6 6 Mounting of motor for types ACN smoke see fig 5 After servicing remount the motor take care that the motor flange item 10 is cor rectly located and that the motor shaft is concentrically placed in the fan casing before tightening the bolts item 06 Mount the impeller item 04 on the mo tor shaft by means of a tool fastened in the threaded hole of the motor sha...

Страница 5: ...ectricity supply Cleaning inside with pressure air outside with water Itisrecommendedtoenterallvaluesand observations in a log 8 Sound The sound generation of the fans de pends on installation and operating con ditions which means that no general da ta of the sound generation can be given Reference is made to our catalogues or computer programs for calculation of the specific sound generation 9 At...

Отзывы: