and the calculation of additional code of the received number. At the receiver, the LRC is calculated again and
compared with the received LRC. In the calculation of LRC the colon, CR and LF are discarded.
An example of the LRC calculation for the command for reading of continuous 2 words from starting address
2102H in UBZ with communication address 01H is shown in Table 5.6.
5.4.6 Register addresses
The register addresses of measured and calculated parameters of UBZ are given in Table 3.5
The register addresses of programmable parameters are given in Table 3.6.
The register addresses of special and service parameters and their purpose are given in Table 3.4.
The register address of the status and purpose bit data in Table 5.9.
The register addresses of the alarm log are given in Table 5.9.
The register addresses of time settings are given in Table 5.10.
The register address of commands is 903 (Table 5.12).
Table 5.9
Description
Address
Service
Remark
Register of UBZ state 900
Bit 0
0
–
No fault;
1
–
fault (code of fault in register - 241).
Bit 1
0
–
load relay is disabled;
1
–
load relay is enable.
Bit 2
0
–
functional relay is disabled;
1
–
functional relay is enabled.
Bit 3
0
–
restart is disabled;
1
–
ARS is waited.
Bit 5-4
Mode of functional relay operation:
00
–
alarm relay;
01
–
time relay;
10
–
star / delta.
Bit 6
0
–
MNS mode is disabled;
1
–
MNS mode is enabled.
Bit 7
0
–
clock battery is normal;
1
–
the clock battery should be replaced.
Bit 8
0
–
normal operation;
1
–
UBZ is in area of hysteresis when operating
with analog inputs.
Register of fault 1
901
Bit service as per Table 5.13
0- no fault;
1- fault.
Register of fault 2
902
Bit service as per Table 5.13
Fault logbook
Fault code 1
1000
Fault code as per Table 5.13
Parameter value 1
1001
Parameter value as per Table 5.13.
Fault time 1
1002
Low byte
–
seconds, high byte
–
minutes.
1003
Low byte
–
hours, high byte
–
day of month.
1004
Low byte
–
month, high byte
–
(year minus 2000).
Fault code N
1000+(N-1)*5
Fault code as per Table 5.12.
Parameter value N
1000+(N-1)*5+1
Parameter value as per Table 5.12.
Fault time N
1000+(N-1)*5+2
Low byte
–
seconds, high byte
–
minutes.
1000+(N-1)*5+3
Low byte
–
hours, high byte
–
day of month.
1000+(N-1)*5+4
Low byte
–
month, high byte
–
(year minus 2000).
N o te
–
At the time of UBZ delivery or after the setting of factory parameters (it.5.2.7) there is a record in the
fault logbook about error code 40 and parameter value 10000.
5.4.7 Time parameter registers
The parameters are transmitted in binary decimal code. For example, the code 0x14 in the register of minutes
means 14 minutes.
Registers of time settings allow reading and recording of data.
Register addresses for time settings are shown in Table 5.10.
Table 5.10
Parameter
Address
Remark
Seconds
80
Minutes
81