Novatek-electro RNPP-311M Скачать руководство пользователя страница 3

 

- 3 - 

NOVATEK-ELECTRO

                                                                                                 RNPP-311M

  

                                                                                                                       

 

  MIN voltage monitoring; 

  MAX voltage monitoring; 

  correct phase sequence monitoring and phase coincidence control; 

  phase imbalance control 

Control of voltage presence on each phase is being performed at any position of 4-8 switches.  

On special request it is possible to arrange operative input voltage of 24V for the RNPP-311M (

is 

recommended for using in the network lines with a high level of harmonic waves)

 

ATTENTION

 - the source of operational supply is galvanically connected to zero network. 

 
2. TECHNICAL CHARACTERISTICS 

Purpose of device

 - 

control and distribution equipment

.

 

Typical operation - continued.

 

 

Rated line/phase voltage, V 
 

400/230, 
415/240 

Rated frequency, Hz 

45 

 65 

Harmonical configuration (nonsinusoidality) of power supply voltage 

EN 61000-3-2 
(IEC 1000-3-2)

 

Adjustable range for

 

U

max/

U

min, 

% of nominal value 

U

nom

 

5 - 50 

Adjustable Tripping time delay (

T

off

), sec 

 10 

Adjustable Autoreclosing time delay (

T

on

), sec 

 600 

Fixed time delay for tripping in case MIN voltage fault detected (time delay

 

for 

U

min

), sec  12* 

Reaction time in case of phase loss, sec (not more) 

0,2 

Readiness time on energizing the RNPP-311M, sec (not more) 

0,2** 

Phase imbalance value, V 

60 

Voltage hysteresis, V 

5 - 6 

Phase imbalance hysteresis, V 

5 - 6 

Accuracy for voltage tripping threshold measurement, V (not more)  

Accuracy for phase imbalance measurement, %  (not more)  

Protection class against electric shock 

 II 

Permissible contamination level 

 II 

Overvoltage category 

 II 

Nominal  voltage  of isolation, V 

 450 

Operational voltage range, % of rated voltage 

from 50 to 150 

Rated impulse withstand voltage, kV 

2.5 

Power consumption (under power load), VA (not more) 

3.0  

Maximal current that output contacts may commutate, A 

Cross-

section area of connection terminals, mm² 

0.5 

– 2 

Maximum torque of terminal fixing, N*m 

0.4 

Commutation endurance for the output contacts: 
   - under 5

А power load, not less than 

   - under 1

А power load, not less than 

                       
100000 times                      
1000000times 

Protection degree: 
  - for the device 
  - for the terminals 

 
IP40 
IP20 

Operational temperature range, 

С 

from - 35 to +55 

Storage temperature conditions, 

С 

from - 45 to +60 

Weight, kg (not more) 

0.200 

Overall Dimensions, mm                                                                               

35 х 93 х 68                                                    

Standard 35 mm DIN rail mounting  

 

Mounting position as per requirement (arbitrary) 

 

_______ 

 

*In case of minimal voltage alarm situation (

Umin

 fault) then tripping time delay of 12 seconds will be applied on the following 

conditions: 

a) 

U

max

 and 

U

min

 switches are set to the left position

b) At any other combination of switches of Umax and Umin, of relay will work with the 

T

off

 

time preset by the user; 

If within this 12 sec time interval it will happen some other type of voltage interruption (for example 

U

max

 

fault), then the  

RNPP-311M will trip the power load with minimal time: with the 

T

off

 

time preset by the user or the left time of 12 sec interval. 

**

In case of maximal voltage mode

 – 

0.3 seconds.

 

Содержание RNPP-311M

Страница 1: ...ompounds for cleaning spirit gasoline solvents etc NEVER ATTEMPT TO REMOVE AND REPAIR THE UNIT Some of the unit components may be live NEVER ATTEMPT TO OPERATE THE UNIT WITH THE MECHANICAL DAMAG THE H...

Страница 2: ...on each phase Using toggle switch Figure 1 point 4 RNPP 311M user may select the type of the power circuit 400V or 415V and the set of optionally performed functions using toggle switches 5 8 shown o...

Страница 3: ...r phase imbalance measurement not more 2 Protection class against electric shock II Permissible contamination level II Overvoltage category II Nominal voltage of isolation V 450 Operational voltage ra...

Страница 4: ...ith isolated Neutral then the measurement accuracy for the phase imbalance and voltage tripping thresholds increase to 5 To terminals 7 8 it is possible to connect 24V AC DC external power supply sour...

Страница 5: ...on one of phases and the external power supply of 24 V is absent then RNPP 311M saves operability when voltage at least 140 V 3 3 Adjustments and settings ATTENTION Not to break or turn the knobs plea...

Страница 6: ...put terminals 9 10 11 see Figure 1 and Neutral to terminal 12 If necessary connect external 24V AC DC power supply source to terminals 7 and 8 5 Connect output terminals 1 2 4 5 and 5 6 2 3 to the con...

Страница 7: ...ion against the phases distortion is carried out by a switch IMB In case the phase loss detected or the voltage on any of the lines becomes lower than 100V then RNPP 311M will turn OFF the power load...

Страница 8: ...pair damage is caused by electric current or voltage in excess to the permissible values as indicated in the Operating manual 6 4 Warranty service is provided in the place of purchase 6 5 Post warrant...

Отзывы: