5.7 Compensated Watts and VARs (Line and Transformer Loss Compensation)
The total Watt and Var losses can be calculated using five user entered parameters
and measured current and voltage values. These losses are added or subtracted
to/from the measured Total Watts and Total Vars when accumulating Energy.
Loss compensation on the PPX II takes the following general form:
P
COM
=
P
UNC
+
A
·
I
2
+
B
·
V
2
+
E
·
P
UNC
Q
COM
=
Q
UNC
+
C
·
I
2
+
D
·
V
4
+
E
·
Q
UNC
Where:
P
COM
Compensated three-phase total watts. Note the accumulators for +kWh and –
kWh in the PPX II are calculated by integrating the
P
COM
measurement over time.
P
UNC
Uncompensated three-phase total watts measured at the point where the meter
is connected.
Q
COM
Compensated three-phase total VARs. Note the accumulators for +kVARh and –
kVARh in the PPX II are calculated by integrating the
Q
COM
measurement over
time.
Q
UNC
Uncompensated three-phase total VARs measured at the point where the meter
is connected.
I
RMS line current measured at the point where the meter is connected.
V
RMS
line-line
voltage measured at the point where the meter is connected.
A
Meter setting
that accounts for the sum of the full-load-watt-losses from all
sources.
B
Meter setting
that accounts for the transformer’s no-load-watt-losses.
C
Meter setting
that accounts for the sum of the full-load-VAR-losses from all
sources.
D
Meter setting
that accounts for the transformer’s no-load-VAR-losses.
E
Meter setting
that accounts for any “system” losses, proportional to the
uncompensated power.
Configuring the meter to perform loss compensation simply requires the user to
calculate the coefficients
A, B, C, D,
and
E
defined above, and enter them in the
appropriate fields in the PPX II’s webserver interface on the Settings/Input page as
shown in the screen shot below
The
sign
of the settings
A
,
B
, C,
D
, and
E
determines whether losses will be added to
or subtracted from the uncompensated measurements in order to determine the
compensated power and energy. To add losses, be sure the settings are all positive.
To subtract losses, be sure the settings are all negative. Settings should always have
the same sign.
Making all of the settings equal to zero
turns off
loss compensation.
Содержание Bitronics PowerPlex II
Страница 2: ...2 ML0044B December 1 2017 Copyright 2017 Bitronics LLC...
Страница 12: ......
Страница 43: ...43 ML0044B December 1 2017 Copyright 2017 Bitronics LLC Figure 9 Tethered Display PPX IITD Cable Wiring Diagram...
Страница 56: ...56 ML0044B December 1 2017 Copyright 2017 Bitronics LLC...
Страница 57: ...57 ML0044B December 1 2017 Copyright 2017 Bitronics LLC...
Страница 58: ...58 ML0044B December 1 2017 Copyright 2017 Bitronics LLC...
Страница 61: ...61 ML0044B December 1 2017 Copyright 2017 Bitronics LLC...
Страница 64: ...64 ML0044B December 1 2017 Copyright 2017 Bitronics LLC Identity...
Страница 65: ...65 ML0044B December 1 2017 Copyright 2017 Bitronics LLC Input...
Страница 68: ...68 ML0044B December 1 2017 Copyright 2017 Bitronics LLC DNP3 Serial Basic Modbus Serial...
Страница 69: ...69 ML0044B December 1 2017 Copyright 2017 Bitronics LLC DNP TCP Advanced DNP Serial Advanced...
Страница 70: ...70 ML0044B December 1 2017 Copyright 2017 Bitronics LLC Modbus TCP Primary Units...
Страница 74: ...74 ML0044B December 1 2017 Copyright 2017 Bitronics LLC Load Store Device Settings...
Страница 75: ...75 ML0044B December 1 2017 Copyright 2017 Bitronics LLC Password Security Settings Firmware Upload...
Страница 77: ...77 ML0044B December 1 2017 Copyright 2017 Bitronics LLC...
Страница 79: ...79 ML0044B December 1 2017 Copyright 2017 Bitronics LLC...
Страница 80: ...80 ML0044B December 1 2017 Copyright 2017 Bitronics LLC...
Страница 83: ...83 ML0044B December 1 2017 Copyright 2017 Bitronics LLC...
Страница 84: ...84 ML0044B December 1 2017 Copyright 2017 Bitronics LLC...
Страница 102: ...102 ML0047 December 1 2017 Copyright 2017 Bitronics LLC Figure 13 Signal Connections PPX II...
Страница 118: ...ML0044B December 1 2017 118 Copyright 2017 Bitronics LLC...
Страница 119: ...ML0044B December 1 2017 119 Copyright 2017 Bitronics LLC...
Страница 120: ...ML0044B December 1 2017 120 Copyright 2017 Bitronics LLC...
Страница 121: ...ML0044B December 1 2017 121 Copyright 2017 Bitronics LLC...
Страница 122: ...ML0044B December 1 2017 122 Copyright 2017 Bitronics LLC...
Страница 123: ...ML0044B December 1 2017 123 Copyright 2017 Bitronics LLC...
Страница 124: ...ML0044B December 1 2017 124 Copyright 2017 Bitronics LLC...
Страница 125: ...ML0044B December 1 2017 125 Copyright 2017 Bitronics LLC...
Страница 126: ...ML0044B December 1 2017 126 Copyright 2017 Bitronics LLC...
Страница 127: ...ML0044B December 1 2017 127 Copyright 2017 Bitronics LLC...
Страница 128: ...ML0044B December 1 2017 128 Copyright 2017 Bitronics LLC...
Страница 129: ...ML0044B December 1 2017 129 Copyright 2017 Bitronics LLC...
Страница 130: ...ML0044B December 1 2017 130 Copyright 2017 Bitronics LLC...
Страница 131: ...ML0044B December 1 2017 131 Copyright 2017 Bitronics LLC...
Страница 132: ...ML0044B December 1 2017 132 Copyright 2017 Bitronics LLC...
Страница 135: ...ML0044B December 1 2017 135 Copyright 2017 Bitronics LLC...
Страница 136: ...Bitronics LLC 261 Brodhead Road Bethlehem PA 18017 610 997 5100 Fax 610 997 5450 www novatechweb com bitronics...