44
Document: GFH-NT 1500-4000 IM 14 DEC 2016
Gas Fired Heater Instructions
©2016 NOVATEC, Inc. All Rights Reserved
Section 2 Check List
Pass
Fail
With power off, verify all electrical connections are tight.
With no flame (WNF), check the combustion blower for
the proper rotation.
WNF, disconnect the flame rod wire and attempt to start
the burner. The flame should go out (FO), and the flame
controller (FC) should go into a lock out condition (LO).
WNF, disconnect the spark plug wire and attempt to start
the burner. The flame should not start, and the FC
should go into LO.
With flame on (WFO), check for gas leaks.
WFO, visually observe blue flame at low fire (LF).
WFO, visually observe blue flame at high fire (HF).
WFO, press test/reset button on flame controller (FCR).
You should observe FO and LO, which requires it to be
reset before allowing restart. The two main safety shut-
off valves should be closed as observed by the position
indicator (PI) or POC switch on each valve.
WFO, press test button on the APS; you should observe
FO, LO, and PI or POC switch.
WFO, turn the gas supply off; you should observe FO,
LO, and PI or POC switch.
Comments
_____________________________________________________________
______________________________________________________________________
_