IMPORTANT:

 Please read these instructions carefully. Whilst straightforward, the installation of these devices is critical to their 

performance. Installation should only be carried out by a suitably qualified person in accordance with all relevant standards.

®

Installation Instructions

Surge Counters

1. Introduction

1.1

  These installation instructions apply to the Novaris range of 

surge counters with the following catalogue numbers:

 

 TSC1-IP65 

 TSC1-DIN 

 TSC1-DIN-EC

 

1.2 

These products are used to count the number of surges 
experienced at a site. The TSC1-DIN-EC also doubles as an 
earth clamp. This eliminates the problems associated with 
having two separate earths by clamping the two together 
during a surge.

Figure 1:   TSC1-IP65  &  TSC1-DIN

2. Installation of TSC1-IP65

2.1 

Using the clamps provided, the TSC1-IP65 model is simply 
clamped to a downconductor (as shown in Figure 2) or to an 

earth return conductor of a surge diverter or surge filter.

 

To adjust the clamps, remove the clear plastic front of the 
unit. The clamps may then be tightened or loosened using 
a suitably long phillips head screwdriver in the four round 
holes at the corners of the TSC1-IP65.

Figure 2:   Installation of TSC1-IP65

3. Installation of TSC1-DIN & TSC1-DIN/EC

3.1  TSC1-DIN: 

If using a MEN wiring system, the TSC1-DIN 

should be connected between the neutral terminal of a surge 

filter or surge diverter and the neutral bar for the system. 

In a non MEN system the TSC1-DIN should be connected 

between the earth terminal of a surge filter or surge diverter 

and earth. Lead lengths must be kept as short as possible.

3.2  TSC1-DIN/EC: 

The TSC1-DIN-EC model is connected 

between two different earthing systems as shown in Figure 4. 
Again, lead lengths must be kept as short as possible.

3.3  Earth: 

All units should be mounted on a DIN rail. For safety 

it is crucial the DIN rail is electrically connected to earth.

3.4  Display unit: 

The display unit is connected as shown 

in Figure 6. The connecting leads do not need to be kept 
short but should be routed away from electrically noisy 
environments. This allows the display unit to be panel 
mounted in a convenient location.

Filter Neutral

Neutral Bar

Figure 3: Installation of TSC1-DIN in MEN system

Figure 4:   Installation of TSC1-DIN in Non MEN system

To earth terminal of surge diverter 

or surge filter

Figure 6 : Wiring Display Unit

Figure 5 :   Installation of TSC1-DIN-EC

Two different 
earthing systems