NOVAR 300 Operation & Maintenance Manual
NOVAR_CM
Page 16 of 29
Table 1 - Sequence settings
Max no. of steps per controller
Switches
Number of Stages
Sequence
Number
Sequence
1
2
3
1
3
6
9
12
00
1:1:1:1:1 etc
0
0
0
1
3
6
9
12
01
1:1:2:2:2 etc
1
0
0
1
4
10
16
22
02
1:2:2:2:2 etc
0
1
0
1
5
11
17
23
03
1:2:3:3:3 etc
1
1
0
1
6
15
24
33
04
1:2:3:4:4 etc
0
0
1
1
6
18
30
30
05
1:2:4:4:4 etc
1
0
1
1
7
19
31
31
06
1:2:3:6:6 etc
0
1
1
1
6
24
30
30
07
1:2:4:8:8 etc
1
1
1
1
7
31
31
31
3.3.2 Safety Lockout Time
Proper selection of switching time delay is a function of the electrical system and capacitor
voltage rating. Usually, as a guide, the time interval must be larger than the discharge time
of the capacitor being switched. This time required for discharge is known as the safety
lockout time. The dual-in-line switch should be set to the desired time by reference to Table
2. In expanded display mode, the setting selected can be checked by pressing the lower
push button once more (a ‘t’ symbol will appear in digit 4 of the display).
Table 2 - Lockout time settings
Safety Lockout
Time (Seconds)
Switches
4
5
6
10
0
0
0
20
1
0
0
30
0
1
0
60
1
1
0
180
0
0
1
300
1
0
1
480
0
1
1
600
1
1
1