background image

NovaLynx Corporation________________________________________________________________________________ 

 

 

 
200-WS-02E 

Page 9 

December 2018 

 

 

10

 

FUNCTIONAL TESTS 

 

The following checks can be done with an ohm-meter after the sensor has been dis-mounted from the 
weather station mast or tower. These tests can help determine whether the sensor needs repair or 
adjustment. 
 

10.1

 

Anemometer Electrical Test 

Set the ohm-meter to a low resistance range and touch its leads together to check for zero ohms. If it is 
an analog meter adjust the dial to read zero ohms. Connect the ohm-meter to the white and brown 
signal wires from the anemometer (polarity is not important). 

Rotate the cup assembly slowly until you notice the meter reading drop to less than 10 ohms. Continue 
to rotate until the switch opens (high resistance). Do this for each of the 3 magnets in the cup 
assembly. If the meter always reads a low resistance then the reed switch is not opening (the contacts 
may have welded together) or there may be a short circuit in the cable. If the switch never closes then 
there may be a break in the cable or the magnets are not near enough to activate the switch. Check 
the distance between the cup assembly and the base. The gap should be about 1/16" (1.6 mm). 

10.2

 

 Potentiometer Electrical Test 

Wind vane calibration involves checking the potentiometer output and verification of the sensor 
alignment to north. 
 
Set the ohm-meter to the 20k range (or greater range if needed). Connect the black meter lead to the 
black sensor wire, and the red meter lead to the red sensor wire. The reading on the meter should be a 
stable output of about 20,000 ohms (+/-20%). Rotate the vane once around while watching the meter 
to ensure the reading does not change. 
 
Connect the red meter lead to the green wire. Observe that the meter reading changes as you rotate 
the vane. Check the "dead band" where the meter goes to "infinite" and verify that the counterweight 
is pointing the same direction as the North indicator label on the base of the sensor. Now rotate the 
vane slowly 

counter-clockwise

 and observe that the resistance changes smoothly from near zero to 

the maximum just before hitting the "dead band" again as you approach north. 
 
If the "dead band" does not align with the North label then the position of the vane can be changed to 
correct the alignment: 

1.

 

Using a 1/16" Allen wrench, loosen the potentiometer set screw located on one side of the hub 
(See Figure 1 on Page 6).  

2.

 

Lift upwards to remove the vane assembly from the sensor. Note that the potentiometer body 
is bonded to the sensor body and should not move. 

Содержание 200-WS-02E

Страница 1: ...200 WS 02E User Manual 200 WS 02E Wind Speed and Direction Sensor Phone 530 823 7185 USA Toll Free 800 321 3577 Fax 530 823 8997 Email nova novalynx com Website www novalynx com ...

Страница 2: ...the case of delicate or sensitive items If packing facilities are not available take the equipment to the nearest Post Office UPS or other freight service and obtain assistance with the packaging Please write the RA on the outside of the box Warranty NovaLynx Corporation warrants that its products are free from defects in material and workmanship under normal use and service for a period of one ye...

Страница 3: ...TION 4 3 1 Anemometer Details 4 3 2 Wind Vane Details 5 4 SITING CONSIDERATIONS 6 5 TAIL ASSEMBLY 6 6 MOUNTING 7 7 CABLE INSTALLATION 7 8 WIRING DIAGRAM 8 9 SENSOR MAINTENANCE 8 10 FUNCTIONAL TESTS 9 10 1 Anemometer Electrical Test 9 10 2 Potentiometer Electrical Test 9 11 Additional Precautions 10 11 1 Lightning Protection 10 11 2 Bird Perch 10 11 3 Falling Parts Hazard 10 11 4 Handling 10 ...

Страница 4: ... s monitoring equipment This manual contains information to aid in the design of custom interface circuits for use with the NovaLynx Model 200 WS 02E Wind Sensor This information is supplied to systems integrators with the express understanding that NovaLynx Corporation assumes no responsibility or liability for the operation of the wind sensor as a part of any equipment that has been designed or ...

Страница 5: ... on the body of the sensor Measurement Range 125 mph max 55 88 m s max Speed Threshold 1 2 mph 0 5364 m s Speed Constant 1 25 mph 1 Hz 0 5588 m s 1 Hz Accuracy 1 mph 0 4470 m s or 3 Transducer Type Reed switch magnet activated Maximum Rating 10 mA 50 V ac or dc Turning Radius 4 inch 10 16 cm Measurement Range 0 360 degree azimuth Potentiometer Gap 5 degree approximate Accuracy 3 degrees Vane Thres...

Страница 6: ...ht of the object Roof mounted sensors should be placed on the upwind side of the building and away from all exhaust vents If the sensor is located on top of a building the sensor height should be 1 5 x H where H is the height of the building In all cases when the wind sensor data is to be correlated to National Weather Service data or World Meteorological Organization data the standard exposure is...

Страница 7: ...ng arm Align the North indicator label to geographic true north and secure the sensor to the mast using the set screws provided in the sensor base Do not use excessive force when tightening the screws Tighten the screws until the sensor base can no longer be manually rotated NOTE Wind direction sensors are usually aligned to true north rather than magnetic north True north is usually found by read...

Страница 8: ...ed before tightening First inspect the counterweight to ensure it is firmly cemented to the vane Repair if necessary Next remove the entire sensor and hold it horizontal to the ground Adjust the distance of the counterweight until it exactly balances the tail Make sure the tail is vertical to the sensor and then tighten the vane Re check the balance 2 With the sensor mounted on the mast make sure ...

Страница 9: ...embly and the base The gap should be about 1 16 1 6 mm 10 2 Potentiometer Electrical Test Wind vane calibration involves checking the potentiometer output and verification of the sensor alignment to north Set the ohm meter to the 20k range or greater range if needed Connect the black meter lead to the black sensor wire and the red meter lead to the red sensor wire The reading on the meter should b...

Страница 10: ...ctrically connected to the metal hub vane assembly The purpose is to bleed off static that would otherwise affect the sensor output Therefore it is important to earth ground the shield wire for best results Installations where nearby lightning strikes are likely should include a properly grounded lightning rod above the level of the sensor preferably on a separate tower 11 2 Bird Perch Birds of al...

Отзывы: