INSTALLATION STEPS

1. Cabinet Mounting

Figure 3. Typical mounting hole locations:

Backbox
Mounting
Holes

In a clean, dry area, mount the backbox using the four holes pro-
vided in the back surface of the cabinet.

2. Chassis Installation

The  CHS-6  chassis  is  mounted  in  the  BB-25,  CAB-3  or  CAB-4 
Series  cabinets.  It  is  shipped  with  two  self-threading  screws, 
which are used to fasten the chassis to the back wall of the cabi-
net (see Figure 4).

Figure 4: Mounting the CHS-6 chassis

Mount with self-threading screws

to back of cabinet

The BB-XP cabinet comes with the chassis already installed, so no 
mounting is necessary.

Chassis 

The CHS-6 chassis is used to mount XP6-R modules in a BB-25, 
CAB-3 or CAB-4 Series cabinet. It accommodates up to six XP6-
R modules in a single cabinet row three modules wide and two 
modules deep.

Figure 1. CHS-6 Chassis

:

The BB-XP cabinet has a built-in chassis that will accommodate 
one or two XP6-R modules.

Figure 2. BB-XP Cabinet:

0

1

2 3 4 5 6

7

8

9

0

7

8

6

5

4

3

2

1

9

1

0

11

1

2

1

3

1

4

15

BASE 

ADDRESS

ADDRESS

DISABLE

N

O

N

E

O

N

E

TW

O

TH

R

E

E

0

1

2 3 4 5 6

7

8

9

0

7

8

6

5

4

3

2

1

9

1

0

11

1

2

1

3

1

4

1

5

BASE 

ADDRESS

ADDRESS

DISABLE

NONE

ONE

TW
O

THREE

The front XP6-R module positions of each chassis are offset below 
the rear XP6-R module positions so that all of the status indicators 
are visible.

Cabinets

A  BB-25,  CAB-3  or  CAB-4  Series  cabinet  will  house  the  CHS-6 
chassis  with  up  to  six  XP6-R  modules  installed  on  it.  Refer  to 
cabinet installation documents for dimensions.
The  BB-XP  cabinet  houses  one  or  two  XP6-R  modules  on  the 
internal chassis that is part of the cabinet.  Refer to cabinet instal-
lation documents for dimensions. 

N500-78-00 

I56-1804-008

C0236-00

C0206-00

C0235-00

C0234-00

Содержание XP6-R

Страница 1: ...olid on Temperature Range 32 F to 120 F 0 C to 49 C Humidity 10 to 93 Non condensing Dimensions 6 8 H 5 8 W 1 0 D Accessories CHS 6 Chassis BB 25 Cabinet BB XP Cabinet CAB 3 Series Cabinets CAB 4 Series Cabinets Wire Gauge 12 18 AWG Relay Current 30 mA Relay Pulse 15 6 mS pulse duration pulse under panel control elsewhere Each XP6 R module also has panel controlled green LED indicators The panel c...

Страница 2: ... single cabinet row three modules wide and two modules deep Figure 1 CHS 6 Chassis The BB XP cabinet has a built in chassis that will accommodate one or two XP6 R modules Figure 2 BB XP Cabinet 0 1 2 3 4 5 6 7 8 9 0 7 8 6 5 4 3 2 1 9 10 11 12 13 14 15 BASE ADDRESS ADDRESS DISABLE NONE ONE TWO THREE 0 1 2 3 4 5 6 7 8 9 0 7 8 6 5 4 3 2 1 9 10 11 12 13 14 15 BASE ADDRESS ADDRESS DISABLE NONE ONE TWO ...

Страница 3: ...dress above 154 as the other modules will be assigned to nonexistent addresses NOTE Some panels support extended addressing In order to set the module above address 99 on compatible systems care fully remove the stop on the upper rotary switch If the panel does not support extended addressing do not set the lowest addressabove 94 4 A shunt is provided to disable a maximum of three unused modules M...

Страница 4: ...bled the lowest four addresses will be functional while the highest two will be dis abled For example if the shunt for Address Disable is placed on two and the base address switch is set to 28 the modules will be assigned to 28 29 30 and 31 NOTE Power must not be applied to the unit when changing functionality of the shunts NOTE The XP6 R must have power cycled for shunt changes to take effect NOT...

Отзывы: