background image

N500-77-00 

I56-1803-007 

 

©2006 Notifier

0

1

2

3

4

5 6

7 8 9

BASE ADDRESS

TO NEXT

DEVICE

STATUS
INDICATORS

  

   

+

  

   

+

  

   

+

  

   

+

  

   

+

  

   

+

IDC

ADDRESS

+0

+1

+2

+3

+4

+5

+6

+7

+8

+9

IDC

ADDRESS

IDC

ADDRESS

IDC

ADDRESS

IDC

ADDRESS

  

   

+

  

   

+

SLC

  

   

+

  

   

+

+

+

FROM PANEL OR

PREVIOUS DEVICE

47K

EOL

RESISTOR

ELR-47K

CONNECT MODULES TO

LISTED COMPATIBLE

NOTIFIER CONTROL

PANELS ONLY

SIGNAL LINE CIRCUIT 32 VDC MAX.

SEE PANEL INSTRUCTION MANUAL

FOR WIRE REQUIREMENTS.

CLASS B IDC (TYPICAL)

  

   

+

  

   

+

A/B SLCT

COM LOSS

DISABLE 1

DISABLE 2

0

1

2

3

4

5 6

7 8 9

10

11

12

13

14

15

POWER LIMITED

AND SUPERVISED

NOTE:

 Any number of UL listed contact closure devices may be used. DO NOT mix fire alarm initiating and supervisory devices on 

the same initiating device circuit. Install contact closure devices per manufacturer’s installation instructions.

NOTE:

 Any number of UL listed contact closure devices may be used. DO NOT mix fire alarm initiating and supervisory devices on 

the same initiating device circuit. Install contact closure devices per manufacturer’s installation instructions.

BASE ADDRESS

TO NEXT

DEVICE

STATUS
INDICATORS

   

  +

   

  +

   

  +

   

  +

   

  +

   

  +

IDC

ADDRESS

+0

+1

+2

+3

+4

+5

+6

+7

+8

+9

IDC

ADDRESS

IDC

ADDRESS

IDC

ADDRESS

IDC

ADDRESS

   

  +

   

  +

SLC

   

  +

   

  +

+

+

FROM PANEL OR

PREVIOUS DEVICE

CONNECT MODULES TO

LISTED COMPATIBLE

NOTIFIER CONTROL

PANELS ONLY

SIGNAL LINE CIRCUIT 32 VDC MAX.

SEE PANEL INSTRUCTION MANUAL

FOR WIRE REQUIREMENTS.

CLASS A IDC (TYPICAL)

   

  +

   

  +

A/B SLCT

COM LOSS

DISABLE 1

DISABLE 2

IDC 2

IDC 3

IDC 4

IDC 5

0

1

2

3

4

5 6

7 8 9

0

1

2

3

4

5 6

7 8 9

10

11

12

13

14

15

POWER LIMITED

AND SUPERVISED

REMOVE SHUNT FOR CLASS A.

Figure 8

Figure 9

Figure 8. Typical Initiating Device Circuit Configuration – Class B, Style B:

Figure 9. Typical Fault Tolerant Initiating Device Circuit Configuration – Class A, Style D:

C0252-01

C0251-01

Содержание XP10-M

Страница 1: ...ltage 10 2 VDC Maximum IDC Current 240µA per device C0202 00 C0206 00 BEFORE INSTALLING If the modules will be installed in an existing operational system inform the operator and local authority that the system will be temporarily out of service Disconnect the power to the control panel before installing the modules This system contains static sensitive components Always ground yourself with a pro...

Страница 2: ...l be installed in the chassis position in front of it Refer to Figures 6a and 6b for method two All necessary screws and standoffs are supplied with the modules Figure 5 Installation of rear module only method one Step 1 Insert the bottom of the XP10 M module down into a rear slot on the chassis Step 2 Carefully swing the upper edge of the board back towards the back of the chassis until it touche...

Страница 3: ...g plate screw 3 Set the address on the modules per the job drawing Use the rotary code switches to set the address of the first module between 01 and 150 In Class B operation the remaining modules are automati cally assigned to the next nine higher addresses For exam ple if the base address switch is set to 28 the next nine modules will be addressed to 29 30 31 32 33 34 35 36 and 37 The module is ...

Страница 4: ...structions NOTE Any number of UL listed contact closure devices may be used DO NOT mix fire alarm initiating and supervisory devices on the same initiating device circuit Install contact closure devices per manufacturer s installation instructions BASE ADDRESS TO NEXT DEVICE STATUS INDICATORS IDC ADDRESS 0 1 2 3 4 5 6 7 8 9 IDC ADDRESS IDC ADDRESS IDC ADDRESS IDC ADDRESS SLC FROM PANEL OR PREVIOUS...

Отзывы: