Notifier ONYXWorks Скачать руководство пользователя страница 2

2

NFN Gateway Installation & Operation Manual - P/N: 52307:Rev: D  06/01/07

Fire Alarm System Limitations

While a fire alarm system may lower insurance rates, it is not a substitute for fire insurance!

An automatic fire alarm system—

typically made up of smoke detec-

tors, heat detectors, manual pull stations, audible warning devices, 
and a fire alarm control panel with remote notification capability—can 
provide early warning of a developing fire.  Such a system, however, 
does not assure protection against property damage or loss of life 
resulting from a fire.  

The Manufacturer recommends that smoke and/or heat detectors be 
located throughout a protected premise following the recommenda-
tions of the current edition of the National Fire Protection Association 
Standard 72 (NFPA 72), manufacturer's recommendations, State and 
local codes, and the recommendations contained in the Guide for 
Proper Use of System Smoke Detectors, which is made available at 
no charge to all installing dealers.  These documents can be found at 
http://www.systemsensor.com/html/applicat.html.

A study by the Federal Emergency Management Agency (an agency 
of the United States government) indicated that smoke detectors may 
not go off in as many as 35% of all fires.  While fire alarm systems are 
designed to provide early warning against fire, they do not guarantee 
warning or protection against fire.  A fire alarm system may not pro-
vide timely or adequate warning, or simply may not function, for a 
variety of reasons: 

Smoke detectors 

may not sense fire where smoke cannot reach the 

detectors such as in chimneys, in or behind walls, on roofs, or on the 
other side of closed doors.  Smoke detectors also may not sense a 
fire on another level or floor of a building.  A second-floor detector, for 
example, may not sense a first-floor or basement fire.  

Particles of combustion or “smoke” 

from a developing fire may not 

reach the sensing chambers of smoke detectors because:

Barriers such as closed or partially closed doors, walls, or chimneys 
may inhibit particle or smoke flow.  

Smoke particles may become “cold,” stratify, and not reach the ceiling 
or upper walls where detectors are located.  

Smoke particles may be blown away from detectors by air outlets.  

Smoke particles may be drawn into air returns before reaching the 
detector.  

The amount of “smoke” present may be insufficient to alarm smoke 
detectors.  Smoke detectors are designed to alarm at various levels of 
smoke density.  If such density levels are not created by a developing 
fire at the location of detectors, the detectors will not go into alarm.  

Smoke detectors, even when working properly, have sensing limita-
tions.  Detectors that have photo-electronic sensing chambers tend to 
detect smoldering fires better than flaming fires, which have little visi-
ble smoke.  Detectors that have ionizing-type sensing chambers tend 
to detect fast-flaming fires better than smoldering fires.  Because fires 
develop in different ways and are often unpredictable in their growth, 
neither type of detector is necessarily best and a given type of detec-
tor may not provide adequate warning of a fire.  

Smoke detectors cannot be expected to provide adequate warning of 
fires caused by arson, children playing with matches (especially in 

bedrooms), smoking in bed, and violent explosions (caused by escap-
ing gas, improper storage of flammable materials, etc.). 

Heat detectors 

do not sense particles of combustion and alarm only 

when heat on their sensors increases at a predetermined rate or 
reaches a predetermined level.  Rate-of-rise heat detectors may be 
subject to reduced sensitivity over time.  For this reason, the rate-of-
rise feature of each detector should be tested at least once per year 
by a qualified fire protection specialist.  Heat detectors are designed 
to protect property, not life.  

IMPORTANT!  Smoke detectors 

must be installed in the same room 

as the control panel and in rooms used by the system for the connec-
tion of alarm transmission wiring, communications, signaling, and/or 
power.  If detectors are not so located, a developing fire may damage 
the alarm system, crippling its ability to report a fire.  

Audible warning devices 

such as bells may not alert people if these 

devices are located on the other side of closed or partly open doors or 
are located on another floor of a building.  Any warning device may 
fail to alert people with a disability or those who have recently con-
sumed drugs, alcohol or medication.  Please note that:

Strobes can, under certain circumstances, cause seizures in people 
with conditions such as epilepsy.  

Studies have shown that certain people, even when they hear a fire 
alarm signal, do not respond or comprehend the meaning of the signal.  
It is the property owner's responsibility to conduct fire drills and other 
training exercise to make people aware of fire alarm signals and 
instruct them on the proper reaction to alarm signals.  

In rare instances, the sounding of a warning device can cause tempo-
rary or permanent hearing loss.  

A fire alarm system 

will not operate without any electrical power.  If 

AC power fails, the system will operate from standby batteries only for 
a specified time and only if the batteries have been properly main-
tained and replaced regularly.  

Equipment used in the system 

may not be technically compatible 

with the control panel.  It is essential to use only equipment listed for 
service with your control panel.  

Telephone lines 

needed to transmit alarm signals from a premise to a 

central monitoring station may be out of service or temporarily dis-
abled. For added protection against telephone line failure, backup 
radio transmission systems are recommended.  

The most common cause 

of fire alarm malfunction is inadequate 

maintenance.  To keep the entire fire alarm system in excellent work-
ing order, ongoing maintenance is required per the manufacturer's 
recommendations, and UL and NFPA standards.  At a minimum, the 
requirements of NFPA 72 shall be followed.  Environments with large 
amounts of dust, dirt or high air velocity require more frequent mainte-
nance.  A maintenance agreement should be arranged through the 
local manufacturer's representative.  Maintenance should be sched-
uled monthly or as required by National and/or local fire codes and 
should be performed by authorized professional fire alarm installers 

Содержание ONYXWorks

Страница 1: ...ONYXWorks NFN Gateway PC Installation Operation Manual Document 52307 06 01 07 Rev D P N 52307 D ECN 06 053...

Страница 2: ...f detec tor may not provide adequate warning of a fire Smoke detectors cannot be expected to provide adequate warning of fires caused by arson children playing with matches especially in bedrooms smok...

Страница 3: ...l electronic assemblies prior to any drilling filing reaming or punching of the enclosure When possible make all cable entries from the sides or rear Before making modifications verify that they will...

Страница 4: ...rate If you have any comments you can email us Please include the following information Product name and version number if applicable Manual page number Your comment Send email messages to FireSystems...

Страница 5: ...d Installation 13 2 2 1 Network Interface Card Layout 14 Figure 2 1 NFN GW PC W Card Layout 14 Figure 2 2 NFN GW PC F Card Layout 14 Table 2 1 NCS NCW F Status LEDs 15 2 2 2 Network Interface Card Ins...

Страница 6: ...Table of Contents 6 NFN Gateway P N 52307 Rev D 06 01 07...

Страница 7: ...Tools software application to upload download data to a panel without having to physically visit the panel The NFN Gateway PC acts like any other node on a NFN network and is compatible with the follo...

Страница 8: ...one Workstation A Workstation can monitor or control a node and its points on the NFN network through the gateway Refer to Figure 1 2 and Figure 1 3 for network diagrams Figure 1 1 Direct Panel Gatewa...

Страница 9: ...rful systems multiple computers can be networked together over the IP network running multiple instances of the Workstation software application or other clients and gateways If the Workstation or gat...

Страница 10: ...n on page 13 Start Finished NFN Gateway Settings on page 18 About the NFN Gateway Mode Setting on page 19 NCM Address Setting on page 18 Login Password Settings on page 19 Network Interface Card Insta...

Страница 11: ...System Units Fifth Edition UL 864 Control Units for Fire Protective Signaling Systems Ninth Edition UL 1076 Proprietary Burglar Alarm Units and Systems Fifth Edition Underwriters Laboratories Canada D...

Страница 12: ...cumentation The following documentation resources is related to the ONYXWorks system ONYXWorks Workstation Manual P N 52342 ONYXWorks Configuration Tool P N 53038 NOTE The contents of this manual are...

Страница 13: ...n When using Style 4 and 7 use CH A and CH B pins The NFN GW PC F card uses fiber cable to connect the Transmit TX and Receive RX pins of one channel to the corresponding pins on the next NFN Gateway...

Страница 14: ...t on the Workstation Battery P N LITHBATT 3V Note The NCS NCW F is shipped with a paper strip between the clip and battery Remove the paper strip before powering Connect cable to an available COM port...

Страница 15: ...y STATA Yellow Channel A inactive for at least 16 seconds RCDA Green Illuminates to indicate data reception on NFN Network Channel A B HI Green Channel B High Threshold NCS NCW only STATB Yellow Chann...

Страница 16: ...mputer s cover and locate a vacant PCI slot Step 3 Remove the blank plate and save the screw from the vacant slot Step 4 Insert the Network Interface Card s edge connector into the vacant PCI slot and...

Страница 17: ...ork Interface Card is connected to NFN network through its network port using one of the following methods NFN GW PC F is the fiber network interface card that is connected to the transmit TX Receive...

Страница 18: ...Select the highest level entry in the Nodes list column hierarchy Figure 2 5 Gateway Node Selection Step 4 Select File Login to gain editing control of the selected gateway The Gateway Login window d...

Страница 19: ...rted the factory default password is used 00000000 eight zeros after the initial configuration it is highly recommended that you can the password Step 1 Select Tools Set Gateway Password The Gateway L...

Страница 20: ...NFN Gateway PC Configuration NFN Gateway PC Configuration Procedure 20 NFN Gateway Installation Operation Manual P N 52307 Rev D 06 01 07...

Страница 21: ...eceding the field s name Figure 3 1 NFN Gateway PC Property and Values Version Displays the gateway s version 3 2 1 GATEWAY SETTINGS Fields Gateway Label The name entered will only display on the NFN...

Страница 22: ...d Descriptions Node Is used to change the NFN network address of the panel VERSIONS If the NCM Version field is displayed in red then the version doesn t match the Local Node entry NOTE The NCM versio...

Страница 23: ...respective version information Connected Clients Used to display a window which lists the clients that are connected to the gateway 3 3 3 Tools Some menu choices are only displayed when a relative se...

Страница 24: ...NFN Config Tool Reference Information Menu Descriptions 24 NFN Gateway Installation Operation Manual P N 52307 Rev D 06 01 07...

Страница 25: ...n Procedure 18 mode 19 multiple 13 PC board LEDs 15 product description 7 Required Equipment 13 Gateway Config Tool field descriptions 21 Gateway Label 21 Gateway PC board layout 14 Gateway System Arc...

Страница 26: ...Index 26 NFN Gateway P N 52307 Rev D 06 01 07...

Страница 27: ...oid if there is a failure to maintain the products and systems in which they operate in a proper and workable manner In case of defect secure a Return Material Authorization form from our Return Autho...

Страница 28: ...World Headquarters 12 Clintonville Road Northford CT 06472 1610 USA 203 484 7161 fax 203 484 7118 www notifier com...

Отзывы: