Service Provided
6
NOTI•FIRE•NET™ PN 50257:E 7/5/01
•
Fiber Optic Cable - MIB-F
•
Twisted Pair Wire and Fiber Optic Cable MIB-WF
Each MIB has two communication ports. The MIB-W has two twisted pair wire ports, the MIB-F
has two fiber optic cable ports and the MIB-WF has one twisted pair wire and one fiber optic cable
port.
The NAM-232 provides a physical communication interface from the AFP-200, AFP-300/AFP-
400, AM2020/AFP1010 Analog Fire Panel to the following communication media which connect
nodes together forming a network:
•
Twisted Pair Wire NAM-232W
•
Fiber Optic Cable NAM-232F
The Serial Interface Board for
NOTI•FIRE•NET™
(SIB-NET) connects an AM2020/AFP1010
to the network through a MIB and permits communication between the AM2020/AFP1010 and
other nodes on the network. The SIB-NET supports all of the same functions as the SIB-2048A;
i.e. Annunciator Control System (ACS), printers, and CRTs.
Each AM2020/AFP1010 requires a network node address.
The NRT-NET interface card and the MIB allow the NRT and NCS to communicate with the
network. The NRT-NET interface card plugs directly into a computer expansion slot located on the
NRT and NCS. The MIB, which supports the physical connection to the network, plugs onto the
NRT-NET card to complete the network interface. Each NRT or NCS requires a network node
address.
The Repeaters (RPT) boost data signals between network nodes extending communication
distances. The RPT-W supports twisted pair wire, the RPT-F supports fiber optic cable, and the
RPT-WF supports twisted pair wire and fiber optic cable.
Service Provided
NOTI•FIRE•NET™
, when properly configured, is suitable for use as a Protected Premises Fire
Alarm System as defined in the National Fire Protection Association (NFPA) 72 documentation.
Related Documentation
To obtain a complete understanding of specific features within the network, or to become familiar
with the network functions in general, make use of the documentation listed in Table 1.
Table 1 Network Related Documentation
For information on…
Refer to…
Part No.
Noti•Fire•Net Nodes
AM2020/AFP1010 Manual
AFP-300/400 Fire Panel Installation Manual
AFP-300/400 Fire Panel Programming Manual
AFP-300/400 Fire Panel Operations Manual
AFP-200 Analog Fire Panel Manual
15088
50253
50259
50260
15511
Off-line programming utility
Veri•Fire Tools Help File
Verifire-CD
Networking
Noti•Fire•Net
3.0 Manual Manual
NCS Network Control Station
INA Intelligent Network Annunciator Manual
NAM-232 Manual
MIB Media Interface Board Manual
RPT Repeater Manual
50257
51095
15092
50038
50255
50256
Technical Manuals Online! - http://www.tech-man.com
firealarmresources.com