Section 2: System Overview
2.1 System Description
The NFS2-640/E control panel is a modular, intelligent fire alarm control panel (FACP) with an
extensive list of powerful features. The control panel uses the CPS-24/E integral power supply with
battery charger. This is combined with a mounting chassis and cabinet to create a complete fire
alarm control system. The panel supports FlashScan® protocol and has network capabilities. A
single SLC loop is supported with the basic equipment package; a second SLC loop can be added
by attaching an optional loop expander module (LEM-320).
Modular devices mount to the chassis to provide additional output circuits, including voice and
telephone modules to form a complete voice evacuation system. Five cabinet options are available
for enclosing system components; each is available in red or black.
The control panel has the capacity for installing up to 636 addressable points; 159 detectors and
159 monitor/control modules per SLC (Signaling Line Circuit).
2.1.1 Standard Features
•
Uses Notifier’s VIEW® early warning fire detection and the FlashScan or Classic Loop
Interface Protocol (CLIP) families of detectors and modules
•
Integral power supply with battery charger
•
Four standard Notification Appliance Circuits (NAC), Class A or B
•
Alarm, Trouble, Supervisory and Security relays
•
Support for 32 annunciator addresses, with 10 special annunciator groups
•
Supports Style 4, Style 6, Style 7 SLC loops
•
Connections to easily mount an expander board to add a second SLC loop
•
Releasing service using on-board NACs or FCM-1 modules
•
Logic Equations
•
Display scroll selection
•
Alarm verification supervisory indication (NYC)
•
Supervisory duct detectors
•
Supports Advanced Warning Addressable Combustion Sensing (AWACS) algorithms
•
Network operation
•
Battery charger supports 18 to 200 amp hour sealed lead-acid batteries
•
EIA-485 connections for wiring ACS annunciators (including LDM custom graphic
annunciators), TM-4 transmitter
•
EIA-232 connections for printer, CRT, printer/CRT, or network operation
•
Autoprogram feature for faster programming of new devices
•
The control panel provides 6 amps of usable output power in an alarm condition; it provides
3 amps of usable output power in normal or continuous operating conditions
•
Diagnostic LEDs and switches
•
Ground fault detection (0 ohm impedance)
•
Battery and battery-charger supervision, voltage-monitoring, and current-monitoring
•
Disconnect of deeply-discharged battery (low battery disconnect)
•
Programmable for strobe synchronization
•
Mass Notification System compatible