Operating Modes
Appendix C: Remote Terminal Access
NFS-640 Operations Manual P/N 51334:B 10/03/2003
69
Local Monitor Mode (LocM)
Functions, passwords, and special requirements of Local Monitor Mode (LocM) are:
Functions available with the Local Monitor Mode:
Table 20 Local Monitor Mode Functions
Functions:
Read Status, Alter Status, and Control Functions (Table 20).
Passwords:
User-defined password for Alter Status and Control functions.
Requirements:
Password security feature for Control Functions eliminates the need for
mounting the CRT-2 in an enclosure.
Function
Lets you...
Read Status
• Display the status of an individual point (Detector, Module, Panel
Circuit, or Zone).
• Display a list of all the points in Alarm or trouble.
• Display a list of all programmed points in the system.
• Step through the History buffer event by event.
• Display the entire History buffer.
Alter Status
• Disable/Enable an individual point.
• Change the sensitivity of a detector.
• Clear the verification counter of all detectors.
• Clear the entire History buffer.
• Set the AWACS alert and action levels.
Control
Functions
• Acknowledge
• Signal Silence
• System Reset
• Drill