Appendix A: Special Zone Operation
Time, Date, and Holiday Functions
60
NFS-640 Operations Manual P/N 51334:B 10/03/2003
How to View Holiday Function Selections
You can use the Read Status Entry option to view the current selection for the Holiday function. To do
so, press the following keys in sequence:
Note:
For instructions on programming the Holiday function, refer to the
NFS-640 Programming Manual.
The LCD display in Figure 46 gives an example of an LCD display of a Holiday function:
Figure 46 Sample Read Status for Holiday Function
How Time Control and Holiday Functions Work
Time and Holiday activation occurs automatically and does not require operator intervention. All
outputs with a CBE list containing F5 or F6 activate within the times specified for the days of the week
listed in F5 or F6. All smoke detectors with a CBE list containing F5 or F6 switch to their lowest
sensitivity (AL:9) within the times specified for the days of the week listed in ZF5 or ZF6. Refer to
“Appendix C: AWACS Applications” in the
NFS-640 Programming Manual
for details on setting
detector sensitivity.
Time Control is active for all days of the week listed in F5 or F6. Holidays listed in F7 are excluded
unless you list Holidays (H) in the day-of-week selection of F5 and F6 (shown in Figure 45). Enter the
time functions in a 24-hour format with the OFF time later than the ON time. After changing
programming using Time Control, always reset the control panel.
Note:
You can turn a
NON
FIRE
control point on and off, by listing zone F5 or F6 in the CBE list of a control/relay
module.
You can use Time Control zones F5 and F6 to program non-fire applications such as turning lights on
and off, setting a thermostat, and so on. For example, you can program zones F5 and F6 to activate
outputs at one time of day and deactivate outputs at later time, on specified days of a week. Table 16
contains descriptions of additional Time Control applications:
Table 16 Time Control Applications
Application Requirement
Control day and night sensitivity of
intelligent, addressable detectors
List zone F5 or F6 in the detector CBE. This
automatically sets the detector sensitivity to the
minimum setting (AL:9) during the day and
automatically returns detector sensitivity to
programmed sensitivity during the evening.
Control a specific date of-year
Input up to nine date in the Holiday selection screen
for Special Zone F7, then list zone F7 (Holiday) in
the CBE of a device.
Status ON (holiday function not in effect)
Holiday Function status banner
Holiday selections (for zone F7)
ON HOLIDAY FUNCTION 12/15 **/** **/**
**/** **/** **/** **/** **/** **/**