Program
Point Program
42
NFS-3030 Programming Manual P/N 51345:C 11/4/03
Figure 3.31 Module Point Programming Screen 2 (Control)
Soft Keys
ZONE MAP:
Displays the zones mapped to this point. The default value assigned to control modules
during initial programming is Z000 at Position 1 (refer to Figure 3.31), with the exception of control modules
with the following Type IDs: Telephone, Gen Alarm, Gen Supervis, Gen Trouble, and Trouble Pend.
To add or delete zones, press this soft key to proceed to the Module Zone Map screen. Refer to
"Zone Map" on page 36 for an illustration and explanation of the Detector Zone Map screen. The
Module Zone Map screen is the same except that Module replaces Detector in the title and the
module address appears instead of the detector address. Up to ten general, logic, release, special or
trouble zones may be mapped to a control module.
WALK TEST:
This field determines if the output will activate during Walk Test. Values are ON
(the output will activate) and OFF (the output will not activate). Default:
OFF
.
Note: The FZM-1 does not participate in Walk Test. The following Type ID codes do not
participate in Walk Test, and the
WALK
TEST
soft key will not appear when the screen displays:
REL END BELL, RELEASE CKT, REL CKT ULC, REL. FORM C, REL AUDIBLE, INST
RELEASE, NONRESET CTL, TELEPHONE, and FORM-C RESET. The FMM-1module with
SMOKE CONV, HEAT DETECT, or SMOKE DETECT does not participate in Walk Test.
SWITCH INHIBIT:
This field determines whether a user can manually activate an output.
Values are YES (can not be activated manually) or NO (can be activated manually). Default:
NO
SILENCEABLE:
This field determines whether the user can manually silence an activated output.
Values are as follows:
Note: This soft key will not appear for modules with Type ID codes where silence is not optional.
LOCAL MODE:
Press to toggle between Local Mode (
ON
) or no Local Mode (
OFF
). When there is
a communication loss between the panel and an SLC, the devices on the SLC that have been
selected for Local Mode participation (
ON
) will continue to function in a limited manner.
Participating input points on the loop will activate output points of the same Type ID designation
on the loop (that is, fire alarm input points will activate fire alarm output points, etc.). Control
NO
Not manually silenceable
YES
-
RESOUND FIRE
Silenceable, resound on fire alarm events
Network and Local Resound
YES
-
RESOUND
SUPERV
Silenceable, resound on supervisory events Network and Local Resound
YES
-
RESOUND
SECURITY
Silenceable, resound on security events
Network and Local Resound
YES
-
RESOUND TROUBLE
Silenceable, resound for trouble
Local Resound
YES
-
NO
RESOUND
Silenceable, does not resound
M O D U L E P O I N T P R O G R A M M I N G
L 0 3 M 1 5 0
Z O N E M A P :
Z 0 0 0
, Z 1 0 4
, Z 1 0 5
, Z 1 0 6
, Z 1 0 7
Z 1 1 0
, Z 1 1 4
, Z 1 1 5
, Z 1 1 6
, Z 1 1 7
W A L K T E S T : O F F
L O C A L M O D E : O N
S W I T C H I N H I B I T : Y E S
A C C E P T
S I L E N C E A B L E : N O
B A C K
Position 1
www.PDF-Zoo.com
Содержание NFS-3030/E
Страница 14: ...General Information Getting Started 14 NFS 3030 Programming Manual P N 51345 C 11 4 03 www PDF Zoo com...
Страница 60: ...Program Autoprogram Menu 60 NFS 3030 Programming Manual P N 51345 C 11 4 03 www PDF Zoo com...
Страница 76: ...Service Screens Application Corrupt Screen 76 NFS 3030 Programming Manual P N 51345 C 11 4 03 www PDF Zoo com...
Страница 120: ...CBE Zones and Equations Equations 120 NFS 3030 Programming Manual P N 51345 C 11 4 03 Notes www PDF Zoo com...
Страница 128: ...Type Codes FlashScan Codes 128 NFS 3030 Programming Manual P N 51345 C 11 4 03 www PDF Zoo com...
Страница 134: ...Glossary Glossary 134 NFS 3030 Programming Manual P N 51345 C 11 4 03 www PDF Zoo com...
Страница 142: ...NFS 3030 Programming Manual P N 51345 C 11 4 03 142 INDEX www PDF Zoo com...