AWACS™ Applications
Detector Status Display
114
NFS-3030 Programming Manual P/N 51345:C 11/4/03
If the detector is an Alert heat detector, the value is indicated by a temperature reading
(example:
148 DEGREES F
).
Line 12
The screen displays the Alarm and Prealarm levels that are in effect when read status is
requested. For example, if unoccupied settings are in effect, they will display.
A L A R M : 6 = 1 . 6 6 %
-
Six is the preprogrammed alarm level value for this detector: its
value is 1.66%, indicating the percent per foot obscuration value assigned to level 6.
P R E A L A R M : 3 = 0 . 4 7 %
-
Three is the preprogrammed alarm level value for this detector:
its value is 0.47%, indicating the percent per foot obscuration value assigned to level 3.
Line 13
A C T I O N / S T A T U S : N O N E / V E R Y C L E A N
-
This displays the maintenance status of
the device. The message that appears in this field depends on the drift compensation value. A
detector will automatically compensate for environmental contaminants and other factors over
time, until the tolerance value has been exceeded. The FACP will signal a trouble condition
when this level has been reached. Refer to the following table for messages and required
action.
Line 13 will not display for Acclimate detectors.
Line 14
P E A K S : 5 6 %
-
This value represents the highest percent per foot obscuration reading taken
by this detector. It can be a historical figure, and does not necessarily represent the highest
reading for this particular alarm. Re-initializing the detector would reset this value to zero.
V E R I F Y C O U N T : 0 2
-
This displays the number of times the detector has gone into
alarm. This count aids in differentiating false alarms from actual alarms by showing repeated
alarm events that have come into the device. In this example, the detector has gone into alarm
two times since the verification count was begun. The FACP will signal a trouble condition
when the verify count exceeds 20.
C O - O P : D 1 0 0 , 1 5 8
-
Indicates the address(es) of any detector(s) linked with the detector
that’s in alarm for Co-operative Multi-Alarm Sensing. This field will not display for Acclimate
detectors.
Line 15 - The current time and date are displayed in this line.
Message
Description
Replace/Malfunction
Replace the defective detector. The detector may not
operate properly.
None/Very Clean
No action necessary. The detector readings are near ideal.
None/Clean
No action necessary. Although not ideal, the detector will
activate at the selected sensitivity level.
None/Fairly Clean
No action necessary. The detector will activate at the
selected sensitivity level.
Needs Cleaning
Clean the detector soon. The detector may cause a false
alarm because it has reached the drift compensation
tolerance value.
Needs Immediate Cleaning
Clean immediately! The detector is a false alarm risk. The
drift compensation tolerance value has been exceeded.
www.PDF-Zoo.com
Содержание NFS-3030/E
Страница 14: ...General Information Getting Started 14 NFS 3030 Programming Manual P N 51345 C 11 4 03 www PDF Zoo com...
Страница 60: ...Program Autoprogram Menu 60 NFS 3030 Programming Manual P N 51345 C 11 4 03 www PDF Zoo com...
Страница 76: ...Service Screens Application Corrupt Screen 76 NFS 3030 Programming Manual P N 51345 C 11 4 03 www PDF Zoo com...
Страница 120: ...CBE Zones and Equations Equations 120 NFS 3030 Programming Manual P N 51345 C 11 4 03 Notes www PDF Zoo com...
Страница 128: ...Type Codes FlashScan Codes 128 NFS 3030 Programming Manual P N 51345 C 11 4 03 www PDF Zoo com...
Страница 134: ...Glossary Glossary 134 NFS 3030 Programming Manual P N 51345 C 11 4 03 www PDF Zoo com...
Страница 142: ...NFS 3030 Programming Manual P N 51345 C 11 4 03 142 INDEX www PDF Zoo com...