Detector Sensitivity Settings
AWACS™ Applications
NFS-3030 Programming Manual P/N 51345:C 11/4/03
109
Action Level
Action Functions
If you program a detector for Action Pre-Alarm and the detector reaches a level that exceeds the
programmed Pre-Alarm level, the control panel indicates an Action condition. The control panel
does the following functions when a detector reaches the programmed pre-alarm level:
•The Action message is sent to the History buffer and installed printers. The message is sent
(and time stamped) only at the time that it first occurred. This historical data could provide
valuable information about the progress of a fire.
•The
PRE
-
ALARM
LED and panel sounder pulse until acknowledged.
•The zone that is in the tenth position of the zone map for this detector activates. The tenth
zone is the right-most entry on line two of the detector zone map list in the Point
Programming screen. (For more information on detector zone positions, refer to Figure
3.24 and the accompanying text). The tenth zone can be used to control functions of a
detector or group of detectors once the pre-alarm level is reached. Tenth zone activations
also allow ACS annunciation by a detector or group of detectors in Action Pre-Alarm
condition.
•Zone Z000 (general alarm) or any other zone and the System Trouble and System Alarm
relays do not activate.
•The Pre-Alarm condition and the zone programmed will latch until system reset, even if the
sensitivity drops below the pre-alarm level.
•A subsequent alarm condition for this detector clears the Action indication from the LCD
display alarm list.
D.4 Detector Sensitivity Settings
How to Select Pre-Alarm and Alarm Sensitivity
Each detector provides a host of selectable intelligent options. The control panel provides nine
levels of Pre-Alarm (PA:1–PA:9) and Alarm (AL:1–AL:9) in percent per foot obscuration:
•
PA:0
no Pre-Alarm selection.
•
PA:1
the self-optimizing setting where the control panel selects a suitable Pre-Alarm level for
a detector.
•
PA:2–PA:9
the detector Pre-Alarm sensitivity level - with PA:2 the most sensitive and PA:9
the least sensitive.
•
AL:1–AL:9
the detector Alarm sensitivity level - with AL:1 the most sensitive and AL:9 the
least sensitive.
www.PDF-Zoo.com
Содержание NFS-3030/E
Страница 14: ...General Information Getting Started 14 NFS 3030 Programming Manual P N 51345 C 11 4 03 www PDF Zoo com...
Страница 60: ...Program Autoprogram Menu 60 NFS 3030 Programming Manual P N 51345 C 11 4 03 www PDF Zoo com...
Страница 76: ...Service Screens Application Corrupt Screen 76 NFS 3030 Programming Manual P N 51345 C 11 4 03 www PDF Zoo com...
Страница 120: ...CBE Zones and Equations Equations 120 NFS 3030 Programming Manual P N 51345 C 11 4 03 Notes www PDF Zoo com...
Страница 128: ...Type Codes FlashScan Codes 128 NFS 3030 Programming Manual P N 51345 C 11 4 03 www PDF Zoo com...
Страница 134: ...Glossary Glossary 134 NFS 3030 Programming Manual P N 51345 C 11 4 03 www PDF Zoo com...
Страница 142: ...NFS 3030 Programming Manual P N 51345 C 11 4 03 142 INDEX www PDF Zoo com...