Operation

Push in and pull down the handle where indicated to activate the station.  The NBG-12LX manual fire alarm pull

station includes one SPST (Single Pole, Single Throw) N/O (normally-open) switch and the addressable module

located inside the station.  Pushing in and pulling down the dual action handle causes the N/O alarm switch to close.

The word ‘ACTIVATED’ is displayed on the top of the handle when the pull station handle is pushed in and pulled

down.  The activated handle can not be reset without employing the key-lock reset.  To reset the NBG-12LX pull

station: 1) Insert the key and turn counterclockwise, 2) Open the door until the handle moves back into the

‘NORMAL’ position, 3) Close the door and lock it.  Closing the door automatically resets the switch to the

‘NORMAL’ position.

ACTIVATED

NBG-12LX PULL

STATION

CAUTION!

Install the Notifier NBG-12LX manual pull

station in accordance with these instructions,

applicable NFPA standards, national and

local Fire and Electrical codes and the re-

quirements of the AHJ (Authority Having

Jurisdiction).  Regular testing of the devices

should be conducted in accordance with the

appropriate NFPA standards.  Failure to fol-

low these directions may result in failure of

the  device  to  report  an  alarm  condition.

Notifier is not responsible for devices that

have been improperly installed, tested or

maintained.

For ADA compliance

, if the clear floor

space only allows forward approach to an

object, the maximum forward reach height

allowed is 48 in. (1,220 mm).  If the clear

floor space allows parallel approach by a

person in a wheelchair, the maximum side

reach height allowed is 54 in. (1,370 mm).

 Document 51093     Revision A2     ECN 01-293     09/14/01

Note - Opening the pull station

door will not activate or deac-

tivate the alarm switch.

DOOR ATTACHMENT

DOOR MATED TO BACKPLATE

STRIP GAUGE

 !"

7

5

2

)6

"""

''

With  the  door  and

backplate aligned and
‘keyed’ together, slide

the  holes  down  onto
the posts.

Closing  the  door  slightly
locks  the  door  and

backplate together.

1) If semi-flush mounting, proceed to step 4.

2) Mount the backbox 

before 

wiring to the pull station.

3) Before mounting the station, pull all necessary wiring through the backbox and

optional trim ring.

4) Remove the correct amount of wire insulation.  The pull station backplate is

molded with a strip gauge to measure the amount of insulation to be removed.

5) Connect the wiring from the addressable fire alarm control panel’s Signaling

Line Circuit (SLC) to Terminals 1(-) and 2(+) on the NBG-12LX addressable

pull station. SLC polarity is critical for this connection.

6) Connect the wiring going to the next device on the SLC to Terminals 1 and 2,

again being certain to observe polarity.

7)  If using a single-gang or SB-10 box for mounting, open the pull station door;

align the mounting holes of the pull station backplate to the backbox and screw

into place.  Tighten both top and bottom screws.

8) Set the address as described in ‘Setting the NBG-12LX Address’ and write the

address in the space provided on the label.

9) Close and lock the pull station door.