background image

DN-5331 • 08/19/04 — Page 1 of 2

GENERAL

The NAM-232 Network Adapter Module functions as an in-
terface between the AFP-200, AFP-300, and AFP-400 Fire
Alarm Control Panels and the 

NOTI•FIRE• NET™

. The

control panels each consume a single-node address on the
network. The NAM-232 interfaces to the control panels
through the EIA-232 serial communications port.

NOTI•FIRE•NET™

 is a series of systems that allow a group

of Fire Alarm Control Panels and other control equipment to
connect together to form a true peer-to-peer network. Equip-
ment that connects to 

NOTI•FIRE• NET™

 and communi-

cates with other equipment using the network may be re-
ferred to as a network node. An NFS-3030/NFS-640 Fire
Alarm System with an NCM Network Control Module installed;
an NCA Network Control Annunciator with an NCM installed;
an AM2020/AFP1010 Fire Alarm System with a SIB-NET Se-
rial Interface Board installed; an NCS Network Control Sta-
tion; an INA Intelligent Network Annunciator; and an AFP-
200/300/400 with a NAM-232 may all be network nodes. The
network supports communications over a twisted-pair wire
or fiber-optic medium. A network combination of both wire
and fiber may exist in the same network.

NOTE: Refer to manual network configuration section for panel
compatibility.

NOTI•FIRE•NET™

 is a trademark of NOTIFIER, 1994.

NETWORK FEATURES

AFP-200:

1. The network has the ability to send Acknowledge, Si-

lence, and Reset commands to the AFP-200.

2. Limited cooperative control-by-event (CCBE). Zones 1-

45 are network independent. Zones 46-89 are initialized
as one (1) “OR” equation.

3. The local node can send or receive network zone activa-

tions.

AFP-300/AFP-400:

1. Read/Alter Status; Group Enable/Disable; Individual Point

Enable/Disable.

2. The network has the ability to send Acknowledge, Si-

lence, and Reset commands to the AFP-300/AFP-400.

3. Cooperative control-by-event (CCBE). Zones 1-99 are

network independent.

4. The local node can send or receive network zone activa-

tions.

5. Remote ACS control via the INA EIA-485 port. Two (2)

annunciator addresses for a total of 128 annunciator
points per AFP-300/AFP-400 system.

FEATURES

NAM-232W: Network Adapter Module (Wire)

• Supports twisted-pair wire medium.
• Data is regenerated at each node.
• DIP switch selectable single-port or dual-port monitoring.

Network Adapter Module

Wire (NAM-232W)

S635

7165-0028:164
7165-0028:181
7170-0028:182

Section: Network Systems

• DIP switch selectable network drill option.
• Selectable Earth Fault detection per channel.
• Provides electrical isolation between nodes.
• Transmission rate of 312.5 Kbaud.
• Compatible with 

NOTI•FIRE•NET™

 Release 2.5 (or

higher).

• Diagnostic LED indicators.

MEA

California

State Fire

Marshal

NAM-232

Network Adapter Module

August 18, 2004

DN-5331 • A0-250

5331wire.wmf

104-93-E Vol. VIII

(NAM-232W)

CS118

Made in the U.S.A.

This document is not intended to be used for installation purposes. We try to keep our
product information up-to-date and accurate. We cannot cover all specific applications
or anticipate all requirements. All specifications are subject to change without notice.
For more information, contact NOTIFIER.  Phone: (203) 484-7161  FAX: (203) 484-7118

12 Clintonville Road, Northford, Connecticut  06472

NOTIFIER® is a Honeywell company.

Отзывы: