background image

DN-6720 • 08/23/04

 

— Page 1 of 6

GENERAL

Four different monitor modules are available for NOTIFIER in-
telligent controls to suit a variety of applications. Monitor mod-
ules are used to supervise a circuit of dry-contact input de-
vices, such as conventional heat detectors and pull stations,
or monitor and power a circuit of two-wire smoke detectors
(FZM-1).

FMM-1 

— is a standard-sized module (typically mounts to

a 4" [10.16 cm] square box) that supervises either a Class A
(Style D) or Class B (Style B) circuit of dry-contact input de-
vices.

FMM-101

 — is a miniature monitor module (a mere 1.3"

(3.302 cm) H x 2.75" (6.985 cm) W x 0.5" (1.270 cm) D) used
to supervise a Class B (Style B) circuit. Its compact design
allows the FMM-101 to often be mounted in a single-gang
box behind the device it’s monitoring.

FZM-1

 — is a standard-sized module used to monitor and

supervise compatible two-wire, 24 volt, smoke detectors on
a Class A (Style D) or Class B (Style B) circuit.

FDM-1

 — is a standard-sized dual monitor module used to

monitor and supervise two independent two-wire initiating
device circuits (IDCs) at two separate, consecutive addresses
in intelligent, two-wire systems.

FlashScan®

 (U.S. Patent 5,539,389) is a new communi-

cation protocol developed by NOTIFIER Engineering that
greatly enhances the speed of communication between ana-
log intelligent devices. Intelligent devices communicate in a
grouped fashion. If one of the devices within the group has
new information, the panel CPU stops the group poll and
concentrates on single points. The net effect is response
speed greater than five times that of other designs.

FlashScan® is a registered trademark of NOTIFIER.

FMM-1 MONITOR MODULE

• Built-in type identification automatically identifies this de-

vice as a monitor module to the control panel.

• Powered directly by two-wire SLC loop. No additional power

required.

• High noise (EMF/RFI) immunity.
• SEMS screws with clamping plates for ease of wiring.
• Direct-dial entry of address: 01 – 159 on FlashScan® sys-

tems, 01 – 99 on CLIP systems.

• LED flashes green during normal operation (this is a pro-

grammable option) and latches on steady red to indicate
alarm.

The  FMM-1 Monitor Module is intended for use in intelli-
gent, two-wire systems, where the individual address of each
module is selected using the built-in rotary switches. It pro-
vides either a two-wire or four-wire fault-tolerant Initiating
Device Circuit (IDC) for normally-open-contact fire alarm and
supervisory devices. The module has a panel-controlled LED
indicator. The FMM-1 can be used to replace MMX-1 mod-
ules in existing systems.

FMM-1, FMM-101, FZM-1, FDM-1

Monitor Modules

Monitor Modules

Monitor Modules

Monitor Modules

Monitor Modules

with FlashScan®

with FlashScan®

with FlashScan®

with FlashScan®

with FlashScan®

August 23, 2004

DN-6720 • H-220

Section: Intelligent/Addressable Devices

FMM-1
and
FZM-1

6724mod2.tif

FMM-1 Applications

 — Use to monitor a zone of four-

wire smoke detectors, manual fire alarm pull stations,
waterflow devices, or other normally-open dry-contact alarm
activation devices. May also be used to monitor normally-
open supervisory devices with special supervisory indica-
tion
 at the control panel. Monitored circuit may be wired as
an NFPA Style B (Class B) or Style D (Class A) Initiating
Device Circuit. A 47K ohm End-of-Line Resistor (provided)
terminates the Style B circuit. No resistor is required for su-
pervision of the Style D circuit. Maximum IDC loop length is
2,500 ft./762 m (20 ohms maximum).

S635

CS669

MEA

143-01-E

 (FDM-1)

317-01-E

(FMM-1/-101)

345-02-E

(FMM-1/-101)

457-99-E 

(FZM-1,

FMM-1/-101)

447-99-E

detail of FDM-1
— note “ones”
addresses are
0, 2, 4, 6, 8 only

6720fdm1.tif

This document is not intended to be used for installation purposes. We try to keep our
product information up-to-date and accurate. We cannot cover all specific applications
or anticipate all requirements. All specifications are subject to change without notice.
For more information, contact NOTIFIER. Phone: (203) 484-7161 FAX: (203) 484-7118

12 Clintonville Road, Northford, Connecticut 06472

NOTIFIER® is a Honeywell company.

U.S. Coast Guard

161.002/23/3 

(AFP-200:

FMM-1/-101, FZM-1)

161.002/42/1

(NFS-640: FMM-1/-101)

93/60141 (E3)

(FMM-1/-101, FZM-1)

94/60004/E2

(AFP200:

except FDM-1)

02/60007

(NFS-640: FDM-1)

7300-0028:202

California

State Fire

Marshal

Отзывы: