background image

BASE TERMINALS

No.             Function

 1

Remote Annunciator (+)

 2

Not used

 3

Not used

 4

Remote Annunciator (-)

 5

Not used

 6

N.O.

Supervisory Relay

 7

N.O

Form A Contacts

 8

N.O.

Alarm Relay

 9

N.O.

Form A

10

C.

Initiation

11

C.

Contacts

12

N.O.

Alarm Relay

13

N.C.

Form C

14

C.

Auxiliary Contacts

N550-03-00

1

I56-647-01

   Notifier, 12 Clintonville Rd., Northfield , CT 06472-1652 (203) 484-7161

B614LP PLUG-IN DETECTOR BASE

INSTALLATION INSTRUCTIONS

FOR USE WITH THE FOLLOWING SMOKE DETECTOR MODELS:
IN US:

CP-651, SD-651

IN CANADA:

CP-651A, SD-651A

IN EUROPE:

CP-651E, SD-651E

Before installing detectors, please thoroughly read manual I56-407-01, 

Guide for Proper Use of System Smoke

Detectors, which provides detailed information on detector spacing, placement, zoning, wiring, and special appli-
cations. Copies of this manual are available at no charge from Notifier. (For installation in Canada, refer to CAN/
ULC-S524-M86, 

Standard for the Installation of Fire Alarm Systems and CEC Part 1, Sec. 32.)

NOTICE: This manual should be left with the owner/user of this equipment.

IMPORTANT: The detector used with this base must be tested and maintained regularly following NFPA 72 re-
quirements. The detector used with this base should be cleaned at least once a year.

GENERAL DESCRIPTION

The model B614LP detector base is designed for use with Notifier model SD-651, SD-651A, and SD-651E photo-
electronic detector heads and CP-651, CP-651A, and CP-651E ionization detector heads. This four-wire base is
equipped with screw terminals for the connection of power, ground, relay connections, and an optional remote
annunciator. It also includes a resistor that limits current when the associated smoke detector is in the alarm state.

Figure 1. Terminal Layout

SPECIFICATIONS

Base Diameter:

6.2 inches (157 mm)

Base Height:

0.95 inches (24 mm)

Weight:

0.6 lb. (274 g)

Mounting:

4-inch square box with or without plaster ring. Min. depth–1.5 inches
4-inch octagon box. Min. depth–1.5 inches

Operating Temperature Range:

0° to 49°C (32° to 120°F)

Operating Humidity Range:

10% to 93% Relative Humidity, Noncondensing

}

}

}