AFP-3030 Operations Manual —
P/N DOC-01-033:C 05/12/2018
15
The Main Menu
General Information
P R E A L A R M : 3 = 0 . 4 7 % - Three is the preprogrammed alarm level value for this detector: its value is 0.47%, indicating the
percent per foot obscuration value assigned to level 3.
Line 13
A C T I O N / S TAT U S : N O N E / V E RY C L E A N - This displays the maintenance status of the device. The message that
appears in this field depends on the drift compensation value. A detector will automatically compensate for environmental
contaminants and other factors over time, until the tolerance value has been exceeded. The FACP will signal a fault condition when
this level has been reached. Refer to the following table for messages and required action.
For FSC-851 IntelliQuad detectors in CLIP mode, the status will display as None/Very Clean until it displays Needs Immediate
Cleaning. No intermediate levels are displayed.
Line 14
P E A K S : 5 6 % - This value represents the highest percent per foot obscuration reading taken by this detector. It can be a
historical figure, and does not necessarily represent the highest reading for this particular alarm. Re-initializing the detector would
reset this value to zero.
V E R I F Y C O U N T : 0 2 - This displays the number of times the detector has gone into alarm. This count aids in differentiating
false alarms from actual alarms by showing repeated alarm events that have come into the device. In this example, the detector has
gone into alarm two times since the verification count was begun. The FACP will signal a fault condition when the verify count is
exceeded. Displays as C O U N T for FSC-851 IntelliQuad and aspiration detectors.
C O - O P : D 1 0 0 , 1 5 8 - Indicates the address(es) of any detector(s) linked with the detector that’s in alarm for Co-operative
Multi-alarm Sensing. This field does not display for Acclimate, FSC-851 IntelliQuad, FCO-851 detectors, Beam detectors or Heat
detectors.
C O : - FSC-851 IntelliQuad and FCO-851 detectors only, FlashScan only - Carbon Monoxide reading in parts per million.
T E M P : - Displays degrees Centigrade for Acclimate, FSC-851, FCO-851, heat, and aspiration detectors
Line 15 - The current time and date are displayed in this line.
Line 16
B A C K - Press to return to the previous screen.
1.6.3 History Display (History Select Screen)
The History Select screen allows the user to select a type of history file to view, and to set time/date or point range viewing parameters.
The particular menu items will not appear on the History Display screen if no associated events are in the queue.
Figure 1.10 History Display Select Screen
Soft Keys
ALL EVENTS, ALARMS ONLY, FAULTS ONLY, SUPERVISORY ONLY, AND OTHERS - Pushing the associated soft key selects
the type of history to be viewed.
TIME/DATE INTERVAL - Sets a time/date interval of events to be displayed.
POINT RANGE - Sets a range of points for which events will be displayed.
Message
Drift Compensation %
Description
None/Very Clean
Less than 50
No action necessary. The detector readings are near ideal.
None/Fairly Clean
50 - 69
No action necessary. The detector will activate at the selected
sensitivity level.
Needs Cleaning
70 - 79
Clean the detector soon. The detector may cause a false alarm
because it has reached the drift compensation tolerance value.
Needs Immediate Cleaning
80 - 100
Clean immediately! The detector is a false alarm risk. The drift
compensation tolerance value has been exceeded.
Table 1.3
L A K E V I E W G E N E R A L H O S P I T A L
S Y S T E M N O R M A L
1 1 : 5 8 : 4 3 A T U E J A N 2 2 , 2 0 1 9
N 1 2 4
H I S T O R Y S E L E C T
A L L E V E N T S
O T H E R S
A L A R M S O N L Y
T I M E / D A T E I N T E R V A L
F A U L T S O N L Y
P O I N T R A N G E
S U P E R V I S O R Y O N L Y
B A C K