The control panel includes ten software zones that you can use to control releasing
functions. Releasing zones R0-R9—reserved for special releasing functions—allow up
to ten release operations. Each releasing zone operates independently, and is fully
programmable. From the Special Function Change Screen (Figure 21), select releasing
functions (R0-R9) to display the Releasing Function screen:
)LJXUH 5HOHDVLQJ )XQFWLRQ 6FUHHQ
1RWH ´6RDNµ HTXDOV WKH HODSVHG
WLPH LQ VHFRQGV EHWZHHQ
DFWLYDWLRQ RI D ]RQH DQG VKXW
GRZQ RI WKH UHOHDVLQJ ]RQH
YDOYHV
Each releasing zone includes four releasing functions, outlined in Table 25:
Table 25 Releasing Functions
1)3$6WDQGDUGV
You can use the AFP-300/AFP-400 as a control panel for agent release or preaction/
deluge control applications. When used with compatible, UL-listed actuating and
initiating devices, the control panel meets the requirements of the following NFPA
standards:
Table 26 NFPA Standards for Releasing Applications
35* 5(/($6( )81&7
5(/($6( &21752/
'(/$< ;; $%257 ;;; &5266 1 62$. ;;;; 5
Function
Lets You...
Delay
Program a 0-60-second delay. The delay equals the time that must elapse
between activating an initiating device and activating all zones mapped to the
active initiating device.
Abort
Select a 3-letter Abort switch-type code (ULI, IRI, NYC, or AHJ) that adds a
delay time to a releasing zone, or prevents a release of a releasing zone (see
Table 27 on page 27).
Cross
Select one of three types of cross zoning or “N” (not used). Cross zoning
requires tripping two or more devices to activate the outputs mapped to one of
the releasing zones.
Soak
Select a Soak timer (0-9999 seconds) or “0” (not used).
Standard
Covers
NFPA 12
CO2 Extinguishing Systems
NFPA 12A
Halon 1301 Extinguishing Systems
NFPA 12B
Halon 1211 Extinguishing Systems
NFPA 13
Sprinkler Systems
NFPA 15
Water Spray Systems
NFPA 16
Foam-water Deluge and Foam-water Spray Systems
NFPA 17
Dry Chemical Extinguishing Systems
NFPA 17A
Wet Chemical Extinguishing Systems
NFPA 2001