background image

Contact:

®

NovaTech Process Solutions, LLC

11500 Cronridge Dr., Suite 110
Owings Mills, MD  21117

T: 410.753.8300
Toll Free: 800.253.3842

www.novatechweb.com

8000 Series I/O

®

Product Catalog

8000 Series I/O

Содержание 8000 Series I/O

Страница 1: ... Contact NovaTech Process Solutions LLC 11500 Cronridge Dr Suite 110 Owings Mills MD 21117 T 410 753 8300 Toll Free 800 253 3842 www novatechweb com 8000 Series I O Product Catalog 8000 Series I O ...

Страница 2: ...ch Process Solutions LLC 11500 Cronridge Dr Suite 110 Owings Mills MD 21117 T 410 753 8300 Toll Free 800 253 3842 www novatechweb com This page intentionally left blank 8000 Series I O Product Catalog 8000 Series I O ...

Страница 3: ...ts NT 8109 DI DC 8 Channel DI 24VdC isolated sinking NT 8110 DI DC 8 channel DI 24Vdc non isolated module powered NT 8121 DI DC 16 channel DI 24Vdc non isolated module powered NT 8122 DI DC 16 channel DI 24Vdc isolated sinking NT 8111 DI AC 8 channel DI 115Vac isolated sinking NT 8112 DI AC 8 channel DI 115Vac non isolated module powered NT 8113 DI AC 8 channel DI 230Vac isolated sinking NT 8114 D...

Страница 4: ...es in any mix Up to 64 I O modules per node Up to 50 nodes per EthernetMPC card Wide operating temperature range 40 to 70 C General purpose and intrinsically safe I O within a single node Redundant Local Area Networks LAN and power supplies supported High channel density Zone 2 and Division 2 hazardous area mounting as standard I O module hot swapping even in Zone 2 and Divi sion 2 HART pass throu...

Страница 5: ...rovides power for the field wiring Where additional power is required for field devices such as high cur rent AC circuits power can be provided by means of cabled connections from each module to external relays This Bussed Field Power facility reduces instal lation time by removing the need to make daisy chain wiring connections at the field terminals of each I O module Node Operation A typical re...

Страница 6: ... the I O mod ules I O module carriers support eight I O modules Field Terminals Field terminals provide the interface between the I O modules and the field wiring They include fusing and loop disconnect as options A mechanical keying system prevents an I O module from being connected to the wrong type of field terminal Field terminals mount onto the module carrier one to each I O module They are c...

Страница 7: ...ch I O signals as Analog Inputs 4 20 mA 10 50 mA 0 10V program mable ranges of 0 50mV 0 100mV 0 1V and 0 10V 100 ohm platinum RTDs thermocouples Analog Outputs 4 20 mA 10 50 mA 0 10V Digital and Pulse Inputs Contact Closures 5 12 24 and 10 to 32 VDC Contact Closures 95 to 130 VAC Pulse Train Inputs up to 100 KHz 5 12 24 VDC Pulse Train Inputs up to 50 Hz 10 to 32 VDC and 95 to 130 VAC Digital and ...

Страница 8: ...tatus active inactive HART variable and status reporting enable disable Response Time Signal change to availability on Railbus 4 20 mA mode 27 ms max HART mode 0 75 s per channel Safety FM non incendive field wiring parameters each channel Voc 28 7 V Isc 33 mA Ca 0 17 µF La 11 0 mH Power Supplies Railbus 12V current 100 mA typ 150 mA max Bussed Field Power 2 wire Tx 300 mA max 24 V dc 10 4 wire Tx...

Страница 9: ...hannel status active inactive Response Time Signal change to availability on Railbus 27 ms max Safety FM non incendive field wiring parameters each channel Voc 28 7 V Isc 33 mA Ca 0 17 µF La 11 0 mH Power Supplies Railbus 12V current 100 mA typ 150 mA max Bussed Field Power 2 wire Tx 300 mA max 24 Vdc 10 4 wire Tx 60 mA max Mechanical Module Key Code A1 Module width 42 mm Weight 200 g Field Termin...

Страница 10: ...atus active inactive Response Time Signal change to availability on Railbus 27 ms max Safety FM non incendive field wiring parameters each channel Voc 28 7 V Isc 33 mA Ca 0 17 µF La 11 0 mH Power Supplies Railbus 12V current 100 mA typ 150 mA max Bussed Field Power 60 mA max at 24 Vdc 10 NT 8119 VI 05 Image Description 8 channel Analog Input 1 5 V Mechanical Module Key Code A1 Module width 42 mm W...

Страница 11: ...75 mA for 100ms Output turns off after 100ms at more than 25mA Calibration accuracy 10 C to 40 C 0 1 of FSR 40 C to 70 C 0 3 of FSR Resolution 15 bits typ Repeatability 0 05 of span Thermocouple Inputs THC Types B E J K N R S T W3 W5 Russian K Russian L Calibration Accuracy 10 C to 40 C 0 1 of span typ 40 C to 70 C 0 2 of span typ Cold junction compensation error 1 C 40 C to 70 C Resolution 14 bit...

Страница 12: ...sc 75mA Ca 0 61 µF La 11 3mH Power Supplies Railbus 12V current 60 mA typ 125 mA max Bussed Field Power 24 V dc 10 All configurations except 4 20mA with excitation 125 mA max 4 20mA with excitation 300 mA max Mechanical Module Key Code A1 Module width 42mm Weight 185g WARNING If this module is being used in an application that requires 250V ac rms channel to channel isolation it must be replaced o...

Страница 13: ...x Isolation any channel to Railbus 250 V ac rms Open circuit bleed current 0 5 µA nom Configurabe Parameters Sensor type user selectable Input dead zone hysteresis user defined value Selectable input filtering off 2 reading avge running avge Drive on open circuit fault disabled upscale downscale Channel status active inactive Response Times Signal change to availability on Railbus 120 ms min 420 m...

Страница 14: ...figurabe Parameters Sensor type user selection Input deadzone user defined value Selectable input filtering off 2 reading avge running avge Drive on open circuit fault disabled upscale Channel status active inactive Offset 2 wire RTD mode user defined value Response Times Signal change to availability on Railbus 180 ms min 840 ms max O C sensor detection 10 s Safety FM non incendive field wiring p...

Страница 15: ...enable disable NT 8102 HO IP Image Description 8 Channel Analog Output 4 20 mA with HART Response Time Signal change to availability on Railbus 4 20 mA mode 25 ms max HART mode 0 75 s per channel Safety FM non incendive field wiring parameters each channel Voc 28 7 V Isc 33 mA Ca 0 17 µF La 11 0 mH Power Supplies Railbus 12V current 100 mA typ 150 mA max Bussed Field Power 300 mA max at 24 Vdc 10 ...

Страница 16: ...el status active inactive Response time From Railbus command to output change 25 ms max Safety FM non incendive field wiring parameters each channel Voc 28 7 V Isc 33 mA Ca 0 17 μF La 11 0 mH Power Supplies Railbus 12V current 100 mA typ 150 mA max Bussed Field Power 300 mA max 24 V dc 10 Quiescent current 60 mA NT 8104 AO IP Image Description 8 channel Analog Output 4 20 mA Mechanical Module Key ...

Страница 17: ... available on Railbus 3 ms max Safety FM non incendive field wiring parameters each channel Vmax 30 V Imax 100 mA Ci 0 μF Li 0 mH Power Supplies Railbus 12V current 35 mA typ 55 mA max Bussed Field Power not required NT 8109 DI DC Image Description 8 channel Discrete Input 24 V dc isolated sinking Mechanical Module Key Code B2 Module width 42 mm Weight 170 g Field Terminals Field Wiring Recommende...

Страница 18: ...ew data available on Railbus 3 ms max Safety FM non incendive field wiring parameters each channel Voc 30 V Isc 15 2 mA Ca 0 12 μF La 151 mH Power Supplies Railbus 12V current 35 mA typ 55 mA max Bussed Field Power 40 mA 18 36 V dc NT 8110 DI DC Image Description 8 channel Discrete Input 24 V dc non isolated module powered Mechanical Module Key Code B1 Module width 42 mm Weight 170 g Field Termina...

Страница 19: ... counting enable disable Response Time I O response time Field event to new data available on Railbus 5 ms max Safety FM non incendive field wiring parameters each channel Voc 30 V Isc 3 5 mA Ca 0 12 μF La 1000 mH Power Supplies Railbus 12V current 90 mA typ 135 mA max Bussed Field Power 60 mA 18 30 V dc NT 8121 DI DC Image Description 16 channel Discrete Input 24 V dc non isolated module powered ...

Страница 20: ... event to new data available on Railbus Safety FM non incendive field wiring parameters each channel Vmax 30 V Imax 100 mA Ci 0 µF Li 0 mH NT 8122 DI DC Image Description 16 channel Discrete Input 24 V dc isolated sinking Power Supplies Railbus 12V current 90 mA typ 135 mA max Bussed Field Power not required Mechanical Module Key Code E2 Module width 42 mm Weight 210 g Field Terminals Field Wiring...

Страница 21: ...vailable on Railbus 33 ms max Power Supplies Railbus 12V current 40 mA typ 60 mA max Bussed Field Power not required Mechanical Module Key Code E4 Module width 42 mm Weight 170 g NT 8111 DI AC Image Description 8 channel Discrete Input 115 V ac isolated sinking Field Terminals Field Wiring Recommended Field Terminal Compatible Field Terminal General Purpose NT 8602 FT ST Standard NT 8604 FT FU Fus...

Страница 22: ...le on Railbus 33 ms max Power Supplies Railbus 12V current 40 mA typ 60 mA max Bussed Field Power 115 V ac 10 Frequency 50 60 Hz Mechanical Module Key Code E1 Module width 42 mm Weight 170 g NT 8112 DI AC Image Description 8 channel Discrete Input 115 V ac non isolated module powered Field Terminals Field Wiring Recommended Field Terminal Compatible Field Terminal General Purpose NT 8604 FT FU Fus...

Страница 23: ...data available on Railbus 33 ms max Power Supplies Railbus 12V current 40 mA typ 60 mA max Bussed Field Power not required Mechanical Module Key Code E5 Module width 42 mm Weight 170 g NT 8113 DI AC Image Description 8 channel Discrete Input 230 V ac isolated sinking Field Terminals Field Wiring Recommended Field Terminal Compatible Field Terminal General Purpose NT 8602 FT ST Standard NT 8604 FT ...

Страница 24: ... data available on Railbus 33 ms max Power Supplies Railbus 12V current 40 mA typ 60 mA max Bussed Field Power 207 to 265 V ac Frequency 50 60 Hz Mechanical Module Key Code E2 Module width 42 mm Weight 170 g NT 8114 DI AC Image Description 8 channel Discrete Input 230 V ac non isolated module powered Field Terminals Field Wiring Recommended Field Terminal Compatible Field Terminal General Purpose ...

Страница 25: ...urrent 45 mA typ 70 mA max Bussed Field Power 2 to 60 V dc NT 8115 DO DC Image Description 8 channel Discrete Output 2 60 V dc non isolated module powered Mechanical Module Key Code B6 Module width 42 mm Weight 200 g Field Terminals Field Wiring Recommended Field Terminal Compatible Field Terminal General Purpose NT 8604 FT FU Fused NT 8602 FT ST Standard Class 1 Div 2 or Zone 2 hazard ous area NT...

Страница 26: ...ime From Railbus command to output change 3 ms max Power Supplies Railbus 12V current 45 mA typ 70 mA max Bussed Field Power not required Mechanical Module Key Code B5 Module width 42 mm Weight 200 g NT 8117 DO DC Image Description 8 channel Discrete Output 2 60 V dc isolated unpowered Field Terminals Field Wiring Recommended Field Terminal Compatible Field Terminal General Purpose NT 8604 FT FU F...

Страница 27: ...mA max Bussed Field Power voltage 20 to 265 V ac NT 8116 DO AC Image Description 8 channel Discrete Output 20 265 V ac non isolated module powered Mechanical Module Key Code F1 Module width 42 mm Weight 220 g Field Terminals Field Wiring Recommended Field Terminal Compatible Field Terminal General Purpose NT 8604 FT FU Fused NT 8602 FT ST Standard Class 1 Div 2 or Zone 2 hazard ous area NT 8611 FT...

Страница 28: ...hange Power Supplies Railbus 12V current 75 mA typ 125 mA max Bussed Field Power not required NT 8118 DO AC Image Description 8 channel Discrete Output 20 265 V ac isolated unpowered Mechanical Module Key Code F4 Module width 42 mm Weight 220 g Field Terminals Field Wiring Recommended Field Terminal Compatible Field Terminal General Purpose NT 8604 FT FU Fused NT 8602 FT ST Standard Class 1 Div 2 ...

Отзывы: