LINETROLL 110E
/110Eµr User Guide February 2010 Page 13 of 16
8.
DIMENSIONS
Figure 12: LINETROLL 110Eµ/110Eµr physical
dimensions. All figures in mm.
9.
MOUNTING.
LINETROLL 110E
mounts directly on
the high voltage conductor using a Hot-
stick as shown in fig 14. It should be
mounted as close as possible to a traverse
to escape line vibrations.
Figure 14Hot-stick mounting, - close to the traverse
To fully cover all kinds of faults,
NORTROLL recommend to mount
indicators on all the phases in multi-phase
networks. Locate the indicators at strategic
points along the line.
9.1 Before mounting.
Make sure the indicator is programmed
(see
4.7 Programming
) and battery
connected before mounting on the line.
9.2 Live-line mounting by using a
Grip-All-Clamp
(shot-gun) Hot-Stick:
1.
Fix the indicator to the hot-stick
and raise/lift it to the line as shown
in fig 14.
2.
Pull the stick downwards and
against the line, until the line is in
correct position, see fig 15.
Release the grip-all stick.
Figure 15: Mounting & Grip-All_clamp hot stick
9.3 Removal.
1.
Fix the claw in the “eye” on the
horizontal part of the line-clamp,
see fig 15.
2.
Pull down, to release the indicator
from the line.
Figure 16: Removal from the line.
158 mm