EXHAUSTO
30
What to do
There is not a lot to do. The
chimney could be insulated or the
fan speed reduced. This is a
problem that is normally only
found in short and small steel
chimneys.
Reduce the fan speed.
Straighten and realign the hinges.
Remove the foreign matter.
Turn the vane. If it doesn't turn
without even the slightest
resistance, the bearings are worn
out and should be replaced.
Replace the vane.
Fasten the motor.
Probable Cause
The flue is undersized, e.g. the
flue area is less than 10% of the
fireplace opening.
The fan is oversized and running
too fast.
The hinges could be bent causing
the vanes to hit the wall on the fan
inlet.
Foreign matter could be stuck in
the bird screen/spark arrester.
A squeeking noise could indicate
that the motor bearings are bad.
The axial vane could be out of
balance causing the fan to wobble.
The bolts holding the motor may
be loose.
Problem
Airflow noise can be heard.
Mechanical noise from the fan.
Содержание EXHAUSTO RS 12
Страница 21: ...Appendix EXHAUSTO 20 NorthlineExpress com http www northlineexpress com Toll Free 1 866 667 8454 ...
Страница 33: ...EXHAUSTO 33 Notes NorthlineExpress com http www northlineexpress com Toll Free 1 866 667 8454 ...
Страница 34: ...EXHAUSTO 34 Notes NorthlineExpress com http www northlineexpress com Toll Free 1 866 667 8454 ...
Страница 35: ...EXHAUSTO 35 Notes NorthlineExpress com http www northlineexpress com Toll Free 1 866 667 8454 ...