Installation / Initial Set-Up 

 

21 

 

4. Select a Suitable Site

 

Before using the generator, you must select a suitable 

OUTDOOR

 

location for installation and 

operation.  This location should meet all of the criteria listed below. 

 

   WARNING:   

You must choose a suitable site for operating your generator to avoid equipment damage 
and/or injury and possible death from carbon monoxide poisoning, electric shock, or fire.  
Choose a site that meets all of the criteria specified.

 

Dry, level surface

 

The generator should be positioned on a dry, firm, level surface.

   

Ensure that the generator sits level and will not slide or shift during operation.  
If applicable, block the generator’s wheels to prevent sliding and shifting.  
 

Outdoors only – 
dangerous carbon 
monoxide exhaust 

 
   WARNING:  Carbon monoxide poisoning hazard 

The exhaust from your generator contains carbon monoxide (CO), a 
poisonous gas that can kill.  You cannot smell it, see it, or taste it.  

Carbon monoxide exhaust is given off whether you are using gasoline, 
natural gas, or propane as the fuel source to power the generator.

  

Follow the directions below for choosing a location to operate your 
generator in order to avoid carbon monoxide poisoning. 

 

The location you choose to operate the generator must be OUTDOORS 
and at least 20 feet from the home, away from windows, vents and air 
intakes, to allow proper ventilation. If you start to feel sick, dizzy, or 
weak while using the generator, shut off the engine and get to fresh air 
RIGHT AWAY

  

 

 

Never run the generator inside any closed or semi-enclosed spaces (even if 
outdoors), including homes, garages, basements, sheds, or boxes.  

These 

spaces can trap poisonous gases, even if you run a fan or open windows.

 

 

Never place the generator immediately adjacent to a building or other 
structure – allow at least 20 feet clearance.  

 

 

Place the generator so that the exhaust fumes will not be directed towards 
people or building air intakes.   

 

 

Ensure that working, battery-operated or battery back-up carbon monoxide 
alarms are used in any dwelling/structure that is in close proximity to the 
running generator. 

 

 

Note that this generator is NOT designed or approved for use in vehicles 
or marine applications.  Never run the generator inside RVs or other 
vehicles, on boats, or on pick-up truck beds. 

 

   

WARNING: 

Never attempt to attach ductwork to the muffler system to allow for 
installation inside an enclosure.  This could cause hot air deflection, 
heat build-up, and increased exhaust back-pressure, resulting in 
possible exhaust leakage or damage to the generator.   
 

 

Содержание M165601M.1

Страница 1: ...e only UL listed outdoor rated grounded extension cords of proper size NEVER plug the generator directly into a wall outlet ANY connection to a building s electrical system MUST ISOLATE THE GENERATOR...

Страница 2: ...Hazard Signal Word Definitions 2...

Страница 3: ...PORTABLE Power Source 17 4 Selecting a Suitable Site 21 5 Grounding the Generator 23 6 Battery Installation 24 Operation 1 General Safety Rules for Operation 25 2 Preparing for Operation 28 3 Starting...

Страница 4: ...rator and attached electrical devices and may also result in fire Be sure to read about site selection and grounding requirements for running this generator More detailed information can be found in t...

Страница 5: ...y questions about the appropriate use of this generator Warranty Registration Please fill in the warranty registration information in the back of this manual and have it on hand when you call in on a...

Страница 6: ...25 Height 22 25 22 25 Dry Weight 174 lb 200 lb Item Number 165604 165605 Maximum Output 8000 Watts W 10000 Watts W Continuous Output 6600 Watts W 8500 Watts W Voltage 120 240 Volt V 120 240 Volt V Pha...

Страница 7: ...798 RPM Fuel Type Non leaded automobile gasoline Non leaded automobile gasoline Fuel Capacity 11 gallons 11 gallons Oil Capacity see Honda Manual see Honda Manual Starting Method Electric Electric Bat...

Страница 8: ...use eye protection Caustic acid and explosive gases can cause blindness or severe burns NO smoking sparks or flames NEVER touch both battery terminals at the same time with your hand or any non insul...

Страница 9: ...1 Recoil 9 Generator Head 2 Fuel Valve Lever 10 6 5 Gallon Gas Tank 3 Engine Key Switch 165604 only 11 Muffler 4 Vibration Isolation Mount 12 Gasoline Tank Cap 5 Oil Drain Plug 13 Carbon Canister 6 O...

Страница 10: ...recommendations Reference 6 Oil Fill Port Refer to your Honda engine manual for oil change recommendations Reference 7 Battery not included Type required 12VDC 18AH Reference 8 Control Panel An electr...

Страница 11: ...ption Ref Description 1 Air Cleaner 8 Battery not included 2 11 Gallon Gas Tank 9 Control Panel 3 Gasoline Tank Cap 10 Vibration Isolation Mount 4 Choke 11 Generator Head 5 Engine Key Switch 12 Carbon...

Страница 12: ...mmendations Reference 7 Oil Fill Port Refer to your Honda engine manual for oil change recommendations Reference 8 Battery not included Type required 12VDC 35AH Reference 9 Control Panel An electrical...

Страница 13: ...o 5 times greater than the running wattage The running and starting wattage requirements are often listed on a device s nameplate If wattage is not given on the device s nameplate the wattage may be c...

Страница 14: ...Inkjet Printer 80 Iron 1200 Laser Printer 950 Lights Ten 75 Watt light bulbs 750 Microwave Oven 1000W 1000 Milk Cooler 1100 1800 Milker Vacuum Pump 2 HP 1000 2300 Miter Saw 10 1650 2400 Oscillating F...

Страница 15: ...s on your list This total must be lower than the continuous output rating of your generator Example Device to be Powered Greater of Starting Running Wattage Light Bulbs 10 75 watt 750 W Refrigerator F...

Страница 16: ...generator 5 Grounding 6 Battery installation electric start models only Each of these steps is discussed in detail below 1 Unpacking Delivery Inspection You should inspect the generator immediately a...

Страница 17: ...to your building s electrical system by isolating your generator from your utility company s power lines AND b Connects your generator to a critical subset of your building s circuits that are needed...

Страница 18: ...s electrical outlets There are different kinds of electrical outlets on your generator 1 120 240 Volt 30 Amp locking receptacle NEMA L14 30R locking receptacle compatible with L14 30P mating plug 2 12...

Страница 19: ...the amperage rating of an outlet 2 Extension cords may be used to power devices that are located at a distance from the generator However use only UL listed outdoor rated grounded extension cords of...

Страница 20: ...d extension cords can cause electric shock fire or damage to connected devices 3 All extension and appliance cords must be in good condition and not worn bare frayed or otherwise damaged WARNING Use o...

Страница 21: ...n monoxide poisoning The location you choose to operate the generator must be OUTDOORS and at least 20 feet from the home away from windows vents and air intakes to allow proper ventilation If you sta...

Страница 22: ...sure to water can cause electric shock You may operate the generator under an outdoor canopy like structure of heat resistant material that is open on all sides Make sure that all parts of canopy are...

Страница 23: ...into the ground close to the generator The pipe rod must penetrate moist earth the depth required will be dictated by local soil conditions Consult with an electrician 2 Connect an approved ground cl...

Страница 24: ...below General Battery Safety Rules ALWAYS use eye protection when handling batteries NEVER smoke or work near sparks or other sources of ignition NEVER touch both battery terminals at the same time wi...

Страница 25: ...adults should set up and operate the generator Do not let children operate Intended use Carefully read about and understand the intended use of this generator Do not use for other purposes as unforese...

Страница 26: ...of California to cause cancer birth defects or other reproductive harm Avoid inhalation of exhaust Wet conditions Do not operate the generator or handle any electrical equipment while standing in wat...

Страница 27: ...etain static electric charge as can objects made of conductive material e g metal water if they are not electrically grounded The static electric charge on an object such as a human body or plastic fu...

Страница 28: ...ding the Generator of this manual WARNING Electric shock hazard Always ensure generator is properly grounded to prevent electrical shock Perform scheduled maintenance as needed Make sure that any regu...

Страница 29: ...not smoke 2 Turn generator engine off and allow to cool for at least two minutes before removing gas cap Note A running or still hot engine is hot enough to ignite fuel 3 Remove generator gasoline ca...

Страница 30: ...the engine on a regular basis A tank of gasoline should last about 4 hours under 100 load and about 8 hours under 50 load Inspect Fuel System Check for Leaks Inspect fuel system check for leaks BEFORE...

Страница 31: ...conds release key and wait 10 seconds before attempting to start again Cranking the electric starter for more than 5 seconds continuously can overheat and damage the starter motor Release the key when...

Страница 32: ...asured voltage should be within the following ranges a 120V 10 at 120V receptacles b 240V 10 at 240V receptacles 4 If measured voltage is not within the specified range have generator adjusted by fact...

Страница 33: ...commended sequence is as follows a Connect items with motors such as refrigerators freezers air conditioners or small hand tools one at a time Let each motor stabilize before connecting the next devic...

Страница 34: ...ources of heat open flames sparks or pilot lights even if the generator s fuel tank is empty Residual fuel in the tank could ignite o Away from extreme high or low temperatures Prevent accidental star...

Страница 35: ...g fuel stabilizer to the gasoline following manufacturer s instructions Fuel stabilizer steps 1 Ensure gasoline tank is full 2 Add fuel stabilizer to fuel tank 3 Run engine at least 10 minutes after a...

Страница 36: ...ging the capacitor Replace guards Make sure all guards and shields are replaced after servicing the generator Repair Major service including the installation or replacement of parts should be performe...

Страница 37: ...clean If dust or debris accumulates on the generator clean the generator with a damp cloth or soft bristle brush Do not allow air intakes to become blocked Note Do not spray generator with a garden h...

Страница 38: ...eating a Generator is overloaded b Insufficient ventilation a Reduce the load See Power Load Planning Mgt section of this manual b Make sure there is at least 7 feet of clearance on all sides of gener...

Страница 39: ...will also void the warranty Engine speed Never attempt to modify the engine speed setting The engine speed is preset at 3600 RPM for safe and optimal performance of the generator If speed needs adjust...

Страница 40: ...GENERATOR FROM UTILITY POWER via an UL approved transfer switch installed by a licensed electrician in compliance with all applicable local building and electrical codes If the generator is not isolat...

Страница 41: ...rs This product contains or emits chemicals known to the State of California to cause cancer birth defects or other reproductive harm Avoid inhalation of exhaust Smoking sparks Never smoke near the ru...

Страница 42: ...or by untrained persons Storage location Store the generator in a dry location away from sources of heat open flames sparks or pilot lights such as water heaters space heaters furnaces clothes dryers...

Страница 43: ...Generator Exploded View Rev P 5 Item s 165601 165603 165604 43...

Страница 44: ...5604 19 306459 Engine ground wire 1 All 20 784706 Base 1 165601 787697 165603 165604 21 785291 Positive battery cable 1 165604 22 Northern 349920 Battery not included 12VDC 18AH n a 165604 23 787698 B...

Страница 45: ...Generator Exploded View Rev P 5 Item s 165605 165606 165607 45...

Страница 46: ...head 1 All 23 306459 Engine ground wire 1 All 24 787370 Base 1 All 25 82377 1 4 20 x 7 HHSC gr g zinc 2 All 26 777164 Battery cable positive 1 All 27 785609 Battery stop 1 All 28 Northern 349900 Batte...

Страница 47: ...Control Panel Parts List Rev P 5 47 Item 165601 Item 165603 Item 165604...

Страница 48: ...Control Panel Parts List Rev P 5 48 Item 165605 Item 165606 Item 165607...

Страница 49: ...er 2 165603 165604 165605 165606 165607 9 783085 NEMA L5 30 Receptacle 1 165603 165604 165605 165606 165607 10 783094 Engine Switch w key Electric Start 1 165604 11 783132 GFCI 5 20R Receptacle 4 dupl...

Страница 50: ...Generator Head Exploded Views Rev P 5 Item s 165601 165603 165604 165605 50...

Страница 51: ...604 165605 7 MA306408 End Cover Plug 1 165601 38271 165603 165604 165605 8 786124 Stator 1 165601 786125 165603 165604 779787 165605 9 778956 Rotor w Diode and Varistor 1 165601 779788 165603 165604 7...

Страница 52: ...Generator Head Exploded Views Rev P 5 Item s 165606 165607 52...

Страница 53: ...l 9 MA31015 M5 X 8 10mm Long 4 All 10 N A Rubber Cup 2 All 11 MA306403 Rear Bearing 1 All 12 MA306416 Nyloc Nut and Star Washer 1 All 13 MA30997 Grill 1 All 14 MA31065 Securing Stud Cap 1 All 15 MA309...

Страница 54: ...54 This page has intentionally been left blank...

Страница 55: ...void warranty Determining whether a part is to be replaced or repaired is the sole decision of NorthStar NorthStar will not provide for replacement of complete products due to defective parts Any cost...

Страница 56: ...56 Assembled by Northern Tool Equipment Company Inc Burnsville MN 55306 NorthernTool com...

Отзывы: