North Star 5500 BDG Скачать руководство пользователя страница 9

8

Load

Output

Percent of
Generator

Output

Speed
(RPM)

Frequency

(Hz)

Generator

voltage at 120V

Receptacle

0 %

3720

62.0

129V

50 %

3600

60.0

120V

100 %

3540

59.0

115V

Output voltage should be  checked  periodically  to

ensure continued proper  operation of  the  generating
plant and appliances, it can be checked with a portable
meter.  Frequency can be checked by using an electric
clock with a sweep second hand.

Timed against a wrist watch  or a  stop  watch  the

clock should be correct /- 2 seconds per
minute.  All speed setting adjustments  should  be  done
by  a qualified technician.

         GENERATOR  CARE

The generator head is a  two  pole, 3600  RPM,   60

Hz, brushless, revolving field and  synchronous  type
with two sealed radial roller bearings.

Proper care  and  maintenance are necessary  to

ensure a long trouble free life.

Exercising The Generator -

 

The generator

should be operated every four weeks.

    Warm  the

unit up by starting the engine and letting it run for 10 to
15 minutes.  This  will dry  out any moisture  that  has
accumulated in the windings.  If left, this moisture can
cause corrosion in the winding.    Frequent operation  of
the engine generator will also ensure that the set is
operating properly should it be needed in an
emergency.

Generator Maintenance 

- The  generator head  is

brushless and maintenance free.  Any major  generator
service including the installation  or  replacement of
parts should be performed only by a qualified electrical
service technician.  USE ONLY FACTORY
APPROVED REPAIR PARTS.

A. Bearing - The bearings used in this generators

are a heavy duty, sealed roller bearing. They  require
no maintenance  or lubrication.

B. Receptacles - Quality receptacles  have  been

utilized.  If a receptacle should become cracked or
otherwise damaged, replace it.  Using cracked or
damaged receptacles can be both dangerous to the
operator and destructive to the equipment.

 

WARNING, Stand-by  Operation

If your generator is to  be  used as  a  standby

electric power source in case of utility  failure, it must
be installed by a registered and licensed  electrician
and in compliance with  all applicable  state  and  local
electrical codes.  Also, local Fire Departments must  be
consulted concerning proper and safe handling
procedures for gasoline. 

NEVER

 connect  any

generator to any existing  electrical system without an
isolating, UL approved transfer switch, installed by a
licensed electrician.

Содержание 5500 BDG

Страница 1: ...P r o v e n P e r f o r m a n c e MODEL 5500 BDG ITEM 165913 Belt Driven Generator M165913B OWNER S MANUAL Any Questions Comments or Problems Call Customer Service at 1 800 270 0810...

Страница 2: ...Generator IMPORTANT If this machine is used by anyone who is not the owner or is loaned or rented make certain the operator Is instructed in the safe and proper operation of this machine Reads and un...

Страница 3: ...uency 59 0 62 0 Hertz Hz Power Factor 100 Engine 11 hp max 9 hp recommended Engine Speed 3540 3720 RPM 120 V Receptacle 20 Amp A duplex NEMA 5 20R 240 V Receptacle 20 Amp A Locking Device NEMA L6 20R...

Страница 4: ...TIFICATION Figure 1 Ref 1 4 00041 Ref Description Ref Description 1 Circuit Breakers 5 7 8 shaft 2 120V 20A Duplex Receptacle 6 Mounting feet 3 240V 20A Locking Receptacle 7 Fan vents 4 Grounding scre...

Страница 5: ...ment from original design and manufacture Before using the user shall determine the suitability of this product for its intended use and assumes liability therein ANSI SAFETY DEFINITIONS DANGER indica...

Страница 6: ...correct diameter sheave Note that a notched V belt requires only one sheave while the standard V belt requires 2 side by side sheaves and 2 V belts All V belts have a B size cross section Figure 3 000...

Страница 7: ...e 2 to 4 times as much current to start than to run Repulsion Induction motors are the easiest to start and require 1 5 to 2 5 times as much to start than to run Most fractional motors take about the...

Страница 8: ...inutes to restart due to its normal build up of compressor head pressure NOTE For extremely hard to start loads such as air conditioners and air compressors consult the equipment dealer to determine t...

Страница 9: ...nding Frequent operation of the engine generator will also ensure that the set is operating properly should it be needed in an emergency Generator Maintenance The generator head is brushless and maint...

Страница 10: ...ting a Generator is overloaded b Insufficient ventilation a Reduce the load See Load Application section of this manual b Make sure there is at least 3 feet of clearance on all sides of generator No o...

Отзывы: