background image

4

area indicates 120V.  During no load conditions, the
needle should be at or above the black line.

References 2 -  Lifting Eye. 

Use when lifting or

moving generator.

Reference 3 - Breather/Oil Fill Plug.   

Use SAE

90 gear oil.  Maintain the  correct oil  level.   Over  filling
can cause the oil to over heat and damage seals and
bearings.

References 4 - 1 3/8” Diameter 6 Spline Input

Shaft.

  540 RPM.   PTO driveline is  available  from

Northern, Item #165936.

References 5 - Sight Glass. 

Fill gear box until oil

is in the middle of the glass.

Reference 6 - Fan Vents.  

Never block the vent

slots or insert objects through the  slots.   The  closest
object should be at least 3 feet away from the vents.

Reference 7 - Mounting Holes.  

Use these four

locations to mount the generator head in place with
four 5/8” grade 5 bolts/anchors   (see  Installation
section ).

Reference 8 - 120V Receptacle.  

This twistlock

receptacle is a 120V  30A  receptacle,  National
Electrical Manufacturer’s Association (NEMA) number
L5-30R.  This  receptacle accepts  NEMA plug  number
L5-30P.

Reference 9 - 120V Receptacle.  

The generator

has a control panel with two 120V  20A straight blade
receptacle duplexes (two receptacles in a common
housing).  NEMA number is  5-20R.

Reference 10

 - 

Circuit Breaker.  

Two 20A  push-

to-reset thermal circuit breakers.

Reference 11

 - 

Circuit Breaker.  

One 30A  push-

to-reset thermal circuit breaker.

Reference 12 - 120/240V Receptacle.  

This

straight blade receptacle is 120/240V  60A.   This
receptacle accepts a NEMA plug number 14-60P.

ALWAYS

 use grounded male plugs.  The neutral

line of the generator is mechanically grounded  to  the
frame.  Matching NEMA male plugs must always be
used.

Reference 13 - Gear Box.  

Cast iron frame. 1:7

gear ratio.

References 14 - Warning Decals.  

Read and

follow all warnings.

Reference 15 - Grounding Clamp.  

Ground the

generator via the grounding clamp, to a copper  pipe or
rod  that is  driven into moist  soil.

Reference 16 - 100A Circuit Breaker.  

One 100A

thermal magnetic breaker.

Reference 17 - 120/240V 100A Pin and Sleeve.

This extremely safe and durable  receptacle  can be
used  for all large loads,  including  transfer  switches.
IEC 309-1 number 4100R12W.  A plug (part #32802)
can be ordered from NorthStar at 1-800-270-0810.

Reference 18

 

60A Circuit Breaker.  

One 60A

thermal magnetic breaker.

References 11  - Shield.   

Plastic implement

shield.   

NEVER

 operate generator without shield in

place.

INTRODUCTION

Before attempting to mount  your generator,

thoroughly study the instructions and cautions  in  this
manual to assure you are fully acquainted with  the
operation of all components of this generator. Proper
preparation,  operation and maintenance  will result in
operator safety, best performance and  long life of the
generator.  NorthStar is constantly improving its
products.  The specifications outlined herein are subject
to change without prior notice or obligation.   The
purchaser and/or user assumes liability  of  any
modification and/or alterations on this equipment from
original design and manufacture.  Before using, the
user shall determine the suitability  of this  product  for  its
intended use and assumes liability therein.

RULES FOR SAFE OPERATIONS

Safety precautions are essential when operating

this generator. Respectful and cautious  operation  will
considerably lessen the possibilities of a personal
injury.  This manual will warn of specific personal injury
potential, and these will be designated by the symbol:

                      

 

WARNING

  This generator is equipped

with a grounding clamp, located on the generator
frame for your protection.  Always complete the
grounding path from the generator  to a  copper
pipe/rod that is driven into moist earth, to  prevent
electrical shock.

ALWAYS

 use  electrical  cords  that are in good

condition.  Worn, bare, frayed or otherwise  damaged
cords can cause electric shock.

ALWAYS

 use a ground  fault  circuit interrupter

(GFCI) in damp or highly electrical conductive areas
and on construction job sites to prevent electric shock.

ALWAYS

 remove PTO driveline before  working

on the generator.

ALWAYS 

provide adequate ventilation. Do not

operate generator  in any enclosed or  narrow  space.
Engines consume oxygen and give off deadly  carbon
monoxide, a poisonous gas.  Improper ventilation  will
cause damage to generator and possible injury to
people.

ALWAYS

 

remove all oil or gasoline deposits and

accumulated dirt from generator and immediate area.
Keep generator head and engine clean.

ALWAYS

 

wear ear protection  while operating

generator.

ALWAYS

 

keep  area around generator  clean.

NEVER

 operate the generator without proper

guarding.

NEVER

 operate the generator continuously  when

PTO driveline is at angle greater  than  15

°

 both

horizontally and vertically .

Содержание 165937

Страница 1: ...MODEL 27500 PTOG ITEM 165937 Power Take Off Generator M165937D OWNER S MANUAL Any Questions Comments or Problems Call Customer Service at 1 800 270 0810 Hours Monday Friday 7 30 AM to 5 30 PM Saturda...

Страница 2: ...If this machine is used by anyone who is not the owner or is loaned or rented make certain the operator Is instructed in safe and proper operation of this machine Reads and understands the manuals per...

Страница 3: ...gnetic Gear Box Gear Ratio 1 7 Gear Oil SAE 80W 90 Oil Capacity 53 Qt 5 L Dimensions Length 36 95 93 9 cm Width 16 85 42 8 cm Height 20 79 52 8 cm Gross Weight 425 lb 193 2 kg ANSI SAFETY DEFINITIONS...

Страница 4: ...Clamp 6 Fan Vents 16 100A Circuit Breaker 7 Mounting Holes 17 120 240V 100A Pin and Sleeve 8 120V 30A Twistlock Receptacle 18 60A Circuit Breaker 9 120V 20A Duplex Receptacles 19 Shield 10 20A Circuit...

Страница 5: ...One 60A thermal magnetic breaker References 11 Shield Plastic implement shield NEVER operate generator without shield in place INTRODUCTION Before attempting to mount your generator thoroughly study...

Страница 6: ...minimize the angle of the driveline 15 maximum The smaller the angle of operation the longer the driveline will last When trailer mounting the generator select a trailer that is wide enough to withsta...

Страница 7: ...Hp motor Running Watts RI type Cap type SP type 1 6 525 7 11 9 18 16 22 1 4 700 9 15 12 23 22 32 1 3 875 11 18 14 29 26 35 1 2 1175 15 25 20 40 NA 1 1925 24 40 32 64 NA 1 1 2 2400 30 50 40 80 NA 2 29...

Страница 8: ...t 1 800 270 0810 GROUNDING All units must be grounded Drive a 3 4 or 1 copper pipe or rod into the ground close to the generator The pipe rod must penetrate moist earth Connect an approved ground clam...

Страница 9: ...rmed only by a qualified electrical service technician USE ONLY NorthStar APPROVED REPAIR PARTS AVAILABLE AT 1 800 270 0810 A Bearing The bearings used in this generator are a heavy duty sealed ball b...

Страница 10: ...n or loose wire c Defective receptacle d Defective stator e Defective rotor f Defective capacitor g Defective circuit breaker h Engine speed too slow I PTO not engaged j Gear box is malfunctioning a D...