Operation (cont’d) 

 

 

 

26

3. Starting the Engine  

After you have completed the pre-start checklist procedures, you are ready to start the engine.  
To start the engine: 

 

1) Disconnect all loads to the generator. 

 

2) Turn the fuel line valve to the ON position.  The fuel valve is located underneath the fuel tank. 

 

3) Start the engine: 

 

a)  Using electric start - 

i)  Turn the engine starting key to the START position and hold it there until the engine 

starts.    

ii)  Release the key when the engine starts or after 10 seconds. 
iii) If the engine does not start after 10 seconds, wait 15 seconds before attempting to start 

again. 

iv)  If the engine will not start, consult the “Troubleshooting” section of this manual.  

 

b)  Using recoil start – 

i)  Turn the engine starting key to the RUN position.   
ii)  Pull the starter grip lightly until you feel a strong resistance, then allow starter cord to 

return to the initial position. 

iii) Push down the decompression lever.  The lever is located on top of the engine and is 

colored RED. 

iv)  Now pull out the starter cord briskly and rapidly with both hands.   
v)  Allow starter cord to return slowly. 
vi)  If the engine will not start, consult the “Troubleshooting” section of this manual.  

 

 

4) Under long, continuous-run operating conditions, be prepared to: 

 

a)  Check and refuel the engine on a regular basis.  A tank of gas should last about 4 hours under 

100% load, and about 8 hours under 50% load.  See engine owner’s manual for more detail. 

 

      

WARNING

 

A running engine is hot enough to ignite fuel.  Never add fuel or remove fuel tank cap if 
engine is running or still hot.  Let cool at least 2 minutes. 

 

b)  Check engine oil level each time you refuel. 

 

c)  Change oil after the first 20 operating hours, and at least every 100 operating hours 

thereafter, as directed in the engine owner’s manual.   

 

     

WARNING: 

Never open oil port while engine is running.  Hot oil can spray over face and body. 

 

 

Содержание 165930

Страница 1: ...sion cords of proper size NEVER plug the generator directly into a wall outlet ANY connection to a building s electrical system MUST ISOLATE THE GENERATOR FROM UTILITY POWER via a UL approved transfer...

Страница 2: ...Hazard Signal Word Definitions 2...

Страница 3: ...NG BACK UP Power Source 13 4 Selecting a Suitable Site 16 5 Grounding the Generator 18 6 Battery Installation 19 Operation 1 General Safety Rules for Operation 20 2 Preparing for Operation 23 3 Starti...

Страница 4: ...o this generator s rated capacity You must not overload the generator Overloading will cause damage to the generator and attached electrical devices and may also result in fire Be sure to read about s...

Страница 5: ...ility of this product for its intended use and assumes liability therein Contact NorthStar Product Support at 1 800 270 0810 for any questions about the appropriate use of this generator Warranty Regi...

Страница 6: ...24 6 L Oil Capacity 1 76 US quarts 1 65 L Starting Method Electric Recoil 120V Receptacle 20 Amp A Duplex GFCI NEMA 5 20R 30 Amp A Locking device NEMA L5 30R 120 240V Receptacle 30 Amp A Locking devic...

Страница 7: ...r hand or any non insulated tools FLUSH immediately with water if battery acid contacts eyes skin or clothing CONNECT cables in correct sequence FIRST RED to POSITIVE terminal then BLACK to NEGATIVE t...

Страница 8: ...ir Cleaner Housing 4 120 Volt 20 Amp GFCI Duplex Receptacles 15 Decompression Lever 5 Hour Meter 16 Muffler 6 Charging Lamp 17 Ignition Fuse 7 120 Volt 30 Amp Locking Receptacle 18 Isolation Mounts 8...

Страница 9: ...ol panel is equipped with one NEMA L14 30R receptacle This receptacle accepts only NEMA L14 30P plugs This receptacle is popular for connection to a transfer switch for home standby power Reference 10...

Страница 10: ...te If wattage is not given on the device s nameplate the wattage may be calculated by multiplying the nameplate voltage by nameplate amperage Watts Volts X Amps Example conversion to watts 120 Volts X...

Страница 11: ...g at the same time with the generator 2 List the greater of the running or starting wattage next to each device as obtained from the devices nameplate or Table 1 If only the running wattage for a devi...

Страница 12: ...n electric start models only Each of these steps is discussed in detail below 1 Unpacking Delivery Inspection You should inspect the generator immediately after you receive delivery See the Machine Co...

Страница 13: ...r building s electrical system by isolating your generator from your utility company s power lines AND b Connects your generator to a critical subset of your building s circuits that are needed for em...

Страница 14: ...outlets There are three different kinds of electrical outlets on the generator 1 One 120 240 Volt 30 Amp locking receptacle NEMA L14 30R locking receptacle compatible with L14 30P mating plug 2 One 12...

Страница 15: ...0 Ga Cord 12 Ga Cord 14 Ga Cord 16 Ga Cord 10 2400 250 150 100 75 20 4800 125 75 50 25 30 7200 60 35 25 10 40 9600 30 15 10 50 12000 15 WARNING Use of under sized extension cords can cause electric sh...

Страница 16: ...way from all air intakes Never run the generator inside any closed or semi enclosed spaces even if outdoors including homes garages basements sheds or boxes These spaces can trap poisonous gases even...

Страница 17: ...ur generator s exhaust system is at least 7 feet from all combustible materials and buildings structures Equip the engine with a spark arrestor if the generator will be used near any ignitable forest...

Страница 18: ...pe 3 Run a 10 gauge wire from the clamp to the generator grounding post located on the rear of the generator head 4 Do not connect the generator grounding post to a water pipe or a ground used by a ra...

Страница 19: ...nt any sparking that could lead to an explosion ALWAYS follow the general battery safety rules and instructions listed below General Battery Safety Rules ALWAYS use eye protection when handling batter...

Страница 20: ...adults should set up and operate the generator Do not let children operate Intended use Carefully read about and understand the intended use of this generator Do not use for other purposes as unforese...

Страница 21: ...ate of California to cause cancer birth defects or other reproductive harm Avoid inhalation of exhaust Wet conditions Do not operate the generator or handle any electrical equipment while standing in...

Страница 22: ...te and retain static electric charge as can objects made of conductive material e g metal water if they are not electrically grounded The static electric charge on an object such as a human body or pl...

Страница 23: ...eeded Make sure that any regular maintenance has been performed as prescribed in this manual in the Maintenance Repair section 1 Refer to the engine owner s manual for engine maintenance instructions...

Страница 24: ...ine off and allow to cool for at least two minutes before removing gas cap Note A running or still hot engine is hot enough to ignite fuel 3 Remove generator fuel cap 4 Add fuel through the fill openi...

Страница 25: ...nder 50 load Inspect Fuel System Check for Leaks Inspect fuel system check for leaks BEFORE starting generator Do not start generator until all needed repairs have been completed WARNING Fuel leak haz...

Страница 26: ...en allow starter cord to return to the initial position iii Push down the decompression lever The lever is located on top of the engine and is colored RED iv Now pull out the starter cord briskly and...

Страница 27: ...The voltmeter s needle should be within the green area initially and during all load conditions 4 If measured voltage is not within the specified range have generator adjusted by factory authorized pe...

Страница 28: ...mmended sequence is as follows a Connect items with motors such as refrigerators freezers air conditioners or small hand tools one at a time Let each motor stabilize before connecting the next device...

Страница 29: ...empty Residual fuel in the tank could ignite o Away from extreme high or low temperatures Note Do not store with battery charger always connected Batteries that are over charged can boil themselves dr...

Страница 30: ...n of the engine Prepare engine for long term storage by o Removing all fuel from the tank and carburetor OR o Adding diesel fuel stabilizer to the fuel following manufacturer s instructions Fuel stabi...

Страница 31: ...nerated thereby discharging the capacitor Replace guards Make sure all guards and shields are replaced after servicing the generator Repair Major service including the installation or replacement of p...

Страница 32: ...s Replace if damaged Keep generator clean Keep generator clean If dust or debris accumulates on the generator clean the generator with a damp cloth or soft bristle brush Do not allow air intakes to be...

Страница 33: ...ed too high a Bring generator to a qualified technician for adjustment Generator overheating a Generator is overloaded b Insufficient ventilation a Reduce the load See Power Load Planning Mgt section...

Страница 34: ...will also void the warranty Engine speed Never attempt to modify the engine speed setting The engine speed is preset at 3600 RPM for safe and optimal performance of the generator If speed needs adjust...

Страница 35: ...ITY POWER via an UL approved transfer switch installed by a licensed electrician in compliance with all applicable local building and electrical codes If the generator is not isolated from the utility...

Страница 36: ...oroughly familiar with proper use of the equipment and all generator controls output receptacles and connections Know how to stop the generator quickly if needed Damaged Do not operate the generator w...

Страница 37: ...rting Safety After use Cool engine before storing Let engine cool for at least five minutes before storing A hot engine can be a fire hazard Shut off fuel supply Make sure fuel shut off valve is in th...

Страница 38: ...Generator Exploded View Rev R 38...

Страница 39: ...20 Generator Assembly 1 11 38462 Generator Mount 1 13 32844 Lower Bracket 6 14 777306 Base 1 15 38770 Control Panel Weldment 1 16 82067 Clip Nut 10 32 4 17 38771 Control Panel Assembly 1 18 32769 Name...

Страница 40: ...eceptacle 30 Amp 120 Volt 1 8 306422 Locking device Receptacle 30 Amp 120 240 Volt 1 9 31575 Engine Ignition Stop Run Start Switch 1 10 30646 Hour Meter 1 11 38763 Lead Wire Assembly 2 3 G1 G3 G4 G5 G...

Страница 41: ...57 Fan 1 4 781479 Drive End Bracket 1 5 38270 Enclosing Band 1 6 777304 End Cover 1 7 38271 End Cover Plug 1 8 780142 Stator 1 9 780229 Rotor 1 10 307479 Diode 2 11 780143 Securing Stud Nut 1 12 38276...

Страница 42: ...42 This page has intentionally been left blank...

Страница 43: ...h as engines are guaranteed by their manufacturer and can be serviced at factory authorized locations near you Any costs incurred due to replacement or repair of items outside of a NorthStar approved...

Страница 44: ...44 Manufactured by Northern Tool Equipment Co 2800 SouthCross Drive West P O Box 1499 Burnsville MN 55337 0499...

Отзывы: