Model: NSC0250-FROST 

Owners Manual 

|

 

P a g e

 

www.northslopechillers.com | (866) 826-2993 | 3130 S 1030 W, Suite 1 | Salt Lake City, UT 84119 

Temperature control settings 

Temperature Control Panel 

 

LED Indicator Lights 

D1 

ON: System is running in intelligent control mode 
OFF: System is running in temperature control mode 
FLASHING: Controller is in parameter setting mode or displaying room temperature 

D2 

ON: Indicates that the compressor is running and the chiller is actively chilling fluid 
OFF: Compressor is off (maintaining temperature) 
FLASHING: Chiller is in energy-saving state 

Alarm codes 

Error Code 

Problem 

E1 

High ambient (room) temperature 

E2 

High water temperature 

E3 

Low water temperature 

E4 

Ambient (room) temperature sensor failure 

E5 

Water temperature sensor failure 

When alarm occurs the alarm code and fluid temperature will alternate on the display 

The alarm sound can be suppressed by pressing any button, but the code will remain until the alarm condition is fixed. 

Check ambient temperature 

1.

 

Press 

 button to display ambient temperature 

2.

 

D1 indicator light will flash while ambient temperature is being displayed. The display will return to normal after 
6 seconds. 

Adjust temperature (Constant Temperature Mode) 

Constant temperature mode is the default control mode. When this mode is selected 

1.

 

Press 

 to display the current target temperature setting 

2.

 

Press 

 or 

 to adjust the target temperature setting 

3.

 

Press 

 to save and exit parameters and return to temperature display. If no buttons are pressed for 20 

seconds the controller will automatically return to the temperature display without saving changes. 

Adjust temperature (Intelligent Temperature Mode) 

1.

 

Press 

 to display the current target temperature setting 

2.

 

Press 

 or 

 to adjust the target temperature setting 

3.

 

Press 

 to save and exit parameters and return to temperature display. If no buttons are pressed for 20 

seconds the controller will automatically return to the temperature display without saving changes. 

Содержание NSC0250-FROST

Страница 1: ...tage outside of these ranges will damage the compressor i 110V model will operate on voltages between 100 130V ii 230V model will operate on voltages between 200 250V c Only use power sources that are...

Страница 2: ...3000 BTU hr 878 kW 90F ambient and 45F fluid Refrigerant R 410a Refrigerant Charge 77 lbs Precision 0 5 F 0 3 C Metering Device Capillary Protection Overcurrent protection for compressor flow alarm a...

Страница 3: ...Model NSC0250 FROST Owners Manual 3 P a g e www northslopechillers com 866 826 2993 3130 S 1030 W Suite 1 Salt Lake City UT 84119 Chiller overview FRONT BACK...

Страница 4: ...S 1030 W Suite 1 Salt Lake City UT 84119 Installation 1 Open package to check for damage and to verify that all components are there 2 Fill the reservoir 3 Connect inlet and outlet hoses 4 Plug in Pow...

Страница 5: ...by pressing any button but the code will remain until the alarm condition is fixed Check ambient temperature 1 Press button to display ambient temperature 2 D1 indicator light will flash while ambient...

Страница 6: ...ng parameter changes Parameter List Parameter Description Range Factory Default Notes Constant Temperature Mode Intelligent Mode F0 Temperature Setting F8 F9 45 F Constant Temperature F1 Temperature D...

Страница 7: ...the operation and performance of the Products themselves Only the Manufacturer is authorized to make any warranty or representation and the customer may not rely on any other warranty or representati...

Отзывы: