29
Yes
Check the voltage of power supply, if the voltage is about 220V, turn off the
power supply to indoor unit and turn it on again after 1 minute
Does the trouble occur again?
Check the voltage of secondary of T3 transformer in outdoor power board ,
is this voltage 12-14V(AC)
No
Replace the outdoor power board