Chapter 25 — Fault locating and clearing
Page 471 of 536
Option 11C Compact
Planning, Installation, Fault Clearing and CCBR Guide
Symptom:
Main circuit breaker off and all LEDs off
All the LEDs in the system are off and the circuit breaker on the power supply
in the cabinet is tripped. Use this procedure to clear the problem.
High room temperature or a power surge can shut down the system. Check
for these external conditions and if present, correct them then reset the
breaker.
You may need to replace:
•
the NTMW11 power supply
•
the NTMW01 SSC card (if the fault is in the main cabinet)
•
the cooling fan in the top of the affected cabinet
•
any one of the remaining circuit cards in the affected cabinet
Possible cause
Action
Thermal overload
Make sure nothing is blocking ventilation throughout the system.
Allow the system to cool for a few minutes then reset the breaker.
Make sure that the fan in the top of the cabinet is operating. If not,
replace the fan.
Check that the fan in the top of the cabinet is operating and is not
obstructed by items left on top of the cabinet. Listen to determine if
fan is operating. To further check or replace fan, remove top cover
to gain access to the fan. See
and
.
If the breaker trips, go to the next possible cause.
Defective circuit card in
the cabinet
Unseat all the circuit cards in the cabinet except the power supply.
Reset the breaker.
If the breaker trips, the power supply is defective. Remove the
existing power supply and install a new one.
If the breaker does not trip, reinstall the circuit cards one-at-a-time
until the breaker trips.
Содержание Meridian Meridian 1
Страница 3: ...553 3121 210 Standard 3 0 January 1999 ...
Страница 17: ...xiv Contents 553 3121 210 Standard 3 0 January 1999 ...
Страница 89: ...Page 70 of 536 Chapter 6 Bracing cabinets against earthquakes 553 3121 210 Standard 3 0 January 1999 ...
Страница 97: ...Page 78 of 536 Chapter 8 Installing a new system 553 3121 210 Standard 3 0 January 1999 ...
Страница 107: ...Page 88 of 536 Chapter 10 Installing the system ground 553 3121 210 Standard 3 0 January 1999 ...
Страница 113: ...Page 94 of 536 Chapter 11 Installing the power supply 553 3121 210 Standard 3 0 January 1999 ...
Страница 125: ...Page 106 of 536 Chapter 12 Adding an expansion cabinet 553 3121 210 Standard 3 0 January 1999 ...
Страница 139: ...Page 120 of 536 Chapter 13 Installing the circuit cards 553 3121 210 Standard 3 0 January 1999 ...
Страница 157: ...Page 138 of 536 Chapter 15 Installing and connecting SDI and Ethernet ports 553 3121 210 Standard 3 0 January 1999 ...
Страница 175: ...Page 156 of 536 Chapter 16 Starting up and testing the system 553 3121 210 Standard 3 0 January 1999 ...
Страница 209: ...Page 190 of 536 Chapter 18 Connecting the trunks 553 3121 210 Standard 3 0 January 1999 ...
Страница 323: ...Page 304 of 536 Chapter 21 Installing Hospitality 553 3121 210 Standard 3 0 January 1999 ...
Страница 419: ...Page 400 of 536 Chapter 23 Pre programmed data 553 3121 210 Standard 3 0 January 1999 ...
Страница 455: ...Page 436 of 536 Chapter 24 Changing pre programmed data 553 3121 210 Standard 3 0 January 1999 ...
Страница 555: ...Page 536 of 536 Chapter 25 Fault locating and clearing 553 3121 210 Standard 3 0 January 1999 ...