Nortek SH1QE4M1SP-24K Скачать руководство пользователя страница 4

4

Connecting Refrigerant Tubing Between the 

Indoor & Outdoor Unit

 CAUTION:

When servicing, cover or seal openings to 

minimize the exposure of the refrigerant system 

to air to prevent accumulation of moisture and 

other contaminants.

After outdoor and indoor unit placement has been determined, 

route refrigerant tubing between the equipment in accordance 

with sound installation practices.
•  Refrigerant tubing should be routed in a manner that 

minimizes the length of tubing and the number of bends 

in the tubing.

•  Refrigerant tubing should be supported in a manner that the 

tubing will not vibrate or abrade during system operation.

•  Tubing should be kept clean of foreign debris during 

installation.

•  Every effort should be made by the installer to ensure that 

the field installed refrigerant containing components of 

the system have been installed in accordance with these 

instructions and sound installation practices to insure 

reliable system operation and longevity.

•  The maximum recommended interconnecting refrigerant 

line length is 75 feet, and the vertical elevation difference 

between the indoor and outdoor sections should not exceed 

20 feet.

•  If precise forming of refrigerant lines is needed, a copper 

tubing bender is recommended. Avoid sharp bends and 

contact of the refrigerant lines with metal surfaces.

These units are equipped with single shot quick connect 

couplings. Together with the indoor section and line set, 

only 4 coupling connections are needed to provide a 100% 

sealed system.

1. Route the suction line and liquid line between indoor and 

outdoor sections, remove protector caps and plugs

2. Lubricate entire surface of the diaphragm “O” ring and 

threads of the male coupling using the lubricant supplied 

with the line set and a small brush.

3. Make sure that coupling halves are held in proper alignment 

with each other prior to starting the threads of female 

coupling nut onto the male half. Thread coupling halves 

together by hand until hand tight.

 CAUTION:

To prevent damage to the unit or internal 

components, it is recommended that two 

wrenches be used when loosening or tightening 

nuts. Do not over tighten!

4. Using two wrenches, tighten the coupling halves until 

seated or a definite resistance is felt.

5. Using a marker, mark a line from the coupling union nut 

to the bulkhead then tighten an additional 1/6 turn. See 

Table 1

 for torque values. Repeat for all couplings.

ELECTRICAL WIRING

 WARNING:

ELECTRICAL SHOCK OR FIRE HAZARD

To avoid risk of electrical shock, personal injury, 

or death, disconnect all electrical power to the unit 

before performing any maintenance or service. The 

unit may have more than one electrical supply.
Label all wires prior to disconnection when servicing 

the unit. Wiring errors can cause improper and 

dangerous operation

•  All electrical connections must be in compliance with all 

applicable local codes and ordinances, and with the current 

revision of the National Electric Code (ANSI/NFPA 70).

•  For Canadian installations the electrical connections and 

grounding shall comply with the current Canadian Electrical 

Code (CSA C22.1 and/or local codes).

Pre-Electrical Checklist

  Verify that the voltage, frequency, and phase of the supply 

source match the specifications on the unit rating plate.

  Verify that the service provided by the utility is sufficient 

to handle the additional load imposed by this equipment. 

Refer to the unit wiring label for proper high and low voltage 

wiring.

  Verify factory wiring is in accordance with the unit wiring 

diagram. Inspect for loose connections. See 

Figure 10 

(page 15)

.

Line Voltage

•  A wiring diagram is located on the inside cover of the 

electrical box of the outdoor unit. The installer should 

become familiar with the wiring diagram before making 

any electrical connections to the outdoor unit.

• 

An electrical disconnect must be located within sight 

of and readily accessible to the unit. This switch shall 

be capable of electrically de-energizing the outdoor unit.

•  Line voltage to the unit should be supplied from a dedicated 

branch circuit containing the correct fuse or circuit breaker 

for the unit. Incoming field wiring and minimum size of 

electrical conductors and circuit protection must be in 

compliance with information listed on the outdoor unit 

data label. Any other wiring methods must be acceptable 

to authority having jurisdiction.

•  The outdoor unit requires both power and control circuit 

electrical connections. Refer to the wiring diagram (

Figure 

10

) for identification and location of outdoor unit field wiring 

COUPLING

SIZE

TORQUE

MALE

COUPLING

FEMALE

COUPLING

NUT

FEMALE

COUPLING

BODY

3/8”

(10mm)

10-12 Ft-Lbs

(14-16 Nm)

3/4”

11/16”

5/8”

3/4”

(19mm)

35-45 Ft-Lbs

(47-61 Nm)

1-1/8”

1-5/16”

1”

7.8”

(22mm)

10-12 Ft-Lbs

(14-16 Nm)

1-1/8”

1-5/16”

1”

Table 1. Torque Values

Содержание SH1QE4M1SP-24K

Страница 1: ...FE PLACE FOR FUTURE REFERENCE INSTALLATION INSTRUCTIONS HEAT PUMP MAINTENANCE 7 Panel Removal 7 Panel Installation 7 REFRIGERANT CHARGING 8 Charging the Unit in AC Mode 8 Charging Charts Application N...

Страница 2: ...er refrigerant may damage the unit WARNING The information listed below and the next page should be followed during the installation service and operation of this product Failure to follow safety reco...

Страница 3: ...h the carrier Please consult your dealer for maintenance information and availability of maintenance contracts Please read all instructions before installing the unit Locating the Heat Pump Survey the...

Страница 4: ...ling union nut to the bulkhead then tighten an additional 1 6 turn See Table 1 for torque values Repeat for all couplings ELECTRICAL WIRING WARNING ELECTRICAL SHOCK OR FIRE HAZARD To avoid risk of ele...

Страница 5: ...Electrical Code Use the grounding lug provided in the control box for grounding the unit Thermostat Low Voltage Connections Thermostat connections should be made in accordance with the instructions su...

Страница 6: ...nected to the correct leads on the low voltage terminal strip Verify that the power supply branch circuit overcurrent protection is sized properly Verify that the thermostat is wired correctly Start U...

Страница 7: ...lectrical connections for tightness at the beginning of each heating and cooling season Service as necessary CAUTION The unit should never be operated without a filterinthereturnairsystem Replacedispo...

Страница 8: ...ing delay before the outdoor unit will energize Charging the Unit in AC Mode With Outdoor Temperatures Above 65 F 1 With the system operating at steady state measure the liquid refrigerant pressure in...

Страница 9: ...move refrigerant if above curve Add refrigerant if below curve SH1QE4M1SP24K CHARGING CHART COOLING 90 95 100 105 110 115 120 125 130 Liquid Temperature F Liquid Pressure psig 75 80 85 200 220 240 260...

Страница 10: ...elow curve SH1QE4M1SP42K CHARGING CHART COOLING Figure 8 Charging Chart for 3 5 Ton Models TXV Matches 90 95 100 105 110 115 120 125 130 Liquid Temperature F Liquid Pressure psig 75 80 85 200 220 240...

Страница 11: ...Pressure psig 75 80 85 200 220 240 260 280 300 320 340 360 380 400 420 440 460 480 500 520 540 560 580 600 135 Remove refrigerant if above curve Add refrigerant if below curve SH1QE4M1SP48K CHARGING C...

Страница 12: ...shown and the ambient temperature is above 50 F then a more accurate way to inspect the system for proper charge is with the cooling mode charging charts Switch the unit into cooling mode and allow i...

Страница 13: ...88 141 112 301 312 153 128 325 336 164 36 216 227 108 51 235 245 115 66 253 263 123 81 271 282 130 96 284 295 139 113 308 319 148 129 332 343 158 37 223 234 106 52 240 251 113 67 258 268 121 82 275 28...

Страница 14: ...311 120 98 340 347 125 114 372 379 129 129 405 412 134 Table 9 Verification Table for 3 5 Ton Models Table 10 Verification Table for 4 Ton Models OUTDOOR TEMPERATURE DEG F 0 10 20 30 40 50 60 SUC PRE...

Страница 15: ...For replacement wires use conductors suitable for 105 C 5 For ampacities and overcurrent protection see unit rating plate 6 Connect to 24 vac 40va class 2 circuit See furnace air handler installation...

Страница 16: ...hermostat level YES NO Is the heat anticipator setting correct If Applicable YES NO REFRIGERATION SYSTEM Wasunitgiven24hrwarmupperiod for crankcase heaters YES NO Stage 1 Liquid Pressure high side Sta...

Отзывы: