background image

3

HEAT PUMP INSTALLATION

General Information

Split system heat pumps are designed only for outdoor rooftop 

or ground level installations. This unit has been tested for 

capacity and efficiency in accordance with AHRI Standards 

and will provide many years of safe and dependable comfort, 

providing it is properly installed and maintained. Abuse, 

improper use, and/or improper maintenance can shorten the 

life of the appliance and create unsafe hazards.

To achieve optimum performance and minimize equipment 

failure, it is recommended that periodic maintenance be 

performed on this unit. The ability to properly perform 

maintenance on this equipment requires certain mechanical 

skills and tools.

Refer to the Quick Reference Data sheet for additional 

electrical, charging and unit information.

Before You Install the Heat Pump

  The cooling load of the area to be conditioned must be 

calculated and a system of the proper capacity selected. 

It is recommended that the area to be conditioned be 

completely insulated and vapor sealed.

  Check the electrical supply and verify the power supply 

is adequate for unit operation. The system must be wired 

and provided with circuit protection in accordance with 

local building codes. If there is any question concerning 

the power supply, contact the local power company.

  The indoor section (air handler, furnace, etc) should be 

installed before routing the refrigerant tubing. Refer to 

the indoor unit's installation instructions for installation 

details.

  All units are securely packed at the time of shipment and 

upon arrival should be carefully inspected for damage prior 

to installing the equipment at the job site. Verify coil fins 

are straight. If necessary, comb fins to remove flattened 

or bent fins. Claims for damage (apparent or concealed) 

should be filed immediately with the carrier.

  Please consult your dealer for maintenance information 

and availability of maintenance contracts. Please read all 
instructions before installing the unit.

Locating the Heat Pump

•  Survey the job site to determine the best location for 

mounting the outdoor unit.

•  Overhead obstructions, poorly ventilated areas, and areas 

subject to accumulation of debris should be avoided. See 

Figure 1

.

•  Sufficient clearance for unobstructed airflow through the 

outdoor coil must be maintained in order to achieve rated 

performance. See 

Figure 1

 for minimum clearances to 

obstructions.

•  Consideration should be given to availability of electric 

power, service access, noise, and shade.

Packaging Removal

To prevent damage to the tubing onnections, carefully remove 

the carton and user’s manual from the equipment. Discard 
the shipping carton.

Ground Level

Ground level installations must be located according to local 

building codes or ordinances and these requirements:

•  Clearances must be in accordance with those shown in 

Figure 1

.

•  A suitable mounting pad must be provided and be separate 

from the building foundation. The pad must be level and 

strong enough to support the unit’s weight. The slab height 

must be a minimum of 2” (5 cm) above grade and with 

adequate drainage. See 

Figure 1

.

Rooftop

•  The method of mounting should be designed so that it 

does not overload roof structures or transmit noise to 

the interior of the structure. The roof must be structurally 

capable of handling the weight of the unit.

•  Full perimeter support is required under the unit. Support 

must be made of weather resistant materials and installed 

prior to unit installation.

•  The support must be built to raise the unit 6" above the 

roof.

Figure 1. Clearance Requirements

2” Mounting Pad

24" for 

Service Access

12" or 18”

See Note

12" or 18”

See Note

DO NOT

OBSTRUCT

TOP OF UNIT

NOTE:

 Units require full perimeter clearances.

Installer must maintain 18” between two units

or 12” between single unit and structure.

6” from Building

or Structure

48”

Содержание SH1BF4M1SP Series

Страница 1: ...ANT CHARGING 8 Charging the Unit in AC Mode 9 Charging the Unit in Heating Mode 9 Charging Charts Application Notes 9 Figure 8 Charging Chart for 2 Ton Models 10 Figure 9 Charging Chart for 2 5 Ton Models 10 Figure 10 Charging Chart for 3 Ton Models 11 Figure 11 Charging Chart for 3 5 Ton Models 11 Figure 12 Charging Chart for 4 Ton Models 12 Figure 13 Charging Chart for 5 Ton Models 12 Heat Mode ...

Страница 2: ...lation service and operation of this unit Unqualified individuals should not attempt to interpret these instructions or install this equipment Failure to follow safety recommendations could result in possible damage to the equipment serious personal injury or death The installer must comply with all local codes and regulations which govern the installation of this type of equipment Local codes and...

Страница 3: ...diately with the carrier Please consult your dealer for maintenance information and availability of maintenance contracts Please read all instructions before installing the unit Locating the Heat Pump Survey the job site to determine the best location for mounting the outdoor unit Overheadobstructions poorlyventilatedareas andareas subject to accumulation of debris should be avoided See Figure 1 S...

Страница 4: ...ces a system with a filter dryer already present in the liquid line the filter dryer must be replaced with the one supplied with the unit The filter dryer must be installed in strict accordance with the manufacturer s installation instructions Optional equipment such as liquid line solenoid valves low ambient etc should be installed in strict accordance with the manufacturer s installation instruc...

Страница 5: ...o the unit or internal components it is recommended that two wrenches be used when loosening or tightening nuts Do not over tighten 5 Realign the assembly nut on the valve body and hand tighten both components Mark a line on both bodies and then tighten an additional turn using two wrenches The movement of the two lines will show how much the nut is tightened ELECTRICAL WIRING WARNING ELECTRICAL S...

Страница 6: ...omfireplaces sunlight or lighting fixtures and convective heat from warm air registers or electrical appliances Refer to the thermostat manufacturer s instruction sheet for detailed mounting and installation information Outdoor Fan Motor If the unit utilizes a 2 speed condenser fan motor this motor will operate on low speed when in low cooling and on high speed when in high cooling A relay within ...

Страница 7: ...em mode to COOL and the fan modetoAUTO Graduallylowerthethermostattemperature setpoint below room temperature and verify the outdoor unit and indoor blower energize 2 Verify blower wheel is spinning in direction indicated by arrow Feel the air being circulated by the indoor blower and verify that it is cooler than ambient temperature Listen foranyunusualnoises Ifunusualsoundsoccur determine the so...

Страница 8: ... pan in order to clear the bottom flange from the base pan See Figure 6 3 Swing the bottom of the panel out and pull the panel down to remove it from the unit Panel Installation 1 Insert the top corners of side panel flanges into the corner post channels as shown in Detail A in Figure 7 2 Slide the panel up into the top pan You may need to push on the center of the panel at the top in order to cle...

Страница 9: ...il the system is correctly charged If the pressure measured in Step 1 is less than the required liquid refrigerant pressure determined in Step 3 there is too little charge in the system Add refrigerant andrepeatSteps1through3untilthesystemiscorrectly charged Charging the Unit in Heating Mode Applies to SH1BF4M2SX 5 Ton Units only 1 Evacuate the unit to 350 500 microns 2 Weigh in the proper charge ...

Страница 10: ...below curve SH1BF4M1SP30K Charging Chart Cooling Figure 9 Charging Chart for 2 5 Ton Models TXV Matches Figure 8 Charging Chart for 2 Ton Models TXV Matches 200 220 240 260 280 300 320 340 360 380 400 420 440 460 480 500 520 540 560 580 600 75 80 85 90 95 100 105 110 115 120 125 130 135 Liquid Pressure psig Liquid Temperature F Remove refrigerant when above curve Add refrigerant when below curve S...

Страница 11: ...elow curve SH1BF4M1SP36K Charging Chart Cooling Figure 10 Charging Chart for 3 Ton Models TXV Matches 200 220 240 260 280 300 320 340 360 380 400 420 440 460 480 500 520 540 560 580 600 75 80 85 90 95 100 105 110 115 120 125 130 135 Liquid Pressure psig Liquid Temperature F Remove refrigerant when above curve Add refrigerant when below curve SH1BF4M1SP42K Charging Chart Cooling Figure 11 Charging ...

Страница 12: ...below curve SH1BF4M1SP48K Charging Chart Cooling Figure 12 Charging Chart for 4 Ton Models TXV Matches 200 220 240 260 280 300 320 340 360 380 400 420 440 460 480 500 520 540 560 580 600 75 80 85 90 95 100 105 110 115 120 125 130 135 Liquid Pressure psig Liquid Temperature F SH1BF4M2SX60K Charging Chart Cooling Remove refrigerant when above curve Add refrigerant when below curve Figure 13 Charging...

Страница 13: ...he rating label However if an inspection with these verification charts does not line up with the values shown and the ambient temperature is above 50 F then a more accurate way to inspect the system for proper charge is with the cooling mode charging charts Switch the unit into cooling mode and allow it to operate and stabilize for a few minutes then inspect the unit operation with the cooling mo...

Страница 14: ... 264 108 83 282 290 118 116 340 348 130 150 397 406 141 57 253 262 76 60 255 264 86 63 257 266 96 66 259 268 106 84 289 297 116 117 347 355 125 151 404 413 135 58 260 269 74 61 261 270 84 64 262 271 94 67 263 271 104 85 296 304 113 118 354 362 121 152 411 420 129 59 267 276 72 62 267 276 82 65 267 275 92 68 266 275 102 86 303 311 110 119 361 369 116 153 418 427 123 60 274 283 70 63 273 282 80 66 2...

Страница 15: ...ESS DISCH PRESS DISCH TEMP SUC PRESS LIQUID PRESS DISCH PRESS DISCH TEMP SUC PRESS LIQUID PRESS DISCH PRESS DISCH TEMP SUC PRESS LIQUID PRESS DISCH PRESS DISCH TEMP SUC PRESS LIQUID PRESS DISCH PRESS DISCH TEMP SUC PRESS LIQUID PRESS DISCH PRESS DISCH TEMP 35 212 223 134 49 235 245 135 64 257 267 136 78 280 290 138 94 293 303 146 111 321 331 160 128 348 359 174 36 219 230 132 50 241 251 133 65 262...

Страница 16: ...n systems that exceed 150 volts to ground 4 For replacement wires use conductors suitable for 105 C 5 For ampacities and overcurrent protection see unit rating plate 6 Connect to 24 vac 40va class 2 circuit See furnace air handler installation instructions for control circuit and optional relay transformer kits 1 Couper le courant avant de faire letretien 2 Employez uniquement des conducteurs en c...

Страница 17: ...ll power before servicing 2 For supply connections use copper conductors only 3 Not suitable on systems that exceed 150 volts to ground 4 For replacement wires use conductors suitable for 105 C 5 For ampacities and overcurrent protection see unit rating plate 6 Connect to 24 vac 40va class 2 circuit See furnace air handler installation instructions for control circuit and optional relay transforme...

Страница 18: ...supply connections use copper conductors only 3 Not suitable on systems that exceed 150 volts to ground 4 For replacement wires use conductors suitable for 105 C 5 For ampacities and overcurrent protection see unit rating plate 6 Connect to 24 vac 40va class 2 circuit See furnace air handler installation instructions for control circuit and optional relay transformer kits 1 Couper le courant avant...

Страница 19: ...nections use copper conductors only 3 Not suitable on systems that exceed 150 volts to ground 4 For replacement wires use conductors suitable for 105 5 For ampacities and overcurrent protection see unit rating plate 6 Connect to 24 vac 40va class 2 circuit See furnace airhandler installation instructions for control circuit and optional relay transformer kits 1 Couper le courant avant de faire let...

Страница 20: ... NO Is the heat anticipator setting correct If Applicable YES NO REFRIGERATION SYSTEM Wasunitgiven24hrwarmupperiod for crankcase heaters YES NO Stage 1 Liquid Pressure high side Stage 1 Suction Pressure low side REPLACEMENT PARTS Replacement parts are available through your distributor Please have the complete model and serial number of the unit when ordering replacement parts ELECTRICAL Capacitor...

Отзывы: