5
Figure 2. CoreSense
TM
Diagnostics Module
Y2 (Thermostat 2nd Stage Demand)
Y (Thermostat Demand)
Data Port
L (Alert)
R (24VAC)
Prot (Contactor Cutout)
DC SOL (2nd Stage Solenoid Power)
C (Common)
Power LED
Alert LED (Yellow)
Trip / Lock LED (Red)
Resetting Alert Codes
When the CoreSense
TM
Diagnostics module has detected a
series of adverse conditions that have caused it to lockout
the compressor, and after the issue has been resolved, it
is necessary to manually reset the module in order to clear
the present alert code.
The primary way of clearing the code and resetting the alert
is to press the reset button located on the module.
NOTE:
Pressing the reset will require a pin or a mini electronics
screwdriver. This button must be pressed and held for a
minimum of one second for the module to be reset. Pressing
the reset button clears the immediate lock code and the seven
day operating history. It will not clear the permanent module
history. In the case of the three-wire module, the codes can
be reset or cleared by cycling power to the module. This can
be done by disengaging the Common (C) terminal. This will
not clear the seven day operating history.
Grounding
WARNING:
The unit cabinet must have an uninterrupted or
unbroken electrical ground to minimize personal
injury if an electrical fault should occur. Do not
use gas piping as an electrical ground!
This unit must be electrically grounded in accordance with
local codes or, in the absence of local codes, with the National
Electrical Code (ANSI/NFPA 70) or the CSA C22.1 Electrical
Code. Use the grounding lug provided in the control box for
grounding the unit.
Thermostat Connections
• Thermostat connections should be made in accordance
with the instructions supplied with the thermostat and the
indoor equipment. Typical AC and thermostat hookups
are shown in
.
• The outdoor unit is designed to operate from a 24 VAC
Class II control circuit. The control circuit wiring must
comply with the current provisions of the NEC (ANSI/NFPA
70) and with applicable local codes having jurisdiction.
• The low voltage wires must be properly connected to the
units low voltage terminal block.
• The thermostat should be mounted about 5 feet above the
floor on an inside wall. DO NOT install the thermostat on
an outside wall or any other location where its operation
may be adversely affected by radiant heat from fireplaces,
sunlight, or lighting fixtures, and convective heat from
warm air registers or electrical appliances. Refer to the
thermostat manufacturer’s instruction sheet for detailed
mounting and installation information.
NOTE: FOR THE MATCH
*SA1BF4MN C6B(A,H)-X30(C,U)-C + *G7T-C
*SA1BF4MN C6B(A,H)-X30(C,U)-C + *G7S-C+*SHE
Only connect Y2 from thermostat to OD Y2
Furnace
Air Conditioner
OD Section
(Without CoreSense)
W2
W1
Y/Y2
G
R
C
Thermostat
O Y2 Y G RC RH C W2 W/E
Y1
Y/Y2
C
Y1
Figure 3. Typical 2-Stage Air Conditioner
(without CoreSense) with Gas Furnace
a problem. Alert identification codes are also listed in
Compressor Protection
The CoreSense
TM
Diagnostics module utilizes proprietary
algorithms to protect the compressor and system from
repeated trips of system pressure controls and the compressor
internal overload. The protection terminal of the module should
be wired in series with the system low pressure and high
pressure cutouts, as well as the compressor contactor. When
the module detects a series of trips as described below, it
will activate a lockout feature that opens the normally closed
protection contacts in the module, thereby cutting power to
the contactor and shutting off the compressor.