background image

5

Figure 2. CoreSense

TM

 Diagnostics Module

Y2 (Thermostat 2nd Stage Demand)
Y (Thermostat Demand)

Data Port
L (Alert)
R (24VAC)

Prot (Contactor Cutout)
DC SOL (2nd Stage Solenoid Power)

C (Common)

Power LED

Alert LED (Yellow)

Trip / Lock LED (Red)

Resetting Alert Codes

When the CoreSense

TM

 Diagnostics module has detected a 

series of adverse conditions that have caused it to lockout 

the compressor, and after the issue has been resolved, it 

is necessary to manually reset the module in order to clear 

the present alert code.
The primary way of clearing the code and resetting the alert 

is to press the reset button located on the module. 

NOTE:

 Pressing the reset will require a pin or a mini electronics 

screwdriver. This button must be pressed and held for a 

minimum of one second for the module to be reset. Pressing 

the reset button clears the immediate lock code and the seven 

day operating history. It will not clear the permanent module 

history. In the case of the three-wire module, the codes can 

be reset or cleared by cycling power to the module. This can 

be done by disengaging the Common (C) terminal. This will 

not clear the seven day operating history.

Grounding

 WARNING:

The unit cabinet must have an uninterrupted or 

unbroken electrical ground to minimize personal 

injury if an electrical fault should occur. Do not 

use gas piping as an electrical ground!

This unit must be electrically grounded in accordance with 

local codes or, in the absence of local codes, with the National 

Electrical Code (ANSI/NFPA 70) or the CSA C22.1 Electrical 
Code. Use the grounding lug provided in the control box for 
grounding the unit.

Thermostat Connections

•  Thermostat connections should be made in accordance 

with the instructions supplied with the thermostat and the 

indoor equipment. Typical AC and thermostat hookups 

are shown in 

Figure 3

.

•  The outdoor unit is designed to operate from a 24 VAC 

Class II control circuit. The control circuit wiring must 

comply with the current provisions of the NEC (ANSI/NFPA 
70) and with applicable local codes having jurisdiction.

•  The low voltage wires must be properly connected to the 

units low voltage terminal block.

•  The thermostat should be mounted about 5 feet above the 

floor on an inside wall. DO NOT install the thermostat on 

an outside wall or any other location where its operation 

may be adversely affected by radiant heat from fireplaces, 

sunlight, or lighting fixtures, and convective heat from 

warm air registers or electrical appliances. Refer to the 

thermostat manufacturer’s instruction sheet for detailed 

mounting and installation information.

NOTE: FOR THE MATCH 
*SA1BF4MN C6B(A,H)-X30(C,U)-C + *G7T-C
*SA1BF4MN C6B(A,H)-X30(C,U)-C + *G7S-C+*SHE

 Only connect Y2 from thermostat to OD Y2

Furnace

Air Conditioner 

OD Section

(Without CoreSense)

W2 

W1 

Y/Y2 

Thermostat

O Y2 Y G RC RH C W2 W/E

Y1

Y/Y2 

Y1

Figure 3. Typical 2-Stage Air Conditioner 

(without CoreSense) with Gas Furnace

a problem. Alert identification codes are also listed in 

Table 

1, (page 15)

.

Compressor Protection

The CoreSense

TM

 Diagnostics module utilizes proprietary 

algorithms to protect the compressor and system from 

repeated trips of system pressure controls and the compressor 

internal overload. The protection terminal of the module should 

be wired in series with the system low pressure and high 

pressure cutouts, as well as the compressor contactor. When 

the module detects a series of trips as described below, it 

will activate a lockout feature that opens the normally closed 

protection contacts in the module, thereby cutting power to 

the contactor and shutting off the compressor.

Содержание SA1BF4M2SN Series

Страница 1: ...IMPORTANT SAFETY INFORMATION 2 AIR CONDITIONER INSTALLATION 3 General Information 3 Before You Install this Unit 3 Locating the Air Conditioner 3 Packaging Removal 3 Ground Level 3 Roof Mount 3 Connec...

Страница 2: ...nt Refrigerant and electrical line should be routed through suitably waterproofed openings to prevent water from leaking into the structure This unit is designed for outdoor installations only and sho...

Страница 3: ...n 18 inches from the outside walls of the facility and in an area free from overhead obstructions to ensure unrestricted airflow through the outdoor unit Sufficient clearance for unobstructed airflow...

Страница 4: ...for loose connections Line Voltage A wiring diagram is located on the inside cover of the electrical box of the outdoor unit The installer should become familiar with the wiring diagram before making...

Страница 5: ...instructions supplied with the thermostat and the indoor equipment Typical AC and thermostat hookups are shown in Figure 3 The outdoor unit is designed to operate from a 24 VAC Class II control circu...

Страница 6: ...ify that it is warmer than ambient temperature Listen for any unusual noises Ifunusualsoundsoccur determinethesourceofthenoise and correct as necessary AIR CONDITIONER MAINTENANCE WARNING To prevent e...

Страница 7: ...unit Use only gage line sets which have a Schrader depression device present to actuate the valve Ahigh pressureswitchisfactory installedandlocatedinthe liquidlineinternaltotheoutdoorunit Theswitchis...

Страница 8: ...the recommended superheat value in the table then ADD refrigerant For TXV systems If your measured subcooling at the liquid valve is LESS THAN the recommended subcooling value in the table then ADD re...

Страница 9: ...uitable for 105 5 For ampacities and overcurrent protection see unit rating plate 6 Connect to 24 vac 40va class 2 circuit See furnace airhandler installation instructions for control circuit and opti...

Страница 10: ...R L2 T2 COMPRESSOR CONTACTS L1 T1 COMPRESSOR OUTDOOR FAN MOTOR Y2 Y L R C P DC SOL CSC C R Y2 Y LPS HPS CORESENSE COMPRESSOR SOLENOID COIL 24 VOLT FIELD CONNECTIONS CC Contactor Coil CCH Crankcase He...

Страница 11: ...0 Hz WIRING DIAGRAM 7110150 1209 FIELD WIRING LEGEND LOW VOLTAGE HIGH VOLTAGE BLACK BLUE YELLOW BLUE BLACK 208 230V H C F CCH R C S S C H L2 T2 COMPRESSOR CONTACTS L1 T1 COMPRESSOR FAN MOTOR L FAN REL...

Страница 12: ...e unit rating plate 6 Connect to 24 vac 40va class 2 circuit See furnace airhandler installation instructions for control circuit and optional relay transformer kits 7 Couper le courant avant de faire...

Страница 13: ...HPS COMPRESSOR SOLENOID COIL 24 VOLT FIELD CONNECTIONS CC 208 230V Two Stage Split System Air Conditioner Outdoor Section With ECM Outdoor Motor Single Phase 60 Hz NOTES 1 Disconnect all power before...

Страница 14: ...rcuit See furnace airhandler installation instructions for control circuit and optional relay transformer kits 7 Couper le courant avant de faire letretien 8 Employez uniquement des conducteurs en cui...

Страница 15: ...m 6 Thermostat is malfunctioning Check thermostat sub base or wiring for short circuit Check thermostat installation location level Yellow ALERT Flash Code 2 Compressor Pressure Trip High Refrigerant...

Страница 16: ...ssor bearings are seized Measure compressor oil level Red LOCKOUT Flash Code 5 Yellow Off Compressor Moderate Run Trip 1 Evaporator blower is not running Check blower relay coil and contacts Check blo...

Страница 17: ...17...

Страница 18: ...18...

Страница 19: ...19...

Страница 20: ...allon MO Nortek Global HVAC LLC 2018 All Rights Reserved REPLACEMENT PARTS Replacement parts are available through your distributor Please have the complete model and serial number of the unit when or...

Отзывы: